Navigation

  • Page 1

     Table of contentsTablesFiguresSINUMERIKSINUMERIK 840D sl,SINAMICS S120AlarmsDiagnostics ManualValid for control SINUMERIK 840D sl / 840DE sl Software  versionCNC software  4.5 SP2 SINAMICS  S120    ...

  • Page 2

    Legal information - Warning notice systemLegal informationWarning notice systemThis manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safe...

  • Page 3

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA13PrefaceSINUMERIK documentationThe SINUMERIK documentation is organized in the following categories:• General documentation• User documentation• Manufacturer/service documentationAdditional informationYou can find information on the follo...

  • Page 4

    Preface Alarms4 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINUMERIKYou can find information on SINUMERIK under the following link: actionURI(http://www.siemens.com/sinumerik):www.siemens.com/sinumerikTarget groupThis publication is intended for:• Project engineers• Commissioning engineer...

  • Page 5

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA15Table of contentsTable of contentsPreface.................................................................................................................................................. 3,.......31Introduction ..................................

  • Page 6

    Table of contentsAlarms6 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1

  • Page 7

    1AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA17Introduction1.1Using the Diagnostics ManualThe Diagnostics Manual refers to the alarms / messages from the NC area, HMI, PLC and SINAMICS. It should be used as a reference manual and allows operators at the machine tool:• To correctly asses...

  • Page 8

    Introduction1.2 Structure of the diagnostics manualAlarms8 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1The description of the alarms is classified according to the following categories: • Explanation• ResponseSee Chapter: 15, NC alarms (Page 15, 15)• Remedy• Program continuationSee Cha...

  • Page 9

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA19Introduction1.2 Structure of the diagnostics manual• Axis name and drive number or• Bus and slave number of the PROFIBUS DP component affectedThe place holder <Location data> is kept in the alarm description for this optional informa...

  • Page 10

    Introduction1.3 Alarm number rangesAlarms10 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Synchronization of time and date1.3Alarm number rangesThe following tables show an overview of all of the reserved number ranges for alarms/messages.NoteSynchronization of timeThe SINAMICS drives have no re...

  • Page 11

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA111Introduction1.3 Alarm number rangesTable 1-2HMI alarms/messages100.000 - 139.999System100.000 - 100.999Basic system101.000 - 101.999Diagnostics102.000 - 10.999Services103.000 - 103.999Machine104.000 - 104.999Parameter105.000 - 105.999Programm...

  • Page 12

    Introduction1.3 Alarm number rangesAlarms12 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1231.000 - 231.999DRIVE-CLiQ component encoder 1232.000 - 232.999DRIVE-CLiQ component encoder 2Note:Faults that occur are automatically output as an alarm if the encoder is parameterized as a direct measurin...

  • Page 13

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA113Introduction1.4 System error alarms1.4System error alarmsThe following alarms are system errors:These system error alarms are not described in detail. If such a system error occurs, please contact the hotline and indicate the following detail...

  • Page 14

    Introduction1.4 System error alarmsAlarms14 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1

  • Page 15

    2AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA115NC alarmsProduct: Solutionline_840D, Version: V14.0, Language: engObjects: 1030System error in link module error code %1 error type %2Parameters:%1 = Hex-Zahl Link-Error%2 = Hex-Zahl Link-Error-TypeDefinitions:This alarm is not a user error....

  • Page 16

    NC alarms Alarms16 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Channel not ready.NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm.Remedy:Please inform the authorized personnel/service department. Check monitoring time frame in MD10100 $MN_PLC_CYCLIC_TIM...

  • Page 17

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA117NC alarms In this context please note for the safety function of the '840D sl' that it will switch off the module automatically after a certain time, if the fan is defect or not plugged in; this will protect the NCU from thermal destruction (...

  • Page 18

    NC alarms Alarms18 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Program Continuation:Clear alarm with the Delete key or NC START.21305V/24V encoder or 15V D/A converter undervoltageDefinitions:A failure has occurred in the power supply to the encoder (5V/24V) or D/A converter (+/-15V).Reaction:...

  • Page 19

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA119NC alarms Interface signals are set.Alarm display.NC Stop on alarm.Remedy:Install the hardware module and activate the function again (MD).Program Continuation:Switch control OFF - ON.2193'Safety Integrated' is not available for link axis %1....

  • Page 20

    NC alarms Alarms20 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA12196Link axis active andMD18720 $MN_MM_SERVO_FIFO_SIZE != %1Parameters:%1 = required value in MD18720 $MN_MM_SERVO_FIFO_SIZEDefinitions:Occurs only with an NCU link system.- Possible causes of the fault:- At least one axis is to be...

  • Page 21

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA121NC alarms 3000Emergency stopDefinitions:The EMERGENCY STOP request is applied to the NCK/PLC interface DB10 DBX56.1 (Emergency stop).Reaction:NC not ready.Mode group not ready, also effective for single axes.NC Start disable in this channel.I...

  • Page 22

    NC alarms Alarms22 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA14002[Channel %1: ] Machine data %2[%3] assigns an axis not defined in channelParameters:%1 = Channel number%2 = String: MD identifier%3 = Index: MD array indexDefinitions:Only axes that have been activated in the channel by MD20070...

  • Page 23

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA123NC alarms 4004[Channel %1: ] Machine data %2 axis %3 defined repeatedly as geometry axisParameters:%1 = Channel number%2 = String: MD identifier%3 = Axis indexDefinitions:An axis may only be defined once as a geometry axis.Reaction:Mode group...

  • Page 24

    NC alarms Alarms24 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Please inform the authorized personel/service department. The sum of the two option data $ON_NUM_AXES_IN_SYSTEM and $ON_NUM_ADD_AXES_IN_SYSTEM must not exceed the maximum number of axes (dependent on configuration).Program C...

  • Page 25

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA125NC alarms NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm.Remedy:Please inform the authorized personnel/service department. Enter the identifier for user-defined names with correct syntax in the displ...

  • Page 26

    NC alarms Alarms26 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA14013Invalid NCU link configuration by machine data %1 = %2 , on NCU_1 = %3Parameters:%1 = String: MD identifier%2 = Index: MD array%3 = MD value of master NCUDefinitions:The link module configuration detected on the local NCU is di...

  • Page 27

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA127NC alarms NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm.Remedy:Machine data 35000 $MA_SPIND_ASSIGN_TO_MACHAX must be either != 0 or == 0 for all axes/spindles in an axis container.Program Continuati...

  • Page 28

    NC alarms Alarms28 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Interface signals are set.Alarm display.NC Stop on alarm.Remedy:Correct and complete the container location assignments. Check machine data MD20070 $MC_AXCONF_MACHAX_USED and MD10002 $MN_AXCONF_LOGIC_MACHAX_TAB.Program Continuatio...

  • Page 29

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA129NC alarms 4021[Channel %1: ] Identifier %2 used several times in machine data %3Parameters:%1 = Channel number%2 = String: Name of identifier%3 = String: MD identifierDefinitions:To determine the name in the channel-specific tables for geomet...

  • Page 30

    NC alarms Alarms30 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA14024Invalid axis configuration due to missing axis container machine dataParameters:%1 = NCU number%2 = Axis container numberDefinitions:The axis configuration could not be generated due to missing axis container machine data. This...

  • Page 31

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA131NC alarms Definitions:Message to the user indicating that the machine data change for the axis was also performed for all other axes in the same container.Reaction:Alarm display.Remedy:NoneProgram Continuation:Clear alarm with the Delete key ...

  • Page 32

    NC alarms Alarms32 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA14031[Channel %1: ] Link axis %2 defined for more than one channel in machine data %3Parameters:%1 = Channel number%2 = Index: Axis number for logical axis assignment%3 = String: MD identifierDefinitions:Occurs only with an NCU link...

  • Page 33

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA133NC alarms 4034Local link axis %1 is not allowed for different interpolation cycle time = %2/%3Parameters:%1 = Axis name%2 = Local interpolation cycle%3 = Max. interpolation cycleDefinitions:Local link axes are only permissible on an NCU if th...

  • Page 34

    NC alarms Alarms34 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:- Activate FAST-IPO-LINK function inMD18780 $MN_MM_NCU_LINK_MASK- Or do not set different position control or IPO cycles on the NCUs (see MD10070 $MN_IPO_SYSCLOCK_TIME_RATIO and MD10060 $MN_POSCTRL_SYSCLOCK_TIME_RATIO).Progr...

  • Page 35

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA135NC alarms 4040[Channel %1: ] Axis identifier %2 not consistent with machine data %3Parameters:%1 = Channel number%2 = String: Axis identifier%3 = String: MD identifier%4 = There are not enough channel axes entered in the MD displayed.Definiti...

  • Page 36

    NC alarms Alarms36 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Please inform the authorized personnel/service department.Correct MD10712 $MN_NC_USER_CODE_CONF_NAME_TAB (protection level 1).The list must be built up as follows:Even address: Identifier to be modified.Following odd addres...

  • Page 37

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA137NC alarms 4070Normalizing machine data has been changedDefinitions:The control uses internal physical units (mm, degrees, s, for paths, velocities, acceleration, etc.). During programming or data storage, some of these values are input and ou...

  • Page 38

    NC alarms Alarms38 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA14075Machine data %1 (and maybe others) not changed due to missing permission level %2Parameters:%1 = String: MD identifier%2 = Write protection level of the MDDefinitions:On executing a TOA file or when writing machine data from th...

  • Page 39

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA139NC alarms - Is it possible to expand the memory? This option depends on the model in use. (Not possible if parameter 4 equals "iS").- The NCK user memory may have been set smaller than it could be. With the appropriate access author...

  • Page 40

    NC alarms Alarms40 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA14090Too many errors during power-upDefinitions:More than <n> errors occurred during control power-up.Reaction:NC Start disable in this channel.Alarm display.Remedy:Set the machine data correctly.Program Continuation:Switch co...

  • Page 41

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA141NC alarms 4112Servo cycle changed to %1 msParameters:%1 = String (new servo cycle time)Definitions:For PROFIBUS/PROFINET only:MD10060 $POSCTRL_SYSCLOCK_TIME_RATIO has been modified because of the modified DP cycle in the SDB (MD10050 $SYSCLOC...

  • Page 42

    NC alarms Alarms42 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1- M function for selecting spindle/axis mode according to MD20094 $MC_SPIND_RIGID_TAPPING_M_NR (default: M70),- M functions for nibbling/punching as configured in MD26008 $MC_NIBBLE_PUNCH_CODE if activated by MD26012 $MC_PUNCHNIB_A...

  • Page 43

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA143NC alarms 4170Invalid M function number for channel synchronisation assignedDefinitions:An M number between 0 and 99 has been specified In machine data MD10800 $MN_EXTERN_CHAN_SYNC_M_NO_MIN or MD10802 $MN_EXTERN_CHAN_SYNC_M_NO_MAX for the con...

  • Page 44

    NC alarms Alarms44 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA14182[Channel %1: ] Invalid M auxiliary function number in %2%3, MD resetParameters:%1 = Channel number%2 = MD identifier%3 = If required, MD indexDefinitions:In the specified machine data, a number has been specified for the config...

  • Page 45

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA145NC alarms 4185[Channel %1: ] Illegal auxiliary function configured %2 %3 %4Parameters:%1 = Channel number%2 = Type of auxiliary function%3 = Extension%4 = Auxiliary function valueDefinitions:An auxiliary function has been illegally configured...

  • Page 46

    NC alarms Alarms46 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Please inform the authorized personnel/service department. Set rotary axis declaration for this machine axis in the axis-specific MD30300 $MA_IS_ROT_AX.Program Continuation:Switch control OFF - ON.4215[Channel %1: ] Spindle ...

  • Page 47

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA147NC alarms 4230[Channel %1: ] Data alteration from external not possible in current channel stateParameters:%1 = Channel numberDefinitions:It is not allowed to enter this data while the part program is being executed (e.g. setting data for wor...

  • Page 48

    NC alarms Alarms48 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Check machine data MD10394 $MN_PLCIO_NUM_BYTES_IN / MD10395 $MN_PLCIO_LOGIC_ADDRESS_IN.Check PLC hardware configuration.Check whether 'technological function' already uses the functionality.Program Continuation:Clear alarm w...

  • Page 49

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA149NC alarms Activation of fast inputs/outputs does not require the corresponding hardware configuration to be available at the con-trol. All functions using fast inputs/outputs can also be made use of by the PLC specification/modification defin...

  • Page 50

    NC alarms Alarms50 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Please inform the authorized personnel/service department. Alter MD10368 $MN_HW_ASSIGN_DIG_FASTOUT or MD10364 $MN_HW_ASSIGN_ANA_FASTOUT.Program Continuation:Switch control OFF - ON.4285Error on terminal block %1, error code ...

  • Page 51

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA151NC alarms 4300Declaration in MD %1 is not allowed for axis %2.Parameters:%1 = String: MD identifier%2 = Axis name, spindle numberDefinitions:The axis cannot be operated as competing positioning axes,for example because the axis is the slave a...

  • Page 52

    NC alarms Alarms52 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:The maximum permissible value of the fine correction in an orientable toolholder is limited by the MD20188 $MC_TOCARR_FINE_LIM_LIN for linear variables, and by the MD20190 $MC_TOCARR_FINE_LIM_ROT for rotary variables. T...

  • Page 53

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA153NC alarms Alarm display.NC Stop on alarm at block end.Remedy:Enter a valid transformation type.Program Continuation:Clear alarm with the RESET key. Restart part program4341[Channel %1: ] Block %2 no data set available for transformation no. %...

  • Page 54

    NC alarms Alarms54 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA14343[Channel %1: ] Attempt made to change the machine data of an active transformation.Parameters:%1 = Channel numberDefinitions:An attempt was made to change the machine data of an active transformation and to activate the machine...

  • Page 55

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA155NC alarms 4346[Channel %1: ] Invalid geoaxis assignment in machine data %2[%3]Parameters:%1 = Channel number%2 = Name of machine data%3 = Transformation numberDefinitions:MD2.... $MC_TRAFO_GEOAX_ASSIGN_TAB_... contains an invalid entry. The f...

  • Page 56

    NC alarms Alarms56 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1- 12. The rotary axis defined in $NT_ROT_AX_NAME[n,2] was not found in any of the relevant kinematic chains.- 20. The linear axis defined in $NT_GEO_AX_NAME[n,0] was not found in any of the relevant kinematic chains.- 21. ...

  • Page 57

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA157NC alarms 4350[Channel %1: ] Axis identifier %2 machine data %3 not consistent with machine data %4Parameters:%1 = Channel number%2 = String: Axis identifier%3 = String: MD identifier%4 = String: MD identifierDefinitions:MD32420 $MA_JOG_AND_P...

  • Page 58

    NC alarms Alarms58 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA14502[Channel %1: ] Anachronism %2(%3) -> %4Parameters:%1 = Channel number%2 = String: MD identifier%3 = String: MD identifier%4 = String: MD identifierDefinitions:Previously, in MD20110 $MC_RESET_MODE_MASK Bit4 and Bit5, the res...

  • Page 59

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA159NC alarms 4611Invalid handwheel input for handwheel %1Parameters:%1 = Handwheel inputDefinitions:For SINUMERIK 840D and SINUMERIK 840Di only:The handwheel input for handwheel %1 requested through MD11352 $MN_HANDWHEEL_INPUT is not available f...

  • Page 60

    NC alarms Alarms60 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA14631Invalid handwheel slot for handwheel %1Parameters:%1 = Handwheel slotDefinitions:For PROFIBUS/PROFINET only:The handwheel slot for handwheel %1 requested through machine data $MN_HANDWHEEL_INPUT is not available for PROFIBUS ha...

  • Page 61

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161NC alarms 4700PROFIBUS I/O: The logical slot / I/O area address %1 was not found.Parameters:%1 = Area addressDefinitions:For PROFIBUS/PROFINET only:The logical slot / I/O area address was not found in MD10500 $MN_DPIO_LOGIC_ADDRESS_IN with th...

  • Page 62

    NC alarms Alarms62 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Redefine the NC memory structure!A specific MD for NC user memory allocation cannot be stated to be the cause of the alarm. The MD initiating the alarm therefore has to be determined on the basis of the default values in the...

  • Page 63

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA163NC alarms - _N_AXa_SEA - System internal: setting data, axial- _N_AXa_TEA - System internal: machine data, axial- _N_AXa_EEC - System internal: leadscrew error compensation data, axial- _N_AXa_QEC - System internal: quadrant error compensatio...

  • Page 64

    NC alarms Alarms64 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA16030Limit of user memory has been adaptedDefinitions:Data management checks during power-up the actually available physical user memory (DRAM, DPRAM and SRAM) with the values in the system-specific machine data MD18210 $MN_MM_USER_...

  • Page 65

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA165NC alarms Remedy:- Error number 1: The memory reserved by MD18238 $MN_MM_CC_MD_MEM_SIZE has to be increased. If the error occurs while loading an archive, then the machine data must be increased "manually". To do this, either Edit t...

  • Page 66

    NC alarms Alarms66 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:- Check whether the magazine data have been defined correctly.- Check whether the magazine is connected to the desired tool holder/spindle via a distance relation.- The user PLC program may have sent wrong data to the NCK.Pr...

  • Page 67

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA167NC alarms 7 Terminate canceled tool command8 Check tool movement with reservation9 Check tool movement0 Transport acknowledgementParameters 2 and 3 designate the PLC command and the status number of the acknowledgement.Example: Parameter 4 of...

  • Page 68

    NC alarms Alarms68 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:A tool change request or a verification request was issued to put the tool in a location which does not satisfy the pre-requisites for filling.The following causes for the error are possible:- Location is blocked or not...

  • Page 69

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA169NC alarms 6412[TO unit %1: ] Tool %2 has reached its monitoring limit with D = %4Parameters:%1 = TO unit%2 = Tool identifier (name)%3 = -Not used-%4 = D numberDefinitions:Tool monitoring: This message informs that the specified D offset has r...

  • Page 70

    NC alarms Alarms70 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA16416[Channel %1: ] Tool %2 with tool edge no. %3 has reached tool monitor warning limitParameters:%1 = Channel number%2 = Tool identifier%3 = Cutting edge numberDefinitions:This message informs that at least one cutting edge of the...

  • Page 71

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA171NC alarms Remedy:- Check whether the magazine data have been defined correctly (e.g. the magazine must not be disabled).- Check whether the tool data are correctly defined (for example, the tool location type must match the location types all...

  • Page 72

    NC alarms Alarms72 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA16425[Channel %1: ] Tool %2 cannot be placed in magazine %3 on location %4. Invalid definition of magazine!Parameters:%1 = Channel ID%2 = String (identifier)%3 = Magazine number%4 = Magazine location numberDefinitions:The desired to...

  • Page 73

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA173NC alarms Definitions:Occurs when a data management function is called which is not available because ToolMan is deactivated. For exam-ple, the language commands GETT, SETPIECE, GETSELT, NEWT, DELT, TCA.Reaction:Correction block is reorganize...

  • Page 74

    NC alarms Alarms74 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Correct the NC program (delete or replace SETMHT) or enable toolholder function via machine data.Program Continuation:Clear alarm with NC START or RESET key and continue the program.6436[Channel %1: ] Block %2 command '%3' c...

  • Page 75

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA175NC alarms 6442[Channel %1: ] Function not executable. No tool assigned to desired magazine/magazine location %2.Parameters:%1 = Channel ID%2 = Magazine/magazine location no.Definitions:PLC logic is presumably incorrect. Tool change with rejec...

  • Page 76

    NC alarms Alarms76 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA16452[Channel %1: ] Block %2 tool change not possible. Tool holder/spindle number = %3 not defined.Parameters:%1 = Channel ID%2 = Block number, label%3 = Tool holder/spindle numberDefinitions:The desired tool change is not possible....

  • Page 77

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA177NC alarms %4 = Magazine numberDefinitions:The desired tool change is not possible. The indicated magazine location is not available in the indicated magazine.Reaction:Correction block is reorganized.Interface signals are set.Alarm display.Rem...

  • Page 78

    NC alarms Alarms78 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA16510Too many part programs in the NC memoryDefinitions:The maximum number of possible files in the NC file system (part of the NC memory) has been reached. Note: During first commissioning, this can affect files from the NC file sy...

  • Page 79

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA179NC alarms 6560Data format not allowedDefinitions:An attempt was made to write impermissible data in an NCK file. This error can occur in particular when the attempt was made to load binary data in the NCK as ASCII file.The error can also occu...

  • Page 80

    NC alarms Alarms80 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA16583NC system memory fullDefinitions:The DRAM file system of the system area (Siemens) is full. The order cannot be executed.Reaction:Alarm display.Remedy:Delete or unload files (e.g. parts programs)Program Continuation:Clear alarm...

  • Page 81

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA181NC alarms 7000Too many compile cycle alarms definedDefinitions:Too many alarms are defined for the compile cycles. On powering up, the quantity was exceeded when defining a new CC alarm.Reaction:Alarm display.Remedy:Apart from reducing the nu...

  • Page 82

    NC alarms Alarms82 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA17200Problem with externally linked compile cycle %1 %2Parameters:%1 = Description character string%2 = Additional informationDefinitions:Problem with loadable compile cyclesExample: "Version_conflict_with_CCNCKInterface_Versio...

  • Page 83

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA183NC alarms Definitions:Alarm for SIEMENS compile cycles. This alarm appears when a SIEMENS compile cycle has been loaded that has not been released for the controller. The "Index" parameters describe the error cause further:Index == ...

  • Page 84

    NC alarms Alarms84 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Index == 1: The COA application is not executable in the current environment. Please inform the authorized personnel/service department.Index == 2 or 3: Check MD18235 $MN_MM_INCOA_MEM_SIZE. The memory requested by the COA ap...

  • Page 85

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA185NC alarms Remedy:Please inform the authorized personnel/service department. Do not use rapid interrupt inputs or contact the machine manufacturer with a view to retrofitting this option!Program Continuation:Clear alarm with the RESET key. Res...

  • Page 86

    NC alarms Alarms86 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA18021Option 'activation of more than %1 mode groups' not setParameters:%1 = Number of mode groupsDefinitions:The option for the number of mode groups is not compatible with the activated mode group.Reaction:NC Start disable in this ...

  • Page 87

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA187NC alarms 8025[Channel %1: ] Option 'Advanced Surface' not setParameters:%1 = Channel numberDefinitions:The option for 'Advanced Surface' functionality is not set.Reaction:NC Start disable in this channel.Interface signals are set.Alarm displ...

  • Page 88

    NC alarms Alarms88 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1NC Start disable in this channel.Interface signals are set.Alarm display.Remedy:- Buy option- Configure fewer link axesProgram Continuation:Clear alarm with the RESET key. Restart part program8034Option 'activation of axis containe...

  • Page 89

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA189NC alarms 8038Option 'activation of more than %1 lead link axes' not setParameters:%1 = Number of axesDefinitions:The option for the number of lead link axes does not match the number of configured axes in the MD30554 $MA_AXCONF_ASSIGN_MASTER...

  • Page 90

    NC alarms Alarms90 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1- Option-free >= 8ms- 1. 1st step >= 6ms- 2. 2nd step >= 4ms- 3. 3rd step >= 2ms- 4. 4th step <2msReaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:- Buy option-...

  • Page 91

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA191NC alarms 8080%1 option(s) is/are activated without setting the license keyParameters:%1 = Number of non-licensed optionsDefinitions:One or more options were activated but no license key was set to prove the purchase of the option(s).Reaction...

  • Page 92

    NC alarms Alarms92 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Select a tool of type 4xx (grinding tool)or install a standard version of the system softwareProgram Continuation:Clear alarm with the RESET key. Restart part program8098Invalid combination of options (%1)Parameters:%1 = Bit...

  • Page 93

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA193NC alarms Remedy:1. Buy an adequate option stage.2. Reduce the number of 3D protection zones.3. Avoid impermissible protection zone types.Program Continuation:Clear alarm with the RESET key. Restart part program8102[Channel %1: ] Block %2 mot...

  • Page 94

    NC alarms Alarms94 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Restore connection to PROFIBUS handwheelProgram Continuation:Alarm display showing cause of alarm disappears. No further operator action necessary.9050PROFIBUS I/O: Sign of life failure, logical slot / I/O area address %1Par...

  • Page 95

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA195NC alarms 10204[Channel %1: ] User action not possible without reference point (internal action=%2<ALNX>)Parameters:%1 = Channel number%2 = internal action number/internal action nameDefinitions:A specific user action is to be executed...

  • Page 96

    NC alarms Alarms96 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1- Search alarm 10208 has been suppressed by the PI service _N_FINDBL (third decade of the parameter supplied with "2"). Alarm 10209 is set as a function of whether or not a search ASUB has been configured (MD11450 $MN_SEA...

  • Page 97

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA197NC alarms Alarm display.NC Stop on alarm.Remedy:Rectify the problem indicated by the other alarms, and press RESET again.Program Continuation:Clear alarm with the RESET key. Restart part program10261[Channel %1: ] Communication overload for b...

  • Page 98

    NC alarms Alarms98 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:This alarm occurs only when several blocks with G33 follow in succession. The block end velocity in the specified block is zero, although a further thread cutting block follows. The reasons for this can be, for instance...

  • Page 99

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA199NC alarms Alarm display.Remedy:Reduce the thread pitch decrease or path length in the NC program.Program Continuation:Clear alarm with NC START or RESET key and continue the program.10607[channel %1: ] block %2 thread with frame cannot be exe...

  • Page 100

    NC alarms Alarms100 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1%4 = StringDefinitions:During the traversing motion, the system detected that the software limit switch would be traversed in the direction indicated. Exceeding the traversing range was not detected during block preparation becaus...

  • Page 101

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1101NC alarms 10631[Channel %1: ] Axis %2 rests at working area limit %3%4Parameters:%1 = Channel number%2 = Axis, spindle%3 = String (+ or -)%4 = The axis of the working area limitation is only output if different from the traversing axis.Defin...

  • Page 102

    NC alarms Alarms102 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:The tool radius compensation of the working area limitation of the stated axis is not taken into account.Reason: The tool is not oriented parallel to the axis (e.g. because toolcarrier or transformation is active).The ...

  • Page 103

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1103NC alarms 10650[Channel %1: ] Axis %2 incorrect gantry machine data, error code %3Parameters:%1 = Channel number%2 = Axis%3 = Error no.Definitions:An incorrect value was entered in the gantry-specific axial machine data. Further information ...

  • Page 104

    NC alarms Alarms104 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA110652[Channel %1: ] Axis %2 gantry warning threshold exceededParameters:%1 = Channel number%2 = AxisDefinitions:The gantry following axis has exceeded the warning limit specified in MD37110 $MA_GANTRY_POS_TOL_WARNING.Reaction:Alar...

  • Page 105

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1105NC alarms Definitions:The alarm may be suppressed with MD37150 $MA_GANTRY_FUNCTION_MASK Bit2 = 1.Reaction:Alarm display.Remedy:--Program Continuation:Alarm display showing cause of alarm disappears. No further operator action necessary.10656...

  • Page 106

    NC alarms Alarms106 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1- 60XX => Gantry group is to be transferred to the channel due to an NC program request, but the channel does not know all the gantry axes.- 70XX => Gantry group cannot be closed, as movement is pending for at least one gant...

  • Page 107

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1107NC alarms 10702[Channel %1: ] NCK protection zone %2 violated during manual modeParameters:%1 = Channel number%2 = Protection zone numberDefinitions:The workpiece-related NCK protection zone has been violated. Note that another tool-related ...

  • Page 108

    NC alarms Alarms108 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Please inform the authorized personnel/service department. Protection zone can be traversed after enable signal from PLC.Program Continuation:Alarm display showing cause of alarm disappears. No further operator action neces...

  • Page 109

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1109NC alarms If bit 11=0 in the machine data MD11411 $MN_ENABLE_ALARM_MASK, this alarm is issued instead of alarm 10722. If bit 11 is set in the machine data MD11411 $MN_ENABLE_ALARM_MASK, an expanded diagnostics option is offered for the softw...

  • Page 110

    NC alarms Alarms110 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:The path programmed for the axis violates the currently valid software limit switch. The alarm is activated when pre-paring the part program block.This alarm is issued instead of alarm 10720 if bit 11=1 in the MD11411 ...

  • Page 111

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1111NC alarms Definitions:This alarm is generated if it is determined during block preparation that the programmed path of the axis violates the working area limitation.If bit 11=0 in machine data MD11411$MN_ENABLE_ALARM_MASK, this alarm is issu...

  • Page 112

    NC alarms Alarms112 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:a) Check NC program for correct positional data and, if necessary, make corrections.b) Check work offsets (current frame)c) Correct working area limitation via G25/G26, ord) Correct working area limitation via setting data,...

  • Page 113

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1113NC alarms 10736[Channel %1: ] Block %5 axis %2 coordinate system-specific working area limitation violated, residual distance: %6 %3<ALUN>Parameters:%1 = Channel number%2 = Axis name, spindle number%3 = Unit of distance%4 = Block numbe...

  • Page 114

    NC alarms Alarms114 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:Possible causes:In a WAB block, the parameter DISR has not been specified or its value is less than or equal to 0.During approach or retraction with circle and active tool radius, the radius of the internally generated...

  • Page 115

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1115NC alarms Interface signals are set.Alarm display.NC Stop on alarm at block end.Remedy:Modify part program. Either remove the position data for the infeed axis from the WAB block or the following block, or program a position in the machining...

  • Page 116

    NC alarms Alarms116 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Modify part programProgram Continuation:Clear alarm with NC START or RESET key and continue the program.10750[Channel %1: ] Block %2 tool radius compensation activated without tool numberParameters:%1 = Channel number%2 = B...

  • Page 117

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1117NC alarms The size of the buffer is fixed by the system and cannot be changed via the MDs.Reaction:Correction block is reorganized.Local alarm reaction.Interface signals are set.Alarm display.NC Stop on alarm at block end.Remedy:Please infor...

  • Page 118

    NC alarms Alarms118 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA110755[Channel %1: ] Block %2 selection of the tool radius compensation via KONT not possible at the current starting pointParameters:%1 = Channel number%2 = Block number, labelDefinitions:When activating the cutter radius compensa...

  • Page 119

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1119NC alarms Definitions:An orientation change has been programmed which is not permissible with the tool radius compensation type (G code of group 22). As a rule, changes to the tool orientation are only permissible and useful if 3D tool radiu...

  • Page 120

    NC alarms Alarms120 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA110760[Channel %1: ] Block %2 helical axis is not parallel to tool orientationParameters:%1 = Channel number%2 = Block number, labelDefinitions:With active tool radius compensation a helix is only permissible if the helix axis is p...

  • Page 121

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1121NC alarms 10763[Channel %1: ] Block %2 path component of the block in the compensation plane becomes zeroParameters:%1 = Channel number%2 = Block number, labelDefinitions:Due to collision monitoring with active tool radius compensation, the ...

  • Page 122

    NC alarms Alarms122 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:This alarm occurs with 3D face milling when, at the time of block transition, the surface defined in the first block is continued in the second block with the rear side of the surface defined there. The block number in...

  • Page 123

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1123NC alarms 10769[Channel %1: ] Block %2 Illegal surface normal vector with 3D tool radius compensationParameters:%1 = Channel number%2 = Block number, labelDefinitions:In 3D face milling, surface normal vector and path tangent vector must the...

  • Page 124

    NC alarms Alarms124 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA110772[Channel %1: ] Block %2 illegal orientation change when activating or deactivating 3D face cuttingParameters:%1 = Channel number%2 = Block number, labelDefinitions:In face milling, no intermediate blocks with pure orientation...

  • Page 125

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1125NC alarms Definitions:This alarm occurs when a tool change has been programmed while 3D tool radius compensation is active with the result that the tool type changes or, if the tool type remains unchanged, at least one relevant tool dimensio...

  • Page 126

    NC alarms Alarms126 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA110778[Channel %1: ] Block %2 preprocessing stop with active tool radius compensationParameters:%1 = Channel number%2 = Block number, labelDefinitions:If a preprocessing stop is detected with active tool radius compensation (either...

  • Page 127

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1127NC alarms 10781[Channel %1: ] Block %2 illegal orientation of involute with tool radius compensationParameters:%1 = Channel number%2 = Block number, labelDefinitions:Tool radius compensation is possible for involutes only if the compensation...

  • Page 128

    NC alarms Alarms128 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:When activating the tool radius compensation with constraint surface, an illegal tool type is active.Only cutting tools of the tool types 1 to 399 are admitted with the following exceptions:- 111 ball end milling cutt...

  • Page 129

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1129NC alarms Local alarm reaction.Interface signals are set.Alarm display.NC Stop on alarm at block end.Remedy:Modify part program.Program Continuation:Clear alarm with NC START or RESET key and continue the program.10793[Channel %1: ] Block %2...

  • Page 130

    NC alarms Alarms130 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Correction block is reorganized.Local alarm reaction.Interface signals are set.Alarm display.NC Stop on alarm at block end.Remedy:Modify part program.Program Continuation:Clear alarm with NC START or RESET key and continu...

  • Page 131

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1131NC alarms For the definition the MD 20090 $MC_SPIND_DEF_MASTER_SPIND is available for the default or the keyword SETMS in the part program, thus allowing each spindle of the channel to be redefined as master spindle.Reaction:Correction block...

  • Page 132

    NC alarms Alarms132 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1- G96: The feedrate is programmed as cutting rate under address S in [m/min]. It is derived from the current spindle speed.Program Continuation:Clear alarm with NC START or RESET key and continue the program.10861[Channel %1: ] Bl...

  • Page 133

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1133NC alarms 10866[Channel %1: ] Block %2 FZ is active, but the number of teeth of the active D number %4 of tool %3 is zero.Parameters:%1 = Channel number%2 = Block number, label%3 = Identifier%4 = D numberDefinitions:Tooth feedrate is active ...

  • Page 134

    NC alarms Alarms134 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Correction block is reorganized.Local alarm reaction.Interface signals are set.Alarm display.Remedy:Please inform the authorized personnel/service department. Modify the part program in order that the permissible number o...

  • Page 135

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1135NC alarms Reaction:Local alarm reaction.Interface signals are set.Alarm display.NC Stop on alarm at block end.Remedy:Modify NC program of continue program without modifications after CANCEL and Start or with Start alone.Program Continuation:...

  • Page 136

    NC alarms Alarms136 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA110910[Channel %1: ] Block %2 irregular velocity waveform of one path axisParameters:%1 = Channel number%2 = Block number, labelDefinitions:When the path axis waveforms were analyzed during block preparation, a large local deviatio...

  • Page 137

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1137NC alarms 10913[Channel %1: ] Block %2 negative feed profile is ignoredParameters:%1 = Channel number%2 = Block number, labelDefinitions:The given feed profile is in part negative. However, negative path feed is not allowed. The feed profile...

  • Page 138

    NC alarms Alarms138 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA110916[Channel %1: ] Block %2 Preparation problem in LookAhead (Identifier %3, Details %4)Parameters:%1 = Channel number%2 = Block number, label%3 = Error code%4 = Error detailsDefinitions:The NCK was incorrectly parameterized (un...

  • Page 139

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1139NC alarms NC Start disable in this channel.Interface signals are set.Alarm display.Remedy:Program the keyword EXECUTE to terminate the contour preparation in the part program before again calling up con-tour segmentation (keyword CONTPRON).P...

  • Page 140

    NC alarms Alarms140 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Program Continuation:Clear alarm with the RESET key. Restart part program10941[Channel %1: ] Block %2: Curve table %3: NC SRAM memory full, type %4Parameters:%1 = Channel number%2 = Block number, label%3 = Number of curve table%4 ...

  • Page 141

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1141NC alarms Alarm display.Remedy:Correct the part program and start it again.Program Continuation:Clear alarm with the RESET key. Restart part program10944[Channel %1: ] Block %2 curve table %3: illegal transformationParameters:%1 = Channel nu...

  • Page 142

    NC alarms Alarms142 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:The contour in a curve table must be continuous. Incontinuity can occur, for example, as a result of activating a trans-formation.Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alar...

  • Page 143

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1143NC alarms 10951[Channel %1: ] Block %2 curve table %3: following value period is zeroParameters:%1 = Channel number%2 = Block number, label%3 = Number of curve tableDefinitions:--Reaction:Alarm display.Remedy:Ensure that the table specificat...

  • Page 144

    NC alarms Alarms144 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:On generating the curve table with the specified ID in the specified memory type(1 = SRAM, 2 = DRAM), polynomial segments were used instead of possible linear segments.By increasing the number of linear curve table seg...

  • Page 145

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1145NC alarms Definitions:With this software release, the specified function can not yet be used together with tool radius compensation. Please modifiy the part program or obtain a higher software version.Reaction:Correction block is reorganized...

  • Page 146

    NC alarms Alarms146 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Modify part program or set MD28590 $MC_MM_ORISON_BLOCKS >= 3.Program Continuation:Clear alarm with NC START or RESET key and continue the program.12000[Channel %1: ] Block %2 address %3 programmed repeatedlyParameters:%1...

  • Page 147

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1147NC alarms Remedy:Key: Press the NC STOP key and select the function "Correction block" with the softkey PROGRAM CORRECT. The correction pointer is then positioned on the incorrect block.Apply non-modal address modifications only fo...

  • Page 148

    NC alarms Alarms148 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:The name of the DIN address (e.g. X, U, X1) is not defined in the control. In addition to the fixed DIN addresses, the control also has variable addresses. Refer to "Variable addresses" in the Programming Gui...

  • Page 149

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1149NC alarms Definitions:The grammar in this block is incorrect at the text position indicated. The precise reason for this error cannot be spec-ified in more detail because there are too many possibilities.Example 1:N10 IF GOTOF ... ; the cond...

  • Page 150

    NC alarms Alarms150 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA112110[Channel %1: ] Block %2 block syntax cannot be interpretedParameters:%1 = Channel number%2 = Block number, labelDefinitions:The addresses programmed in the block are not permissible together with the valid syntax defining G f...

  • Page 151

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1151NC alarms 12140[Channel %1: ] Block %2 functionality %3 not implementedParameters:%1 = Channel number%2 = Block number, label%3 = Software construct in the source textDefinitions:In the full configuration of the control functions are possibl...

  • Page 152

    NC alarms Alarms152 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Press the NC Stop key and select the function "Correction block" with the softkey PROGRAM CORRECT. The cor-rection pointer positions on the incorrect block.Correct value of the constant or adapt data type. If the ...

  • Page 153

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1153NC alarms 20 Moment of inertia [kgm²]21 Per cent22 Frequency [Hz]23 Voltage [V]24 Current [A]25 Temperature [degrees Celsius]26 Angle [degrees]27 KV [ 1000/min ]28 Linear or angluar position [mm|deg or inch|deg]29 Cuttin...

  • Page 154

    NC alarms Alarms154 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:The language commands APW and APR are used to program access protection for access to both the part program and the OPI. APWP and APRP define access protection from the part program; APWB and APRB define access pro-tec...

  • Page 155

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1155NC alarms Definitions:A bit combination is not possible with the assignment to this address. Bit combinations are permitted only for coupling adresses ( CPMBRAKE, CPMVDI and CPMAL ).Reaction:Correction block is reorganized.Interface signals ...

  • Page 156

    NC alarms Alarms156 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Interface signals are set.Alarm display.Remedy:Complete the area specification for the GUD variable definition in the GUD definition file.The definition of a GUD variable must conform to the following syntax:DEF <Area> <D...

  • Page 157

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1157NC alarms Definitions:A string can also contain bytes that do not correspond to a character that can be entered or one that is available on a keyboard with a minimized number of keys. These characters can be input as binary or hexadecimal co...

  • Page 158

    NC alarms Alarms158 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA112260[Channel %1: ] Block %2 too many initialization values specified %3Parameters:%1 = Channel number%2 = Block number, label%3 = Source stringDefinitions:In the initialization of an array (array definition and value assignments ...

  • Page 159

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1159NC alarms Remedy:Press the NC Stop key and select the function "Correction block" with the softkey PROGRAM CORRECT. The cor-rection pointer positions on the incorrect block.Select DEFINE instruction with another macro name.Program ...

  • Page 160

    NC alarms Alarms160 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1 :M17ENDPROCMain program:N10 DEF INT XN11 DEF INT YN11 DEF INT Z :N50 XYZ (X, Y); REF parameter Z missingorN50 XYZ (X, Z) ; REF parameter Z missing!Reaction:Correction block is reorganized.Interface signals are set.Alarm display.R...

  • Page 161

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1161NC alarms Definitions:A constant or the result of a mathematical expression has been assigned to a REF parameter instead of a variable at the time of the subroutine call, even though only variable identifiers are allowed.Examples:N10 XYZ (NA...

  • Page 162

    NC alarms Alarms162 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Correction block is reorganized.Interface signals are set.Alarm display.Remedy:Press the NC Stop key and select the function "Correction block" with the softkey PROGRAM CORRECT. The cor-rection pointer positions...

  • Page 163

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1163NC alarms Definitions:A variable has been initialized with a value range outside an initialization block. The definition of program-global vari-ables is allowed only in special initialization blocks. These variables can be initialized with a...

  • Page 164

    NC alarms Alarms164 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Interface signals are set.Alarm display.Remedy:Press the NC Stop key and select the function "Correction block" with the softkey PROGRAM CORRECT. The cor-rection pointer positions on the incorrect block.- Define variable...

  • Page 165

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1165NC alarms 12420[Channel %1: ] Block %2 identifier %3 too longParameters:%1 = Channel number%2 = Block number, labelDefinitions:The symbol to be defined or the specified jump target has a name which is longer than the 32 characters allowed.Re...

  • Page 166

    NC alarms Alarms166 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:The label of this block already exists.If the NC program is compiled off-line, the entire program is compiled block for block. During this procedure all multiple labels are recognized; this is not always the case with ...

  • Page 167

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1167NC alarms Alarm display.Remedy:Press the NC Stop key and select the function "Correction block" with the softkey PROGRAM CORRECT. The cor-rection pointer positions on the incorrect block. You should decide on the basis of the machi...

  • Page 168

    NC alarms Alarms168 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Press button NC STOP and select the function "Compensation block" using softkey PROGAM CORRECT. The cursor jumps to the incorrect block. Then delete the invalid program attribute.Program Continuation:Clear alarm w...

  • Page 169

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1169NC alarms Definitions:The displayed keyword may not be used in this type of block and at this location (all files in the NCK are designated as blocks).Block types:Program blockContains a main program or subroutineData blockContains macro or ...

  • Page 170

    NC alarms Alarms170 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Correction block is reorganized.Interface signals are set.Alarm display.Remedy:Press the NC Stop key and select the function "Correction block" with the softkey PROGRAM CORRECT. The cor-rection pointer positions...

  • Page 171

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1171NC alarms Macro: The keyword, to be defined with the DEFINE ... AS ... instruction, is missing in one of the files:_N_SMAC_DEF_N_MMAC_DEF_N_UMAC_DEF_N_SGUD_DEF_N_MGUD_DEF_N_UGUD_DEFVariable: DEF instruction is missingProgram: PROC declaratio...

  • Page 172

    NC alarms Alarms172 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Press the NC Stop key and select the "Compensation block" function by pressing the PROGRAM CORRECT softkey. The cursor positions itself on the incorrect block.- Correct the name used (in the case of a typing error...

  • Page 173

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1173NC alarms Definitions:The name of the symbol to be created is part of the NC language scope and therefore already known. Although the NC function is not active, this name can no longer be used for GUDs, macros and PROC definitions.Reaction:C...

  • Page 174

    NC alarms Alarms174 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:The predefined subprogram %3 specified here is not allowed in a block with motion synchronous action. It may only be contained in a "normal" block.Reaction:Correction block is reorganized.Interface signals ar...

  • Page 175

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1175NC alarms 12581[Channel %1: ] Block %2 invalid read access to %3 while in motion synchronous actionParameters:%1 = Channel number%2 = Block number, label%3 = Source symbolDefinitions:In a motion synchronous action, the displayed variable mus...

  • Page 176

    NC alarms Alarms176 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA112584[Channel %1: ] Block %2 variable %3 cannot be read synchronously with motionParameters:%1 = Channel number%2 = Block number, label%3 = Source symbolDefinitions:In motion synchronous actions on the left side of the compare ope...

  • Page 177

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1177NC alarms Remedy:Modify part program: Use variables of the same type.Program Continuation:Clear alarm with NC START or RESET key and continue the program.12587[Channel %1: ] Block %2 motion synchronous action: operation/function %3 not allow...

  • Page 178

    NC alarms Alarms178 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Interface signals are set.Alarm display.Remedy:Modify part program: Replace the on-line variable by an arithmetic variable.Program Continuation:Clear alarm with NC START or RESET key and continue the program.12590[Channel %1: ] Bl...

  • Page 179

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1179NC alarms 12620[Channel %1: ] Block %2 accessing this variable as single character not possible %3Parameters:%1 = Channel number%2 = Block number, label%3 = Source stringDefinitions:The variable is not a user-defined variable. The single cha...

  • Page 180

    NC alarms Alarms180 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Correct part program. If necessary, move parts to a subroutine.Program Continuation:Clear alarm with the RESET key. Restart part program12650[Channel %1: ] block %2 axis identifier %3 different in channel %4Parameters:%1 =...

  • Page 181

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1181NC alarms Remedy:Modify part program.Program Continuation:Clear alarm with NC START or RESET key and continue the program.12700[Channel %1: ] Block %2 contour definition programming not allowed as modal sub-programis activeParameters:%1 = Ch...

  • Page 182

    NC alarms Alarms182 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA112720[Channel %1: ] Block %2 program number for macro call (G65/G66) missingParameters:%1 = Channel number%2 = Block number, labelDefinitions:During macro call with G65/G66 no program number was defined. The program number must be...

  • Page 183

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1183NC alarms Remedy:For plane selection with G17, G18, G19 either program the basic axis of the coordinate system or the assigned parallel axis.Program Continuation:Clear alarm with NC START or RESET key and continue the program.12728[Channel %...

  • Page 184

    NC alarms Alarms184 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Splitting the T word is determined by the machine dates 10888 $MN_EXTERN_DIGITS_TOOL_NO and 10889 $MN_EXTERN_DIGITS_OFFSET_NO. However, only one of the two functions may be active, and at least one func-tion must be active. Alarm ...

  • Page 185

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1185NC alarms Definitions:After system-internal data manipulation (e.g. when reloading from an external source) a part file can end without hav-ing LF as the last character.Reaction:Interpreter stopNC Start disable in this channel.Interface sign...

  • Page 186

    NC alarms Alarms186 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA114009[Channel %1: ] Block %2 illegal program path %3Parameters:%1 = Channel number%2 = Block number, label%3 = Program pathDefinitions:The part program command CALLPATH was called with a parameter (program path) referring to a dir...

  • Page 187

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1187NC alarms Remedy:Ensure that the subroutine (alarm parameter %3)- is available in the parts program memory- has been released and is not being edited- is available in the search path if not being called via an absolute path name.Program Cont...

  • Page 188

    NC alarms Alarms188 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA114015[Channel %1: ] Block %2 program %3 is not enabledParameters:%1 = Channel number%2 = Block number, label%3 = Program nameDefinitions:The execution right currently set in the control (e.g. key switch position 0) is inadequate t...

  • Page 189

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1189NC alarms 14018[Channel %1: ] Block %2 parts program command %3 not executable (protection level setpoint value / actual value: %4)Parameters:%1 = Channel number%2 = Block number, label%3 = Programmed command%4 = Protection level of the comm...

  • Page 190

    NC alarms Alarms190 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:- An illegal parameter value was specified in a function or procedure call.- An illegal number of actual parameters was programmed in a function or procedure call.Reaction:Interpreter stopNC Start disable in this chann...

  • Page 191

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1191NC alarms 14027[Channel %1: ] Block %2 motion-synchronous action: Too many technology cycles programmed.Parameters:%1 = Channel number%2 = Block number, labelDefinitions:You can call a maximum of eight technology cycles with one motion-synch...

  • Page 192

    NC alarms Alarms192 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA114034[Channel %1: ] Block %2 involute: angle of rotation too largeParameters:%1 = Channel number%2 = Block number, labelDefinitions:With programming of the angle of rotation (with AR) for involute interpolation, the maximum progra...

  • Page 193

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1193NC alarms 14038[Channel %1: ] Block %2 involute not definable: end point errorParameters:%1 = Channel number%2 = Block number, labelDefinitions:The programmed end point does not lie on the involute defined by the start point, radius and cent...

  • Page 194

    NC alarms Alarms194 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA114045[Channel %1: ] Block %2 error in tangential circle programmingParameters:%1 = Channel number%2 = Block number, labelDefinitions:The alarm may have the following causes:The tangent direction is not defined for tangent circle, ...

  • Page 195

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1195NC alarms - In a data type, the representable value range has been exceededReaction:Correction block is reorganized.Interface signals are set.Alarm display.Remedy:Analyze the program and correct the defective point in the program.Program Con...

  • Page 196

    NC alarms Alarms196 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:When interpreting the SPRINT or ISOPRINT command, an error was detected which was described in more detail by parameter %4. Parameter %3 may supply additional information on the incurring problem.List of error codes (p...

  • Page 197

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1197NC alarms 14070[Channel %1: ] Block %2 memory for variables not sufficient for subroutine callParameters:%1 = Channel number%2 = Block number, labelDefinitions:A called subroutine cannot be processed (opened), either because the internal dat...

  • Page 198

    NC alarms Alarms198 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA114085[Channel %1: ] Block %2 instruction not allowedParameters:%1 = Channel number%2 = Block number, labelDefinitions:The instruction 'TML()' may only be used in the subprogram, which replaces the T command.Reaction:Correction blo...

  • Page 199

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1199NC alarms Definitions:A function has been programmed or triggered which is not permitted in the current program context. The function in question is encoded in the "index" parameter:Index == 1: "RET" command was programme...

  • Page 200

    NC alarms Alarms200 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:- Correct the part program according to which of the above errors is involved.- Program SPOS.- Set the correct master spindle with SETMS.Program Continuation:Clear alarm with NC START or RESET key and continue the program.1...

  • Page 201

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1201NC alarms 14096[Channel %1: ] Block %2 illegal type conversionParameters:%1 = Channel number%2 = Block number, labelDefinitions:During the program run, a variable value assignment or an arithmetic operation has caused data to be processed in...

  • Page 202

    NC alarms Alarms202 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA114098[Channel %1: ] Block %2 conversion error: no valid number foundParameters:%1 = Channel number%2 = Block number, labelDefinitions:The string is not a valid INT or REAL number.Reaction:Interpreter stopNC Start disable in this c...

  • Page 203

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1203NC alarms Definitions:Euler angles or a vector have been used in programming an orientation and no orientation transformation is active, i.e. the keyword TRAORI(n) (n ... number of transformation grouping) is missing.Example of correct tran...

  • Page 204

    NC alarms Alarms204 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Change function call.Program Continuation:Clear alarm with the RESET key. Restart part program14104[Channel %1: ] Block %2 Active transformation allows neither vector programming nor interpolationParameters:%1 = Channel num...

  • Page 205

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1205NC alarms 14106[Channel %1: ] Block %2 orientation calculation not possible with ORISOL.Parameters:%1 = Channel number%2 = Block number, labelDefinitions:The G code ORISOL has been programmed and either no valid orientation has been programm...

  • Page 206

    NC alarms Alarms206 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Correction block is reorganized.Interface signals are set.Alarm display.Remedy:Change the NC program:Activate dynamic orientation transformation.Change the G code for group 49.Execute linear and rotary axis movement succe...

  • Page 207

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207NC alarms A non-settable orientation can only be specified by vector programming (direct programming of the vector compo-nents, Euler or RPY angle, programming with virtual orientation axes), whereas a non-settable orientation cannot arise w...

  • Page 208

    NC alarms Alarms208 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Interface signals are set.Alarm display.Remedy:Modify part program.Program Continuation:Clear alarm with NC START or RESET key and continue the program.14116[Channel %1: ] Block %2 absolute orientation programmed while ORIPATH/ORI...

  • Page 209

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1209NC alarms Remedy:Modify part program.Program Continuation:Clear alarm with NC START or RESET key and continue the program.14120[Channel %1: ] Block %2 plane determination for programmed orientation not possibleParameters:%1 = Channel number%...

  • Page 210

    NC alarms Alarms210 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:With taper circumference interpolation, the programmed opening angle of the taper must be greater than the half of the angle between the start and end orientation. Otherwise, a taper cannot be defined.Reaction:Correcti...

  • Page 211

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1211NC alarms Definitions:The rotation (3rd degree of freedom of orientation at 6-axis transformations) has been programmed several times.The rotation is clearly defined by one of the following specifications:- Specification of the rotary axis p...

  • Page 212

    NC alarms Alarms212 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Interface signals are set.Alarm display.Remedy:Reduce the number of initialization values.Program Continuation:Clear alarm with the RESET key. Restart part program14131[Channel %1: ] Block %2 orientation axes and lead/tilt angles ...

  • Page 213

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1213NC alarms 14134[Channel %1: ] Block %2 G code for orientation interpolation not allowed: error no. %3Parameters:%1 = Channel number%2 = Block number, label%3 = Error codeDefinitions:The alarm can have various causes, which are identified by ...

  • Page 214

    NC alarms Alarms214 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA114138[Channel %1: ] Block %2 Polynomials PO[XH], PO[YH] and PO[ZH] are not permittedParameters:%1 = Channel number%2 = Block number, labelDefinitions:Polynomials for the coordinates of a reference point on the tool (PO[XH], PO[YH]...

  • Page 215

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1215NC alarms 14146[Channel %1: ] Block %2 CP or PTP movement without transformation not allowedParameters:%1 = Channel number%2 = Block number, labelDefinitions:The CP or PTP G code was programmed for a movement but no transformation was active...

  • Page 216

    NC alarms Alarms216 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA114151[Channel %1: ] Block %2 illegal tool carrier rotationParameters:%1 = Channel number%2 = Block number, labelDefinitions:A toolholder was activated with an angle of rotation unequal to zero, although the associated axis is not ...

  • Page 217

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1217NC alarms Interface signals are set.Alarm display.Remedy:Change the tool carrier data.Program Continuation:Clear alarm with NC START or RESET key and continue the program.14154[Channel %1: ] Block %2 The amount of fine correction in paramete...

  • Page 218

    NC alarms Alarms218 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA114157[Channel %1: ] Block %2 illegal interpolation type with MOVTParameters:%1 = Channel number%2 = Block number, labelDefinitions:Linear or spline interpolation must be active with MOVT (G0, G1, ASPLINE, BSPLINE, CSPLINE).Reactio...

  • Page 219

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1219NC alarms Remedy:Change MD20380 $MC_TOOL_CORR_MODE_G43G44 or the part program.Program Continuation:Clear alarm with NC START or RESET key and continue the program.14162[Channel %1: ] Block %2 error %3 on activation of the CUTMOD or CUTMODK f...

  • Page 220

    NC alarms Alarms220 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:An error occurred while programming a tool length offset with TOFF or TOFFL. More information about the type of error is given by the error code number:Error code1At least one tool length offset component has been prog...

  • Page 221

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1221NC alarms Exception: The structured cutting edge D1 of the active tool can also be selected with H99 in ISO2 mode or with the offset component in the tool selection in ISO3 mode.When writing the tool offset with G10: Only tool offsets 1 ...

  • Page 222

    NC alarms Alarms222 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:Only relevant in ISO2 mode:The structured D number D1 of the active tool has been selected with H99. These offset values cannot be calculated negatively with G44.Reaction:Correction block is reorganized.Interface signa...

  • Page 223

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1223NC alarms Definitions:G49 (select tool length compensation) and an H word not equal to H0 have been programmed simultaneously.Reaction:Correction block is reorganized.Local alarm reaction.Interface signals are set.Alarm display.NC Stop on al...

  • Page 224

    NC alarms Alarms224 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA114197[Channel %1: ] Block %2 D number and H number programmed simultaneouslyParameters:%1 = Channel number%2 = Block number, labelDefinitions:A D word and H word have been programmed simultaneously.Reaction:Correction block is reo...

  • Page 225

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1225NC alarms Definitions:In the endpoint specification of a traversing block with G00, G01, G02 or G03 in polar coordinates, the polar radius entered for the keyword RP=... is negative.Definition of terms:- Specification of end of block point w...

  • Page 226

    NC alarms Alarms226 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA114260[Channel %1: ] Block %2 pole angle too largeParameters:%1 = Channel number%2 = Block number, labelDefinitions:In redefining the pole with G110, G111 or G112 in polar coordinates, the value range of the pole angle specified un...

  • Page 227

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1227NC alarms Definitions:A polynominal degree greater than five was programmed for the polynominal interpolation. You can only program poly-nomials up to the 5th degree.Reaction:Correction block is reorganized.Interface signals are set.Alarm di...

  • Page 228

    NC alarms Alarms228 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Alarm display.Remedy:Use the handwheel for one purpose at a time only.Program Continuation:Alarm display showing cause of alarm disappears. No further operator action necessary.14400[Channel %1: ] Block %2 tool radius com...

  • Page 229

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1229NC alarms Definitions:Positioning axis runs cannot be accurately calculated beforehand. Consequently, the position in the MCS is not known exactly. It might therefore be possible that a change in the multiple significance of the transformati...

  • Page 230

    NC alarms Alarms230 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Modify part program.Program Continuation:Clear alarm with NC START or RESET key and continue the program.14411[Channel %1: ] Block %2 tool radius compensation active at geometry axis changeoverParameters:%1 = Channel number...

  • Page 231

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1231NC alarms - More than 6 parameters were specified.- A geometry axis number was programmed which was less than 0 or greater than 3.- A geometry axis number was programmed more than once.- An axis identifier was programmed more than once.- An ...

  • Page 232

    NC alarms Alarms232 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Change part program and delete active tangential control with TANGDEL.Program Continuation:Clear alarm with NC START or RESET key and continue the program.14432[Channel %1: ] Block %2 Rounding length for tangential axis %3 ...

  • Page 233

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1233NC alarms Definitions:In subroutine calls with parameter transfer ("call-by-value" or "call-by-reference") the called subroutine must begin with a PROC statement.Reaction:Correction block is reorganized.Interface signals ...

  • Page 234

    NC alarms Alarms234 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA114540[Channel %1: ] Block %2 contour tool: the min. limit angle has been programmed more than once (edge D%3)Parameters:%1 = Channel number%2 = Block number, label%3 = Edge number, labelDefinitions:The limit angle of a contour too...

  • Page 235

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1235NC alarms Definitions:On defining a contour tool, either no limit angle must be indicated, or both the minimum and the maximum limit angle must be programmed once for each.Reaction:Correction block is reorganized.Local alarm reaction.Interfa...

  • Page 236

    NC alarms Alarms236 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Change tool definition.Program Continuation:Clear alarm with NC START or RESET key and continue the program.14547[Channel %1: ] Block %2 contour tool: checksum erroneous or not availableParameters:%1 = Channel number%2 = Bl...

  • Page 237

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1237NC alarms Reaction:Correction block is reorganized.Local alarm reaction.Interface signals are set.Alarm display.NC Stop on alarm at block end.Remedy:Change the NC program.Program Continuation:Clear alarm with NC START or RESET key and contin...

  • Page 238

    NC alarms Alarms238 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:The download buffer for "execute from external" could not be created. Possible causes:- Not enough memory available (for minimum see MD18360 $MN_MM_EXT_PROG_BUFFER_SIZE)- No resources available for HMI NCK co...

  • Page 239

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1239NC alarms Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:Check the connection to the HMI and repeat selection of the program that is to be executed from external source.Program Contin...

  • Page 240

    NC alarms Alarms240 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1The NCK input number must lie between 1 and 8. It is assigned a priority from 1 to 128 (1 is the highest priority) in the SETINT instruction with the keyword PRIO = ... .Example:If NCK input 5 changes to "1 signal", the ...

  • Page 241

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1241NC alarms Definitions:After reset, it has been found that the number of available blocks has decreased compared with the last reset. This is due to a system error. Part program execution can be resumed after the alarm has been acknowledged. ...

  • Page 242

    NC alarms Alarms242 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1MD20126 $MC_TOOL_CARRIER_RESET_VALUE,MD20150 $MC_GCODE_RESET_VALUES, MD20154 $MC_EXTERN_GCODE_RESET_VALUES,MD20140 $MC_TRAFO_RESET_VALUE,MD21330 $MC_COUPLE_RESET_MODE_1,MD24002 $MC_CHBFRAME_RESET_MASK If parameter %3= 100 - 104:Ch...

  • Page 243

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1243NC alarms Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:The following conditions have to be fulfilled in order to select JOG Retract:- A program execution with active tool offset has...

  • Page 244

    NC alarms Alarms244 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA114740[Channel %1: ] Block %2 no tool data available for centerless grindingParameters:%1 = Channel number%2 = Block number, labelDefinitions:For centerless grinding, the tool data must be contained in T1, D1 (grinding wheel) or T2...

  • Page 245

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1245NC alarms Definitions:Processing of motion-synchronous actions requires resources that are configured using MD28060 $MC_MM_IPO_BUFFER_SIZE, MD28070 $MC_MM_NUM_BLOCKS_IN_PREP, MD28251 $MC_MM_NUM_SAFE_SYNC_ELEMENTS, MD28250 $MC_MM_NUM_SYNC_ELE...

  • Page 246

    NC alarms Alarms246 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm.Remedy:Modify part program.Program Continuation:Clear alarm with NC START or RESET key and continue the program.147...

  • Page 247

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1247NC alarms 14759[Channel %1: ] Block %2 motion synchronous action and wrong axis typeParameters:%1 = Channel number%2 = Block number, labelDefinitions:When there are several feeds, a spark-out time, or a retraction stroke for path motions, at...

  • Page 248

    NC alarms Alarms248 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:The number of programmed PLC variables has exceeded the maximum permissible number. The number is set in MD 28150 $MC_MM_NUM_VDIVAR_ELEMENTS.Reaction:Interpreter stopNC Start disable in this channel.Interface signals a...

  • Page 249

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1249NC alarms Reaction:NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm.Remedy:Insert main run blocks which require a sufficient number of interpolation cycles for execution (e.g. G4 F10) between the assi...

  • Page 250

    NC alarms Alarms250 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:A maximum of 5 auxiliary functions of type "M" may be entered in an NC block. The upper limit is the total of pro-grammed and implicitely generated M auxiliary functions. Implicit auxiliary functions M19 and ...

  • Page 251

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1251NC alarms 10 Transmit option 11 Tracon option 12 Tracyl option 13 Traang option 14 Oscill option 15 SynSpi option 16 Repos option 17 Spline option 18 Involute option 19 Poly option 20 Com...

  • Page 252

    NC alarms Alarms252 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1 13 Traang option 14 Oscill option 15 SynSpi option 16 Repos option 17 Spline option 18 Involute option 19 Poly option 20 Compress option 23 Masl option 24 ExtLang or ExtLanguage o...

  • Page 253

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1253NC alarms Definitions:An attempt is made in the block to activate a group of the coordinate system-specific working area limitation.However, this group is not set up (see MD28600 $MC_MM_NUM_WORKAREA_CS_GROUPS).Reaction:Correction block is re...

  • Page 254

    NC alarms Alarms254 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA114811[Channel %1: ] Block %2 Incorrect value range for programmed dynamic value of axis/spindle %3, error no. %4Parameters:%1 = Channel number%2 = Block number, label%3 = Axis, spindle%4 = Error no.Definitions:A value outside the ...

  • Page 255

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1255NC alarms Definitions:For the function "Constant cutting speed G96" a maximum spindle speed can be programmed with the keyword LIMS=.... The values are in the range 0.1 - 999 999.9 [rev/min].Reaction:Correction block is reorganized...

  • Page 256

    NC alarms Alarms256 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Correction block is reorganized.Interface signals are set.Alarm display.Remedy:Check tool compensation data.- $TC_DP1 : 400 - 499.- $TC_TPG1: Spindle number.- $TC_TPG8: Inclination angle for slope grinding wheel.- $TC_TPG...

  • Page 257

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1257NC alarms Remedy:Modify part program.Program Continuation:Clear alarm with NC START or RESET key and continue the program.14830[Channel %1: ] Block %2 wrong feed type selectedParameters:%1 = Channel number%2 = Block number, labelDefinitions:...

  • Page 258

    NC alarms Alarms258 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:Selection of the cutting rate SVC is not permissible in the current stateCauses of the problem: the following function is active.1: Constant cutting rate G96, G961 or G962 active2: SPOS/SPOSA/M19 (spindle positioning m...

  • Page 259

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1259NC alarms 14900[Channel %1: ] Block %2 center point and end point programmed simultaneouslyParameters:%1 = Channel number%2 = Block number, labelDefinitions:When programming a circle by means of the opening angle, the circle center point was...

  • Page 260

    NC alarms Alarms260 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:A WAITM/WAITMC/SETM/CLEARM instruction was programmed with a marker number of less than 1 or greater than the maximum number of markers. Exception: CLEARM(0) is allowed and clears all markers in the channel!Reaction:Co...

  • Page 261

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1261NC alarms Remedy:Program CHANDATA instruction in accordance with the actual configuration.Program Continuation:Clear alarm with the RESET key. Restart part program15025CHANDATA(%3): channel is not active. Channel data will be ignored.Paramet...

  • Page 262

    NC alarms Alarms262 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Please inform the authorized personnel/service department. No remedial measures are available for the further exe-cution of the current part program, however:1. Reduce log file size requirement by:Reducing the distance betw...

  • Page 263

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1263NC alarms 15122Power ON after power failure: %1 data were restored, of which %2 machine data, %3 errors.Parameters:%1 = Number of data%2 = Number of machine data%3 = Number of errors occurredDefinitions:Notification alarm. The alarm has no n...

  • Page 264

    NC alarms Alarms264 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA115165[Channel %1: ] Block %2 error when translating or interpreting Asup %3 Parameters:%1 = Channel number%2 = Block number, label%3 = StringDefinitions:At part program start and at start of an ASUB under Reset condition, the rele...

  • Page 265

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1265NC alarms Definitions:When calling a precompiled subroutine, it was noticed that the compiled program is older than the relevant SPF file. The compiled program was deleted and during start the subroutine is executed instead of the compiled p...

  • Page 266

    NC alarms Alarms266 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA115176[Channel %1: ] Block %2 Program%3 may only be executed after Power ONParameters:%1 = Channel number%2 = Block number, label%3 = File nameDefinitions:If an encrypted program is loaded to the NCK, an NCK reset (restart) must be...

  • Page 267

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1267NC alarms 15180[Channel %1: ] Block %2: Error on editing program %3 as INI/DEF file.Parameters:%1 = Channel number%2 = Block number, label%3 = StringDefinitions:Errors were found when processing an initialization program (INI file), or a GUD...

  • Page 268

    NC alarms Alarms268 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:NC Start disable in this channel.Interface signals are set.Alarm display.Remedy:Modify definition file or initialization fileProgram Continuation:Clear alarm with the RESET key. Restart part program15187[Channel %1: ] Err...

  • Page 269

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1269NC alarms Program Continuation:Switch control OFF - ON.15190[Channel %1: ] Block %2 not enough free memory for subroutine callParameters:%1 = Channel number%2 = Block number, labelDefinitions:The following deadlock has been found in the inte...

  • Page 270

    NC alarms Alarms270 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Modify the block search command.Program Continuation:Clear alarm with the Delete key or NC START.15330[Channel %1: ] Block %2 invalid block number as search targetParameters:%1 = Channel number%2 = Block number, labelDefini...

  • Page 271

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1271NC alarms 15370[Channel %1: ] Target of block search not foundParameters:%1 = Channel numberDefinitions:In a block search, an impermissible search target has been specified (e.g. negative block number).Reaction:Alarm display.Remedy:Check the...

  • Page 272

    NC alarms Alarms272 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Make sure that all relevant axes are in the same channel.Program Continuation:Clear alarm with the RESET key. Restart part program15400[Channel %1: ] Block %2 selected initial INIT block does not existParameters:%1 = Channe...

  • Page 273

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1273NC alarms 15450[Channel %1: ] Block %2 compiled program cannot be storedParameters:%1 = Channel number%2 = Block number, labelDefinitions:In the compile mode, a compiled program could not be stored. One of the following reasons applies:- Not...

  • Page 274

    NC alarms Alarms274 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Program alarm number in the SETAL instruction in the correct range.Program Continuation:Clear alarm with the RESET key. Restart part program15701[Channel %1: ] Block %2 motion synchronous action: %3 illegal cycle alarm numb...

  • Page 275

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1275NC alarms 15900[Channel %1: ] Block %2 touch probe not allowedParameters:%1 = Channel number%2 = Block number, labelDefinitions:Measure with deletion of distance-to-goIn the part program, an illegal probe has been programmed with the command...

  • Page 276

    NC alarms Alarms276 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA115960[Channel %1: ] Block %2 no traverse motion programmedParameters:%1 = Channel number%2 = Block number, labelDefinitions:Measure without deletion of distance-to-goIn the part program, no axis or a traversing path of zero has be...

  • Page 277

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1277NC alarms Remedy:After the channel stop, the axes must be retracted manually in JOG and the program canceled with Reset.Program Continuation:Clear alarm with the RESET key. Restart part program16015[Channel %1: ] Block %2 wrong axis identifi...

  • Page 278

    NC alarms Alarms278 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Path | | STOP + LIFTFASTPOS | | STOP + LIFTFASTPOS | non-modal | STOP + LIFTFASTPOS | modal | STOP + LIFTFASTPOS | stati. | RUN + SHOWALARM 16017POSA | | STOP + LIFTFASTMOV | non-modal | S...

  • Page 279

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1279NC alarms NC Start disable in this channel.Interface signals are set.Alarm display.Remedy:Assign the axes/spindles that are to be repositioned to the channel via GET command prior to the REPOS command.Example:GET(A); assign the A axis to the...

  • Page 280

    NC alarms Alarms280 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Positioning mode:Position control (spindle position under SPOS/SPOSA)Oscillating mode:Speed control (M41 - M45 or M40 and S...)Control mode:Speed control (spindle speed under S..., M3/M4/M5)Position control (SPCON/SPCOF, spindle s...

  • Page 281

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1281NC alarms Reaction:Correction block is reorganized.Interface signals are set.Alarm display.Remedy:Modify part program: Length 1 - 3 or 4 permissible for radius.Program Continuation:Clear alarm with NC START or RESET key and continue the prog...

  • Page 282

    NC alarms Alarms282 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:The spline and polynomial interpolation are options that are not contained in the basic version of the control.Reaction:Correction block is reorganized.Interface signals are set.Alarm display.Remedy:Do not program spli...

  • Page 283

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1283NC alarms 16420[Channel %1: ] Block %2 axis %3 programmed repeatedlyParameters:%1 = Channel number%2 = Block number, label%3 = Axis name, spindle numberDefinitions:It is not allowed to program an axis more than once.Reaction:Correction block...

  • Page 284

    NC alarms Alarms284 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA116424[Channel %1: ] Block %2 coordinate %3 programmed repeatedly in the blockParameters:%1 = Channel number%2 = Block number, label%3 = CoordinateDefinitions:It is not allowed to program a coordinate of the 2nd contact point of th...

  • Page 285

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1285NC alarms Alarm display.Remedy:Values for chamfers, roundings and modal roundings must be programmed with positive values only.Program Continuation:Clear alarm with NC START or RESET key and continue the program.16510[Channel %1: ] Block %2 ...

  • Page 286

    NC alarms Alarms286 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Correction block is reorganized.Interface signals are set.Alarm display.Remedy:The changeover to speed control operation is performed by programming M3, M4 or M5. The M functions can be writ-ten together with the S word i...

  • Page 287

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1287NC alarms Definitions:An attempt was made to activate more generic couplings than are configured in MD18450 $MN_MM_NUM_CP_MODULES.Reaction:NC not ready.NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm...

  • Page 288

    NC alarms Alarms288 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:An attempt was made to activate more generic couplings than are configured in MD18450 $MN_MM_NUM_CP_MODULES.Reaction:NC not ready.NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alar...

  • Page 289

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1289NC alarms Definitions:An attempt was made to define or activate a CP coupling, although a coupling had already been defined or activated on this following axis/spindle in another channel.Reaction:NC Start disable in this channel.Interface si...

  • Page 290

    NC alarms Alarms290 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:The stated instruction has been programmed repeatedly in the block for the same followingaxis/spindle of a generic coupling.Reaction:Correction block is reorganized.Interface signals are set.Alarm display.Remedy:Modify...

  • Page 291

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1291NC alarms 16685[Channel %1: ] Block %2 following axis/spindle %3 instructions %4 are not possible separately.Parameters:%1 = Channel number%2 = Block number, label%3 = Axis name, spindle number%4 = CP instructionsDefinitions:The stated instr...

  • Page 292

    NC alarms Alarms292 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:The maximum number of master values has been exceeded for the stated type of generic coupling.Reaction:Correction block is reorganized.Interface signals are set.Alarm display.Remedy:Modify part program, reduce number o...

  • Page 293

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1293NC alarms Remedy:Modify part programm.End coupling and reactivate with desired reference system.Program Continuation:Clear alarm with NC START or RESET key and continue the program.16692[Channel %1: ] Block %2 following axis/spindle %3 maxim...

  • Page 294

    NC alarms Alarms294 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA116696[Channel %1: ] Block %2 following axis/spindle %3 coupling has not been defined.Parameters:%1 = Channel number%2 = Block number, label%3 = Axis name, spindle numberDefinitions:An instruction to an undefined coupling is to be ...

  • Page 295

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1295NC alarms Definitions:An instruction to an undefined leading axis/spindle of a coupling is to be executed.Reaction:NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm.Remedy:Modify part programm.Define t...

  • Page 296

    NC alarms Alarms296 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Add S value or direction of rotation for the master spindle in the displayed block.Program Continuation:Clear alarm with the RESET key. Restart part program16715[Channel %1: ] Block %2 axis %3 spindle not in standstillParam...

  • Page 297

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1297NC alarms 16740[Channel %1: ] Block %2 no geometry axis programmedParameters:%1 = Channel number%2 = Block number, labelDefinitions:No geometry axis was programmed for tapping (G33) or for rigid tapping (G331, G332). The geometry axis is, ho...

  • Page 298

    NC alarms Alarms298 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Procedure for automatically engaging the suitable gear stage prior to thread cutting:* Program the spindle speed (S) in a G331 block without axis motions and prior to thread cutting, e.g. G331 S1000.* Activate M40 for the s...

  • Page 299

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1299NC alarms 16755[Channel %1: ] Block %2 no stop requiredParameters:%1 = Channel number%2 = Block number, labelDefinitions:No Stop is needed for the programmed function. A Stop is necessary after SPOSA or after M5 if the next block is to be lo...

  • Page 300

    NC alarms Alarms300 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Correction block is reorganized.Interface signals are set.Alarm display.Remedy:Program the spindle speed under address S in [rpm] (in spite of axis mode); the direction of rotation is given by the sign of the spindle lead...

  • Page 301

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1301NC alarms 16765[Channel %1: ] Block %2 motion synchronous action: %3 following spindle/axis missingParameters:%1 = Channel number%2 = Block number, line number%3 = Synact IDDefinitions:The following spindle/axis has not been written in the p...

  • Page 302

    NC alarms Alarms302 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm.Remedy:Modify part program.Program Continuation:Clear alarm with the RESET key. Restart part program16770[Channel %1: ] Block %2 ax...

  • Page 303

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1303NC alarms 16773[Channel %1: ] Axis %2 is the following axis. The axis/spindle disables of leading axes %3 and %4 differ from one another.Parameters:%1 = Channel number%2 = Axis, spindle%3 = Axis, spindle%4 = Axis, spindleDefinitions:The axis...

  • Page 304

    NC alarms Alarms304 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Please inform the authorized personnel/service department. Retrofit a measuring system.Program Continuation:Clear alarm with the RESET key. Restart part program16776[Channel %1: ] Block %2 curve table %3 does not exist for ...

  • Page 305

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1305NC alarms 16779[Channel %1: ] Block %2 coupling: too many couplings for axis %3, see active leading axis %4Parameters:%1 = Channel number%2 = Block number, label%3 = Axis name, spindle number%4 = Axis name, spindle numberDefinitions:More lea...

  • Page 306

    NC alarms Alarms306 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Please inform the authorized personnel/service department. Put the master spindle/axis with spindle/axis exchange into the necessary channel or release from the PLC.Program Continuation:Clear alarm with NC START or RESET ke...

  • Page 307

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1307NC alarms 16787[Channel %1: ] Block %2 coupling parameter not changeableParameters:%1 = Channel number%2 = Block number, labelDefinitions:The specified coupling is write-protected. Therefore, the coupling parameters cannot be modified.Reacti...

  • Page 308

    NC alarms Alarms308 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Please inform the authorized personnel/service department.- Configure link accordingly in SD42300 $SC_COUPLE_RATIO_1- or correct part program.Program Continuation:Clear alarm with NC START or RESET key and continue the prog...

  • Page 309

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1309NC alarms Definitions:The specified axis is a (gantry) slave axis and cannot therefore approach the reference point.Reaction:Correction block is reorganized.Interface signals are set.Alarm display.Remedy:Modify part program. Switch off coupl...

  • Page 310

    NC alarms Alarms310 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:The programmed axis/spindle is active as a slave axis/spindle in a coupling. When the coupling is active, the axis con-tainer cannot be rotated.Reaction:Correction block is reorganized.Interface signals are set.Alarm d...

  • Page 311

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1311NC alarms Definitions:The keyword ACP (Absolute Coordinate Positive) is only allowed for "modulo axes". It causes approach of the pro-grammed absolute position in the specified direction.Reaction:Correction block is reorganized.Int...

  • Page 312

    NC alarms Alarms312 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Wait until the procedure is terminated or canceled with Reset and repeat the operation.Program Continuation:Clear alarm with the Delete key or NC START.16904[Channel %1: ] Program control: action %2<ALNX> not allowed ...

  • Page 313

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1313NC alarms Definitions:This action may only be performed in Reset state or at end of block.In JOG mode, no axis that is traversed as geometry axis in the switched coordinate system, must be active as PLC or command axis (started through stati...

  • Page 314

    NC alarms Alarms314 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Either activate the Reset key to reset program processing, or activate the mode in which the program was being pro-cessed previously.Program Continuation:Clear alarm with the Delete key or NC START.16914[Mode group %1: ] [C...

  • Page 315

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1315NC alarms 16919[Channel %1: ] Action %2<ALNX> is not allowed due to a pending alarmParameters:%1 = Channel number%2 = Action number/action nameDefinitions:This action cannot be performed due to an alarm, or the channel is in the fault ...

  • Page 316

    NC alarms Alarms316 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA116923[Channel %1: ] Program control: action %2<ALNX> not allowed in the current stateParameters:%1 = Channel number%2 = Action number/action nameDefinitions:The current processing cannot be stopped since a preprocessing proc...

  • Page 317

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1317NC alarms Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:Repeat action.Program Continuation:Clear alarm with the RESET key. Restart part program16927[Channel %1: ] Action %2<ALNX&g...

  • Page 318

    NC alarms Alarms318 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Correction block is reorganized.Interpreter stopInterface signals are set.Alarm display.Remedy:Program an executable NC block between the previous and the current NC block.Example:N10 SETM.N15 STOPRE ; insert executable N...

  • Page 319

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1319NC alarms Reaction:NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm.Remedy:Cancel program with the RESET key.Program Continuation:Clear alarm with the RESET key. Restart part program16934[Channel %1: ...

  • Page 320

    NC alarms Alarms320 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA116937[Channel %1: ] Action %2<ALNX> not possible due to program testParameters:%1 = Channel number%2 = Action number/action nameDefinitions:This action is not allowed as program test is currently active.Example: It is not pe...

  • Page 321

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1321NC alarms 16941[Channel %1: ] Action %2<ALNX> rejected because no program event has been executed yetParameters:%1 = Channel number%2 = Action number/action nameDefinitions:The setting of the MD20108 $MC_PROG_EVENT_MASK forces an async...

  • Page 322

    NC alarms Alarms322 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1In this case, it is irrelevant whether a user ASUP or a system ASUP has been triggered. User ASUPs are activated via FC-9 or via the fast inputs.The following events lead to system ASUPS:- Mode change- Overstore on- Canceling subp...

  • Page 323

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1323NC alarms This alarm occurs if the channel was started via the START part programm command and MD22622 $MC_DISABLE_PLC_START==FALSE was set.Reaction:Alarm display.Remedy:Modify MD22622 $MC_DISABLE_PLC_START of switch off "Group Serupro&...

  • Page 324

    NC alarms Alarms324 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Alarm display.Remedy:In each wait marker, list all channels with which you want to synchronize, or suppress the alarm with MD11410 $MN_SUPPRESS_ALARM_MASK, bit 23.==========================================================...

  • Page 325

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1325NC alarms 16952[Channel %1: ] Start program command not possible due to MDIParameters:%1 = Channel numberDefinitions:NCK is currently executing an ASUB in MDI mode. In this constellation, parts program command "Start" is not allowe...

  • Page 326

    NC alarms Alarms326 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:MD11550 $MN_STOP_MODE_MASK and language command DELAYFSTON DELAYFSTOFProgram Continuation:Alarm display showing cause of alarm disappears. No further operator action necessary.16956[Channel %1: ] Program %2 cannot be starte...

  • Page 327

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1327NC alarms Remedy:Wait for end of program area EXECUTE.Program Continuation:Clear alarm with the Delete key or NC START.16961[Channel %1: ] Action %2<ALNX> prohibited during syntax check.Parameters:%1 = Channel number%2 = Action number/...

  • Page 328

    NC alarms Alarms328 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA116965[channel %1: ] SAFE.SPF ramp-up not completedParameters:%1 = Channel numberDefinitions:The alarm is triggered if the safety program /N_CST_DIR/N_SAFE_SPF needs to be executed during ramp-up and this has not been completed af...

  • Page 329

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1329NC alarms 17001[Channel %1: ] Block %2 no memory left for tool/magazine dataParameters:%1 = Channel number%2 = Block number, labelDefinitions:The number of the following tool/magazine data variables in the NC is specified using machine data:...

  • Page 330

    NC alarms Alarms330 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA117018[Channel %1: ] Block %2 incorrect value for parameter %3Parameters:%1 = Channel number%2 = Block number, label%3 = Parameter nameDefinitions:An incorrect value has been assigned to the stated parameter.Only the following valu...

  • Page 331

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1331NC alarms The following applies specifically: If the alarm occurs while writing one of the parameters $TC_MDP1/$TC_MDP2/$TC_MLSR,check whether MD18076 $MN_MM_NUM_LOCS_WITH_DISTANCE has been set correctly. $MN_MM_NUM_LOCS_WITH_DISTANCE define...

  • Page 332

    NC alarms Alarms332 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1 - An illegal value is to be written in a machine data (e.g. MD10010 $MN_ASSIGN_CHAN_TO_MODE_GROUP[0] = 0) - On accessing an individual frame element, a frame component other than TRANS, ROT, SCALE or MIRROR was addresse...

  • Page 333

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1333NC alarms Reaction:Correction block is reorganized.Interface signals are set.Alarm display.Remedy:Reduce array dimensions.Program Continuation:Clear alarm with NC START or RESET key and continue the program.17070[Channel %1: ] Block %2 data ...

  • Page 334

    NC alarms Alarms334 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:An attempt was made to write into a machine data with a value greater than the defined upper limit.Reaction:Correction block is reorganized.Interface signals are set.Alarm display.Remedy:Please inform the authorized pe...

  • Page 335

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1335NC alarms 17120[Channel %1: ] Block %2 analog input no. %3 not activatedParameters:%1 = Channel number%2 = Block number, label%3 = Input numberDefinitions:An attempt has been made by means of the system variable $A_INA[n] to read an analog i...

  • Page 336

    NC alarms Alarms336 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Correction block is reorganized.Interface signals are set.Alarm display.Remedy:Program fewer digital/analog outputs in a block. The specified maximum number applies in each case separately for analog or digital outputs. I...

  • Page 337

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1337NC alarms Reaction:Correction block is reorganized.Interface signals are set.Alarm display.Remedy:Check tool call in the NC parts program:- Correct tool correction number D programmed? If no D number is specified with the tool change command...

  • Page 338

    NC alarms Alarms338 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Correction block is reorganized.Interface signals are set.Alarm display.Remedy:- Change program:- Select different H numberProgram Continuation:Clear alarm with NC START or RESET key and continue the program.17188[Channel...

  • Page 339

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1339NC alarms - Tool parameters P1 - P25 defined? The dimensions of the tool edge must have been entered previously either through the operator panel or through the V.24 interface.Description of the system variables $P_DP x [n, m]n ... Associate...

  • Page 340

    NC alarms Alarms340 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:The tool at the specified toolholder/spindle at which the last tool change was carried out as master toolholder or master spindle, has been replaced.Example:N10 SETHTH(1)N20 T="Wz1" ; Tool change at master to...

  • Page 341

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1341NC alarms Reaction:Correction block is reorganized.Interface signals are set.Alarm display.Remedy:Check access to tool offset memory by means of $TC_DP1[t,d] = 0 or deselect tool.Program Continuation:Clear alarm with NC START or RESET key an...

  • Page 342

    NC alarms Alarms342 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:Indicates that the specified manual tool must be loaded in the specified toolholder or spindle before the program con-tinues. A manual tool is a tool whose data is known to the NCK but has not been assigned to a magazi...

  • Page 343

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1343NC alarms Remedy:Make sure that the manual tools are exchanged. The alarm is cleared automatically after PLC acknowledgement of the tool change on command. Manual tools can only be used efficiently if this is supported by the PLC program.Pro...

  • Page 344

    NC alarms Alarms344 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA117230[Channel %1: ] Block %2 Duplo no. already assignedParameters:%1 = Channel number%2 = Block number, labelDefinitions:If an attempt is made to write a tool Duplo number to the name of which another tool (another T number) alrea...

  • Page 345

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1345NC alarms Reaction:Correction block is reorganized.Interface signals are set.Alarm display.Remedy:Correct the NC program.Program Continuation:Clear alarm with NC START or RESET key and continue the program.17262[Channel %1: ] Block %2 illega...

  • Page 346

    NC alarms Alarms346 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Please inform the authorized personnel/service department. Remove programming instruction for indexing axis posi-tions (CIC, CAC, CDC) from the NC part program or declare the relevant axis to be an indexing axis.Indexing ax...

  • Page 347

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1347NC alarms Definitions:The 'Hirth tooth system' function is activated for the indexing axis and the axis is to be traversed although it is not ref-erenced.Reaction:Alarm display.Remedy:Reference axis.Program Continuation:Clear alarm with the ...

  • Page 348

    NC alarms Alarms348 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:The programmed PRESET axis is involved in the current transformation. This means that setting the actual value memory (PRESET) is not possible for this axis.Example:Machine axis A should be set to the new actual value ...

  • Page 349

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1349NC alarms Definitions:The axis is involved in the active transformation. It can therefore not execute the demanded action, traversing as posi-tioning axis, enable for axis exchange.Reaction:Correction block is reorganized.Interface signals a...

  • Page 350

    NC alarms Alarms350 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA117650[Channel %1: ] Block %2 machine axis %3 not programmableParameters:%1 = Channel number%2 = Block number, label%3 = Axis name, spindle numberDefinitions:The machine axis cannot be used in an active transformation. You may be a...

  • Page 351

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1351NC alarms Definitions:A 'fixed-point approach in JOG' has been requested for an axis. This is not possible because:Reason 1: The axis is involved in the active transformation.Reason 2: The axis is a following axis in an active coupling.The f...

  • Page 352

    NC alarms Alarms352 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Adapt MD30610 $MA_NUM_FIX_POINT_POS and, if necessary, MD30600 $MA_FIX_POINT_POS[].Deselect fixed-point approach or select a valid fixed point, and restart the JOG motion.Program Continuation:Clear alarm with the Delete key...

  • Page 353

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1353NC alarms 17822[Channel %1: ] Axis %2 JOG to position: Position changedParameters:%1 = Channel numberDefinitions:An axis motion is active for the axis with 'JOG to position' but the position, that is the content of SD43320 $SA_JOG_POSITION, ...

  • Page 354

    NC alarms Alarms354 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:The JOG in circles function was activated, but this is not possible because:1. The current positions of the axes involved lie outside the selected pitch circle.2. The current positions of the axes involved, with pitch ...

  • Page 355

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1355NC alarms Definitions:There is an error in the definition of the protection zone. The error number gives the specific reason for the alarm:No.Meaning1: Incomplete or conflicting contour definition.2: Contour encompasses more than one surface...

  • Page 356

    NC alarms Alarms356 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:An error has occurred on activating the protection zone. The error number gives the specific reason for the alarm.No.Meaning1: Incomplete or conflicting contour definition.2: Contour encompasses more than one surface a...

  • Page 357

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1357NC alarms 8: Incorrect parameter used.9: Protection zone to be activated is not defined or number of the contour element <2 or >MAXNUM_CONTOURNO_PROTECTAREA.10: Error in internal structure of the protection zones.11: Other, not furth...

  • Page 358

    NC alarms Alarms358 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Correction block is reorganized.Local alarm reaction.Interface signals are set.Alarm display.Remedy:Modify part program.Program Continuation:Clear alarm with NC START or RESET key and continue the program.18006[Channel %1...

  • Page 359

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1359NC alarms 18102[Channel %1: ] Block %2 invalid value assigned to FXSW[]Parameters:%1 = Channel number%2 = Block number, labelDefinitions:Only positive values including zero are valid at the present time.Reaction:Correction block is reorganiz...

  • Page 360

    NC alarms Alarms360 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Remove the CTABEND command or add the CTABDEF( ..) command at the appropriate program location. The CTAB-DEF and CTABEND instructions must be programmed in the same program level (main or subprogram). Start the pro-gram aga...

  • Page 361

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1361NC alarms 18300[Channel %1: ] Block %2 frame: fine shift not possibleParameters:%1 = Channel number%2 = Block number, labelDefinitions:Allocation of a fine shift to settable frames or the basic frame is not possible since MD18600 $MN_MM_FRAM...

  • Page 362

    NC alarms Alarms362 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA118313[Channel %1: ] Block %2 frame: illegal switchover of geometry axesParameters:%1 = Channel number%2 = Block number, labelDefinitions:It is not allowed to change the geometry axis assignment because the current frame contains r...

  • Page 363

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1363NC alarms Definitions:After starting the reference point approach, the rising edge of the reduction cam must be reached within the section defined in the MD34030 $MA_REFP_MAX_CAM_DIST (phase 1 of referencing). (This error occurs only with in...

  • Page 364

    NC alarms Alarms364 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Please inform the authorized personnel/service department.Check the cam adjustment and make sure that the distance is sufficient between the end of the cam and the zero marker signal that follows. The path must be greater t...

  • Page 365

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1365NC alarms Reaction:NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm.Remedy:Please inform the authorized personnel/service department. Check the possible reasons for termination:- Servo enable missing:...

  • Page 366

    NC alarms Alarms366 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA120008[Channel %1: ] Axis %2 reference point approach requires second referenced measuring systemParameters:%1 = Channel number%2 = Axis name, spindle numberDefinitions:When setting MD34200 $MA_ENC_REFP_MODE = 6 the 2nd encoder mus...

  • Page 367

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1367NC alarms 20053[Channel %1: ] Axis %2 DRF, FTOCON, external zero point offset not possibleParameters:%1 = Channel number%2 = Axis name, spindle numberDefinitions:The axis is traversed in a mode (e.g. referencing) that allows no additional ov...

  • Page 368

    NC alarms Alarms368 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:An axis is to travel in JOG with revolutional feed, but the spindle/axis the feed is to be derived from is 0.Reaction:Alarm display.Remedy:Traverse the spindle/axis from which the feed is to be derived.Program Continua...

  • Page 369

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1369NC alarms Remedy:Wait for the axis to traverse or cancel with distance-to-go delete or RESET.Program Continuation:Clear alarm with the Delete key or NC START.20060[Channel %1: ] Axis %2 cannot be traversed as geometry axisParameters:%1 = Cha...

  • Page 370

    NC alarms Alarms370 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA120064[Channel %1: ] Axis %2 selection of several axes with an active taper angle is not permitted.Parameters:%1 = Channel number%2 = Axis name, spindle numberDefinitions:With an active taper angle, only one geometry axis at the ti...

  • Page 371

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1371NC alarms Definitions:The displayed axis is to be traversed as a "concurrent positioning axis" to the programmed limit position and the cor-responding working area limitation active for the axis is violated. No traversing takes pla...

  • Page 372

    NC alarms Alarms372 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA120075[Channel %1: ] Axis %2 can currently not oscillateParameters:%1 = Channel number%2 = Axis numberDefinitions:The axis cannot perform an oscillating movement now because it is already being traversed, e.g. in JOG mode.Reaction:...

  • Page 373

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1373NC alarms Reaction:Local alarm reaction.NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm.Remedy:Specify smaller target position.Deactivate working area limitation.Set working area limitation different...

  • Page 374

    NC alarms Alarms374 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA120082[Channel %1: ] Axis %2 coordinate system-specific working area limit %3 end position %4Parameters:%1 = Channel number%2 = Axis number%3 = "+" or "-"%4 = End positionDefinitions:The displayed axis is operat...

  • Page 375

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1375NC alarms 3. It is always necessary to program a traversing movement in the selection block for the axis/spindle for which the "Traverse against fixed stop" function is activated.The alarm can be reprogrammed in the MD11412 $MN_ALA...

  • Page 376

    NC alarms Alarms376 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1- Has the deselection process been interrupted by a RESET?- Has the PLC switched the acknowledgement signals?Program Continuation:Restart part program.Clear alarm with the RESET key in all channels of this mode group. Restart part...

  • Page 377

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1377NC alarms - The torque set for the brake test MD36966 $MA_SAFE_BRAKETEST_TORQUE must be greater than the current holding torque.Program Continuation:Clear alarm with the Delete key or NC START.20096Axis %1 brake test canceled, additional inf...

  • Page 378

    NC alarms Alarms378 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA120101Timeout during initialization of communication with the digitizerDefinitions:The attempt to synchronize the communications link to the digitizing unit and to transfer the machine parameters was canceled after the preset timeo...

  • Page 379

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1379NC alarms 20106The digitizer has triggered an emergency stop.Definitions:The digitizing unit has recognized a serious error and triggered an emergency stop. Cause: See display on the digi-tizing unit.Reaction:Channel not ready.NC Start disab...

  • Page 380

    NC alarms Alarms380 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Check table parameters $AN_CEC_OUTPUT_AXIS and correct and/or switch off one or more tables (SD41300 $SN_CEC_TABLE_ENABLE).Program Continuation:Clear alarm with the RESET key. Restart part program20121Axis %1: Configuration...

  • Page 381

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1381NC alarms Reaction:Interface signals are set.Alarm display.Remedy:Check characteristic data of the compensation tables assigned to the axis.Check characteristic curves in the tables ($AN_CEC).Program Continuation:Clear alarm with the RESET k...

  • Page 382

    NC alarms Alarms382 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Modify part program.Program Continuation:Clear alarm with the RESET key. Restart part program20139[Channel %1: ] Block %2 motion synchronous action: %3 invalid markerParameters:%1 = Channel number%2 = Block number, line num...

  • Page 383

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1383NC alarms 20142[Channel %1: ] Block %2 motion synchronous action: %3: command axis %4: rotation of axis container already enabledParameters:%1 = Channel number%2 = Block number, line number%3 = Synact ID%4 = Axis nameDefinitions:The synchron...

  • Page 384

    NC alarms Alarms384 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA120145[Channel %1: ] Block %2 motion synchronous action: %3 arithmetic errorParameters:%1 = Channel number%2 = Block number, line number%3 = Synact IDDefinitions:In calculating an arithmetic expression for a motion synchronous acti...

  • Page 385

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1385NC alarms 20148[Channel %1: ] Block %2 motion synchronous action: %3 internal error %4Parameters:%1 = Channel number%2 = Block number, line number%3 = Synact ID%4 = Error codeDefinitions:An internal error has occurred during processing of a ...

  • Page 386

    NC alarms Alarms386 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Interface signals are set.Alarm display.Remedy:For information only.Program Continuation:Clear alarm with the Delete key or NC START.20170[Channel %1: ] Machine data $AC_FIFO invalidParameters:%1 = Channel numberDefinitio...

  • Page 387

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1387NC alarms 20203[Channel %1: ] No active toolParameters:%1 = Channel numberDefinitions:A tool fine compensation has been written for the active tool of channel %1 with PUTFTOC. No tool is active in this channel. Therefore, the compensation ca...

  • Page 388

    NC alarms Alarms388 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:- Modify program- Select new traversing positions for centerless axes- or suppress computation by G00.Program Continuation:Alarm display showing cause of alarm disappears. No further operator action necessary.20211[Channel ...

  • Page 389

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1389NC alarms Remedy:Deselect JOG Retract with RESETProgram Continuation:Clear alarm with the Delete key or NC START.20306[Channel %1: ] Cartesian manual traverse not possibleParameters:%1 = Channel number%2 = Axis name, spindle numberDefinitio...

  • Page 390

    NC alarms Alarms390 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Remedy for error cause:1 Define another travel direction2 Deactivate the coupling and travel the axis/axes separately3 Deactivate the coupling and travel the axis/axes separately4 Reserved5 Deactivate the transformation and...

  • Page 391

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1391NC alarms 21612[Channel %1: ] Axis %2: enable reset, cause %3Parameters:%1 = Channel number%2 = Axis name, spindle number%3 = Cause of the alarmDefinitions:Causes of alarm: 0: The cause of the alarm cannot be precisely determined. 1: The i...

  • Page 392

    NC alarms Alarms392 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Please inform the authorized personnel/service department.1. With axes that have already been referenced, the software limit switch 1 or 2 should respond before the hardware limit switch is reached. Check MD36110 $MA_POS_LI...

  • Page 393

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1393NC alarms 21618[Channel %1: ] As from block %2 transformation active: overlaid motion too greatParameters:%1 = Channel number%2 = Block number, labelDefinitions:The share of overlaid motion on the transformation-related axes is so high that ...

  • Page 394

    NC alarms Alarms394 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA121650[Channel %1: ] Axis %2 overlaid motion not allowedParameters:%1 = Channel number%2 = Axis name, spindle numberDefinitions:An overlaid motion was requested for the axis, however, this is not allowed due to the MD32074 $MA_FRAM...

  • Page 395

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1395NC alarms Definitions:If an offset has been activated in tool direction by means of $AA_TOFF[i], no block is allowed to be activated in which the offset axis assignment i is modified (plane change, tool change cutting tool <=> turning ...

  • Page 396

    NC alarms Alarms396 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA121702[Channel %1: ] Block %3 axis %2 measurement canceledParameters:%1 = Channel number%2 = Axis name, spindle number%3 = Block numberDefinitions:The measurement block has ended (the programmed end position of the axis has been re...

  • Page 397

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1397NC alarms 21750Error during output of cam switching signals via timerDefinitions:The signal output activated by the MD10480 $MN_SW_CAM_TIMER_FASTOUT_MASK via the hardware timer (inde-pendent of the clock grid) did not work. Cause: interpolat...

  • Page 398

    NC alarms Alarms398 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:The number of programmed auxiliary functions has exceeded the maximum permissible amount. This alarm can occur in conjunction with motion synchronous actions: The maximum number of auxiliary functions must not be excee...

  • Page 399

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1399NC alarms 22001[Channel %1: ] Block %2 Axis %3: Brake ramp longer than Stop D time. Reason: %4.Parameters:%1 = Channel number%2 = Block number, label%3 = Axis name%4 = Identification of causeDefinitions:The current axis dynamic response is ...

  • Page 400

    NC alarms Alarms400 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Modify part program: Only those valid gear stages can be entered which have also been installed according to MD35090 $MA_NUM_GEAR_STEPS.Limit M70 configuration (MD 35014 $MA_GEAR_STEP_USED_IN_AXISMODE) to MD35090 $MA_NUM_GE...

  • Page 401

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1401NC alarms Reaction:Alarm display.Remedy:Change deselection block or block search target block to speed control mode (M3, M4, M5, SBCOF). Set bit 2 of MD35035 $MA_SPIND_FUNCTION_MASK to 0.Program Continuation:Clear alarm with the Delete key o...

  • Page 402

    NC alarms Alarms402 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Use spindles/axes with identical dynamic responses. If the differing settings have been selected on purpose, the alarm can be suppressed with MD11410 $MN_SUPPRESS_ALARM_MASK bit 21 = 1 or with CP programming by setting CPMA...

  • Page 403

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1403NC alarms 22019[Channel %1: ] Block %2 following axis/spindle %3 time monitoring: 'Synchronism coarse' not reachedParameters:%1 = Channel number%2 = Block number, label%3 = Following axis/spindle numberDefinitions:After reaching the setpoint...

  • Page 404

    NC alarms Alarms404 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA122024[Channel %1: ] Block %2 Spindle %3 tapping: PLC signal 'invert M3/M4' changed after %4Parameters:%1 = Channel number%2 = Block number, label%3 = Spindle%4 = ValueDefinitions:When loading a G331 block it was detected that the ...

  • Page 405

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1405NC alarms 22030[Channel %1: ] Block %2 following spindle %3 Impermissible programmingParameters:%1 = Channel number%2 = Block number, label%3 = SpindleDefinitions:With synchronous spindle-VV-coupling an additional motion for the following sp...

  • Page 406

    NC alarms Alarms406 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA122035[Channel %1: ] Block %2 following axis/spindle %3 unable to determine the offset value (reason %4).Parameters:%1 = Channel number%2 = Block number, label%3 = Following axis/spindle number%4 = ReasonDefinitions:The determinati...

  • Page 407

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1407NC alarms Definitions:VDI interface signal DB31..,DBX31.6 'Correct synchronism' is being ignored, because VDI interface signal DB31..,DBX31.7 'Delete synchronism override' has been set.Reaction:Alarm display.Remedy:Reset the two VDI interfac...

  • Page 408

    NC alarms Alarms408 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:- Program a GET for the master spindle/axis in the NC program before activating the coupling, or- Assign the master spindle/axis to the channel that activated the coupling via PLC.Program Continuation:Clear alarm with the D...

  • Page 409

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1409NC alarms Reaction:NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm.Remedy:Before programming the spindle/axis again using the SPOSA instruction, a WAITS command should be activated in order to wait f...

  • Page 410

    NC alarms Alarms410 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA122057[Channel %1: ] Block %2 for following spindle %3 coupling as leading spindle/axis already existingParameters:%1 = Channel number%2 = Block number, label%3 = Axis name, spindle numberDefinitions:A coupling has been switched on...

  • Page 411

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1411NC alarms Remedy:Please inform the authorized personnel/service department.Check active spindle speed limitations. Configure a lower zero marker search velocity MD34040 $MA_REFP_VELO_SEARCH_MARKER. Check the tolerance range for the actual ve...

  • Page 412

    NC alarms Alarms412 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm.Remedy:Please inform the authorized personnel/service department.- Check that the specified tool is contained in the desired magazi...

  • Page 413

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1413NC alarms 22069[Channel %1: ] Block %2 tool management: No tool available in tool group %3, program %4Parameters:%1 = Channel number%2 = Block number, label%3 = String (identifier)%4 = Program nameDefinitions:The specified tool group does no...

  • Page 414

    NC alarms Alarms414 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Interface signals are set.Alarm display.Remedy:The alarm is intended for information purposes. If only one tool in a group can be active at a time for technological reasons or for reasons of display, the "active"...

  • Page 415

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1415NC alarms 22150[Channel %1: ] Block %3 spindle %2 maximum speed for position control exceededParameters:%1 = Channel number%2 = Axis name, spindle number%3 = Block number, labelDefinitions:The maximum encoder speed was exceeded with SPCON. P...

  • Page 416

    NC alarms Alarms416 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:When DECODING SINGLE BLOCK has been selected and there is a chain of thread blocks, then machining pauses occur at the block limits until the next block is executed with the new NC Start.In normal single block mode, th...

  • Page 417

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1417NC alarms Definitions:Thread cutting with G33, G34, G35: Block length too short for predefined thread pitch. Block length is displayed.Reaction:Alarm display.Remedy:Reduce thread pitch (thread pitch change).Program Continuation:Clear alarm w...

  • Page 418

    NC alarms Alarms418 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:NC Start disable in this channel.Interface signals are set.Alarm display.Remedy:Resolve the conflict, for example by deactivating transformation prior to spindle start.Program Continuation:Clear alarm with the Delete key ...

  • Page 419

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1419NC alarms 22296[Channel %1: ] Spindle %2 Error on gear stage change (cause: error code %3)Parameters:%1 = Channel number%2 = Axis name, spindle number%3 = Error codeDefinitions:An error occurred during gear stage change. The cause is specifi...

  • Page 420

    NC alarms Alarms420 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA122320[Channel %1: ] Block %2 motion synchronous action: %3 PUTFTOCF command could not be transferredParameters:%1 = Channel number%2 = Block number, line number%3 = Synact IDDefinitions:The cyclic transfer of the PUTFTOCF data blo...

  • Page 421

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1421NC alarms Remedy:Please inform the authorized personnel/service department.- Set option- Cancel the activation of the function 'contour handwheel'- Modify part program.Program Continuation:Clear alarm with the Delete key or NC START.25000Axi...

  • Page 422

    NC alarms Alarms422 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Mode group not ready.The NC switches to follow-up mode.Channel not ready.NC Start disable in this channel.Axes of this channel must be re-referenced.Interface signals are set.Alarm display.NC Stop on alarm.Channel not rea...

  • Page 423

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1423NC alarms 1. Transmission path: Check the actual-value connectors for correct contacting, encoder cable for continuity, and also check for short-circuits and grounding (loose contact?).2. Encoder pulses: Is the encoder power supply within th...

  • Page 424

    NC alarms Alarms424 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA125030Axis %1 actual velocity alarm limitParameters:%1 = Axis name, spindle numberDefinitions:If the axis has at least one active encoder, then the actual speed of the axis is cyclically checked in the IPO cycle. If there are no er...

  • Page 425

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1425NC alarms Remedy:Please inform the authorized personnel/service department.- Check MD36040 $MA_STANDSTILL_DELAY_TIME and MD36030 $MA_STANDSTILL_POS_TOL; increase if nec-essary. The value must be greater than the machine data "Exact stop...

  • Page 426

    NC alarms Alarms426 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA125060Axis %1 speed setpoint limitationParameters:%1 = Axis name, spindle numberDefinitions:The speed setpoint has exceeded its upper limit for a longer period than allowed.The maximum speed setpoint is limited to a certain percent...

  • Page 427

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1427NC alarms Reaction:Mode group not ready.The NC switches to follow-up mode.Channel not ready.NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm.Channel not ready.Remedy:Please inform the authorized perso...

  • Page 428

    NC alarms Alarms428 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1NC Stop on alarm.Channel not ready.Remedy:Please inform the authorized personnel/service department. Check machine data for the active, selected encoders. Check the machine data relating to encoder (MD36510 $MA_ENC_DIFF_TOL) toler...

  • Page 429

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1429NC alarms Reaction:Mode group not ready.The NC switches to follow-up mode.Channel not ready.NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm.Channel not ready.Remedy:Evaluation of the drive alarms lis...

  • Page 430

    NC alarms Alarms430 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Mode group not ready.The NC switches to follow-up mode.Channel not ready.NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm.Channel not ready.Remedy:Determine the position deviation ...

  • Page 431

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1431NC alarms Reaction:Mode group not ready.The NC switches to follow-up mode.Channel not ready.NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm.Channel not ready.Remedy:Please inform the authorized perso...

  • Page 432

    NC alarms Alarms432 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA126005Axis %1 parameterization error: output ratingParameters:%1 = Axis name, spindle numberDefinitions:For analog drives:The output evaluation of the analog speed setpoint set in the MD32250 $MA_RATED_OUTVAL or in MD 32260 $MA_RAT...

  • Page 433

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1433NC alarms 26007Axis %1 QEC: invalid coarse step sizeParameters:%1 = Axis name, spindle numberDefinitions:The course step width for QEC must be within the range 1 <= course step width <= maximum value of MD18342 $MN_MM_QEC_MAX_POINTS (c...

  • Page 434

    NC alarms Alarms434 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA126011Axis %1 QEC: invalid measuring periodsParameters:%1 = Axis name, spindle numberDefinitions:$AA_QEC_MEAS_TIME_1/2/3: measuring time to determine the error criterion.The measuring period begins when the criterion for activating...

  • Page 435

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1435NC alarms Definitions:Machine data includes a value that is not valid.Reaction:NC not ready.The NC switches to follow-up mode.Mode group not ready, also effective for single axes.NC Start disable in this channel.Interface signals are set.Ala...

  • Page 436

    NC alarms Alarms436 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Mode group not ready.The NC switches to follow-up mode.Channel not ready.NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm.Remedy:Please inform the authorized personnel/service depa...

  • Page 437

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1437NC alarms Definitions:Alarm occurs on the control when a measurement was made without the encoder hardware (simulated encoder).Reaction:Local alarm reaction.NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on ...

  • Page 438

    NC alarms Alarms438 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:- Set P2038 = 1 or- Set P0922 = 100...199 or - Set bit 15 of MD13070 $MN_DRIVE_FUNCTION_MASK (note the boundary conditions, see above)and execute a Power ON in each case.Program Continuation:Switch control OFF - ON.26027Axi...

  • Page 439

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1439NC alarms 26031Axis %1 configuration error master-slaveParameters:%1 = Axis name, spindle numberDefinitions:The alarm is output when the same machine axis has been configured as a master and a slave axis. Each of the axes in the master/slave...

  • Page 440

    NC alarms Alarms440 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA126051[Channel %1: ] In block %2 unanticipated stop crossed in continuous path modeParameters:%1 = Channel number%2 = Block number, labelDefinitions:The path interpolation did not stop, as required, at the end of the block, but wil...

  • Page 441

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1441NC alarms 26054[Channel %1: ] Block %2 interpolation warning in Look Ahead (module %3, problem %4)Parameters:%1 = Channel number%2 = Block number, label%3 = Module identifier%4 = Error codeDefinitions:The computer performance is inadequate t...

  • Page 442

    NC alarms Alarms442 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA126075[Channel %1: ] Axis %2 not available for the NC program, as exclusively controlled by the PLCParameters:%1 = Channel%2 = Axis, spindleDefinitions:The axis is exclusively controlled by the PLC. Therefore, the axis is not avail...

  • Page 443

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1443NC alarms 26082[Channel %1: ] ESR for PLC-controlled axis %2 has been triggeredParameters:%1 = Channel%2 = Axis, spindleDefinitions:An axial ESR has been triggered for an individual axis (PLC-controlled axis):The display can be suppressed by...

  • Page 444

    NC alarms Alarms444 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA126102Axis %1 drive %2 sign of life missingParameters:%1 = Axis name, spindle number%2 = Drive numberDefinitions:For PROFIdrive only:The sign-of-life cell is no longer being updated by the drive.Reaction:Mode group not ready.The NC...

  • Page 445

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1445NC alarms Reaction:Mode group not ready.The NC switches to follow-up mode.Channel not ready.NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm.Remedy:Possible causes:- MD 30240 $MA_ENC_TYPE not equal to...

  • Page 446

    NC alarms Alarms446 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Do not apply $AA_ESR_ENABLE[Achse] = 1 to neutral axes (apart from single axes).Alarm can be suppressed via MD11415 $MN_SUPPRESS_ALARM_MASK_2 bit 6 = 1.Program Continuation:Clear alarm with the Delete key or NC START.26122[...

  • Page 447

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1447NC alarms 3: Writing one or more ESR parameters in SINAMICS was prevented. Activate the output of additional information alarms through MD11411 $MN_ENABLE_ALARM_MASK, bit 1 = 1.Program Continuation:Clear alarm with the RESET key. Restart p...

  • Page 448

    NC alarms Alarms448 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA126204[Channel %1: ] Block %2: The chain element %3 referred to in $NK_NEXT[%4] is already contained in the chainParameters:%1 = Channel number%2 = Block number, label%3 = Name of the next chain link%4 = Index of the chain elementD...

  • Page 449

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1449NC alarms Definitions:The specified parallel chain element was not found.Reaction:Correction block is reorganized.Interface signals are set.Alarm display.Remedy:In $NK_PARALLEL[...], specify the name of an existing chain element.Program Cont...

  • Page 450

    NC alarms Alarms450 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Reduce the amount of the value in the named component or increase the permitted limit value in $NK_A_OFF_FINE_LIM.Program Continuation:Clear alarm with NC START or RESET key and continue the program.26216[Channel %1: ] Bloc...

  • Page 451

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1451NC alarms Remedy:Use a permissible type.Program Continuation:Clear alarm with NC START or RESET key and continue the program.26222[Channel %1: ] Block %2: The names of the protection areas $NP_PROT_NAME[%3] and $NP_PROT_NAME[%4] are the same...

  • Page 452

    NC alarms Alarms452 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA126226[Channel %1: ] Block %2: Invalid protection area type in $NP_TYPE[%3]Parameters:%1 = Channel number%2 = Block number, label%3 = Index of protection area elementDefinitions:An invalid type of protection area element was entere...

  • Page 453

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1453NC alarms Definitions:If an explicitely specified protection area element is referred to in a tool protection area with $NP_1ST_PROT, it must be of the type "FRAME".Reaction:Correction block is reorganized.Interface signals are set...

  • Page 454

    NC alarms Alarms454 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA126233[Channel %1: ] Block %2: The maximum permissible number of tool protection zone elements has been exceeded.Parameters:%1 = Channel number%2 = Block number, labelDefinitions:The maximum permissible number of protection zone el...

  • Page 455

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1455NC alarms Definitions:A closed definition chain was found, i.e. a protection area element contains the protection area of which it is a part.Reaction:Correction block is reorganized.Interface signals are set.Alarm display.Remedy:Change defin...

  • Page 456

    NC alarms Alarms456 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Enter in $NP_ADD[...] a protection area not linked with the kinematic chain or delete the reference to a kinematic chain in the protection area to be added or delete the entry in $NP_ADD[...].Program Continuation:Clear alar...

  • Page 457

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1457NC alarms 26246[Channel %1: ] Block %2: Parameter $NP_PARA[%3,%4] is invalidParameters:%1 = Channel number%2 = Block number, label%3 = Index of protection area element%4 = Index of parameters Definitions:An invalid parameter value for defini...

  • Page 458

    NC alarms Alarms458 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA126252[Channel %1: ] Block %2: No name was entered in $NP_COLL_PAIR[%3, %4].Parameters:%1 = Channel number%2 = Block number%3 = 1st index%4 = 2nd indexDefinitions:Only one name was entered in the collision pair $NP_COLL_PAIR[n, 0] ...

  • Page 459

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1459NC alarms Definitions:In the collision pair element entered, a protection area was specified, which is not anchored to a kinematic chain, which is part of the kinematic description of the machine. Only protection areas with a known position ...

  • Page 460

    NC alarms Alarms460 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Correction block is reorganized.Alarm display.NC Stop on alarm.Remedy:Change NC program or definition of the protection areas involved.Adjust MD18896 $MN_MM_MAXNUM_3D_COLLISION.Program Continuation:Clear alarm with NC STA...

  • Page 461

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1461NC alarms 26267[channel %1: ] block %2: error %3 when calling WORKPIECE or FIXTURE process.Parameters:%1 = Channel number%2 = Block number%3 = Error codeDefinitions:When calling the WORKPIECE or FIXTURE process, an error has incurred. The er...

  • Page 462

    NC alarms Alarms462 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Correction block is reorganized.Alarm display.NC Stop on alarm.Remedy:Call function with valid parameters.Program Continuation:Clear alarm with NC START or RESET key and continue the program.26270[Channel %1: ] Block %2: ...

  • Page 463

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1463NC alarms Remedy:Indicate in $NP_CHAIN_NAME[...] the name of an existing kinematic chain or define a chain with the name indicated.Program Continuation:Clear alarm with NC START or RESET key and continue the program.26276[Channel %1: ] Block...

  • Page 464

    NC alarms Alarms464 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Correction block is reorganized.Interface signals are set.Alarm display.Remedy:Enter a valid name in $NK_AXIS[...]. In a regular case (without OEM software), that is a machine axis identifier.Enter the type of element in ...

  • Page 465

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1465NC alarms Remedy:Protection zones and kinematic chain must be defined without errors.This is achieved by calling the procedure PROTA and closing it without errors.Program Continuation:Clear alarm with NC START or RESET key and continue the p...

  • Page 466

    NC alarms Alarms466 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Increase the number of allowed Protection Area Facet elements (MD18895 $MN_MM_MAXNUM_3D_FACETS) or reduce the number of defined facets in the CAD file.Program Continuation:Clear alarm with NC START or RESET key and continue...

  • Page 467

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1467NC alarms Definitions:The CAD file does not contain valid VRML data.Reaction:Correction block is reorganized.Interface signals are set.Alarm display.Remedy:Check the format of the input CAD/VRML data.Program Continuation:Clear alarm with NC ...

  • Page 468

    NC alarms Alarms468 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Even if the axis is already referenced, there is no confirmation that referencing has supplied the correct result. For example, wrong results can occur if the axis was moved after the control was switched off, with the result that...

  • Page 469

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1469NC alarms - 12 Limit position MD36935 $MA_SAFE_POS_LIMIT_MINUS[0].- 13 Limit position MD36934 $MA_SAFE_POS_LIMIT_PLUS[1].- 14 Limit position MD36935 $MA_SAFE_POS_LIMIT_MINUS[1].- 15 Cam position MD36936 $MA_SAFE_CAM_POS_PLUS[0] + MD36940 $MA...

  • Page 470

    NC alarms Alarms470 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1- 74 SG override factor 16 MD36932 $MA_SAFE_VELO_OVR_FACTOR[15].- 75 Velocity limit n<nx MD36946 $MA_SAFE_VELO_X or velocity hysteresis n<nx MD36947 $MA_SAFE_VELO_X_HYSTERESIS.- 76 Stop reaction SG1 MD36963 $MA_SAFE_VELO_ST...

  • Page 471

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1471NC alarms - 135 Cam position MD36936 $MA_SAFE_CAM_POS_PLUS[15] + MD36940 $MA_SAFE_CAM_TOL.- 136 Cam position MD36936 $MA_SAFE_CAM_POS_PLUS[15].- 137 Cam position MD36937 $MA_SAFE_CAM_POS_MINUS[15] + MD36940 $MA_SAFE_CAM_TOL.- 138 Cam positio...

  • Page 472

    NC alarms Alarms472 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1- 198 Cam track assignment SN4 MD36938 $MA_SAFE_CAM_TRACK_ASSIGN[3].- 199 Cam track assignment SN5 MD36938 $MA_SAFE_CAM_TRACK_ASSIGN[4].- 200 Cam track assignment SN6 MD36938 $MA_SAFE_CAM_TRACK_ASSIGN[5].- 201 Cam track assignment...

  • Page 473

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1473NC alarms Reaction:NC Start disable in this channel.Alarm display.A Stop F was triggered.If safe monitoring was active, STOP B was also triggered automatically. In this case, a power OFF/ON of the control will be required.Remedy:Find the dif...

  • Page 474

    NC alarms Alarms474 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA150: Position actual value + limit value SG4. 51: Position actual value - limit value SG4. 52: Standstill position + tolerance. 53: Standstill position - tolerance. 54: Position actual value "+ nx" + tolerance. 55: Positi...

  • Page 475

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1475NC alarms 113: Safe cam 10- (+ tolerance). Enter MDs consistently.114: Safe cam 10-. Enter MDs consistently.115: Safe cam 11+ (+ tolerance). Enter MDs consistently.116: Safe cam 11+. Enter MDs consistently.117: Safe cam 11- (+ tolerance). En...

  • Page 476

    NC alarms Alarms476 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1176: Safe cam 26+. Enter MDs consistently.177: Safe cam 26- (+ tolerance). Enter MDs consistently.178: Safe cam 26-. Enter MDs consistently.179: Safe cam 27+ (+ tolerance). Enter MDs consistently.180: Safe cam 27+. Enter MDs consi...

  • Page 477

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1477NC alarms tact).1001: Incorrect control timer initialization. See F01711.1002: User agreement timer expired. 1003: Reference tolerance violated. Compare the reference position with the current safe actual position.1004: Plausibility of user ...

  • Page 478

    NC alarms Alarms478 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:A difference has been found on the specified safe input. The state of the specified input signal differed in the two mon-itoring channels NCK and drive during the duration set in $MA_SAFE_MODE_SWITCH_TIME.Monitoring in...

  • Page 479

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1479NC alarms Remedy:Alarm disappears automatically when the test has been exited by deleting the "Test stop of external shutdown" SGE.Program Continuation:Alarm display showing cause of alarm disappears. No further operator action nec...

  • Page 480

    NC alarms Alarms480 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm.Axis stop with STOP A, C, D or E, depending on the configuration in MD $MA_SAFE_VELO_STOP_MODE or MD $MA_SAFE_VELO_STOP_REACTION. R...

  • Page 481

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1481NC alarms Reaction:NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm.Trigger a LIFTFAST ASUB and internal activation of the safe operational stop (SBH) after expiry of the time set in MD $MA_SAFE_STOP_...

  • Page 482

    NC alarms Alarms482 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Alarm display.NC Stop on alarm.Channel not ready.Trigger a "Deceleration on the current limit" and activation of the timer for a switchover after STOP A (see MD $MA_SAFE_PULSE_DISABLE_DELAY).Remedy:Eliminate causes of al...

  • Page 483

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1483NC alarms Remedy:Reduce the limit value in MD $MA_SAFE_VELO_LIMIT[x], x = (2nd alarm parameter) - 1, or correct the setting of the gear factors.Program Continuation:Switch control OFF - ON.27032Axis %1 checksum error of safe monitoring. Conf...

  • Page 484

    NC alarms Alarms484 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1- 16. In MD $MA_SAFE_REFP_POS_TOL, a value greater than 1mm was entered for a linear axis.- 17. The limit values for the "n<n_x" monitoring, calculated from MD $MA_SAFE_VELO_X and MD $MA_SAFE_POS_TOL, are of equal siz...

  • Page 485

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1485NC alarms - 49. More than 15 cams have been assigned to one cam track by $MA_SAFE_CAM_TRACK_ASSIGN[n]. ("Safe cam track" function")- 50. Cam modulo functionality has been selected in $MA_SAFE_MODULO_RANGE, however this is not ...

  • Page 486

    NC alarms Alarms486 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:If the alarm occurs during setup, proceed as follows:- Confirm the checksum SAFE_ACT_CHECKSUM[1] (keyswitch position 3 or password has to be entered). Resume setup.If the alarm occurs after an encoder module or a DRIVE-CLiQ...

  • Page 487

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1487NC alarms 27038Axis %1 value %2 in drive parameter %3 violates the limits of NCK MD %4.Parameters:%1 = Axis number%2 = Value in drive parameter%3 = Drive parameter number, for example parameter 979.%4 = NCK machine data name.Definitions:A SI...

  • Page 488

    NC alarms Alarms488 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA127040Axis %1 waiting for motor module.Parameters:%1 = Axis name, spindle numberDefinitions:Alarm on ramp-up as long as the motor module is not yet ready for SI.Communication to the motor module is not yet active on ramp-up, the sa...

  • Page 489

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1489NC alarms Remedy:Check machine data, have the checksum recalculated and confirm. Re-accept the safety functions (connections NCK axis - drive/encoder).Program Continuation:Switch control OFF - ON.27070Checksum error parameterization SPL and ...

  • Page 490

    NC alarms Alarms490 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA127073Checksum error S7 PROFIsafe configuration. Confirmation and acceptance test required!Definitions:The F parameters required for PROFIsafe communication are protected by a checksum. The alarm indicates that the current checksum...

  • Page 491

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1491NC alarms The display of alarm 27090 can be modified via MD $MN_SAFE_ALARM_SUPPRESS_LEVEL: MD $MN_SAFE_ALARM_SUPPRESS_LEVEL = 2 : Alarm 27090 will now only be displayed for the first data difference found.Reaction:Alarm display.Trigger a STO...

  • Page 492

    NC alarms Alarms492 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:A checksum error has occurred in the NCK SPL. The file /_N_CST_DIR/_N_SAFE_SPF was subsequently modified. The safe programmable logic (SPL) in the NCK may have been corrupted. Parameter %1 provides more information abo...

  • Page 493

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1493NC alarms 27097SPL start not executedDefinitions:SPL start not executed after predefined timeout in MD SAFE_SPL_START_TIMEOUT.Reaction:Alarm display.Remedy:Find the cause of the failure of the SPL to start. Possible causes may be:- There is ...

  • Page 494

    NC alarms Alarms494 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Even if the axis is already referenced, there is no confirmation that referencing has supplied the correct result. For example, wrong results can occur if the axis was moved after the control was switched off, with the result that...

  • Page 495

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1495NC alarms Monitoring status (%3, %4):- OFF = Monitoring is inactive in this monitoring channel- OK = Monitoring is active in this monitoring channel, limit values are not violated- L+ = Monitoring is active in this monitoring channel, upper ...

  • Page 496

    NC alarms Alarms496 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1The following applies to the "Safe cam track" function: (each of result lists 3-7 contains 6 cam results)- Safe cam 1+: bit 0, 1 in result list 3- Safe cam 2+: bit 4, 5 in result list 3- Safe cam 3+: bit 8, 9 in res...

  • Page 497

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1497NC alarms The following applies to the "Safe cam track" function: (each of result lists 3-7 contains 6 cam results)- Safe cam 1-: bit 2, 3 in result list 3- Safe cam 2-: bit 6, 7 in result list 3- Safe cam 3-: bit 10,11 in res...

  • Page 498

    NC alarms Alarms498 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Monitoring status (%2, %3):- OFF = Monitoring is inactive in this monitoring channel- OK = Monitoring is active in this monitoring channel, limit values are not violated- L+ = Monitoring is active in this monitoring channel, upper...

  • Page 499

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1499NC alarms 27111Axis %1 fault during encoder evaluation of the safe actual value.Parameters:%1 = Axis numberDefinitions:The redundantly determined safe actual value does not match the fine resolution actual value of the same encoder.Reaction:...

  • Page 500

    NC alarms Alarms500 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA127124Stop A triggered at least in 1 axisDefinitions:This is only an informational alarm indicating that Stop A has been triggered in at least 1 axis and Power On is required for alarm acknowledgment.This alarm occurs if the alarm ...

  • Page 501

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1501NC alarms 27140Waiting for motor module of at least one axis.Definitions:Alarm during ramp-up as long as the motor module of at least one axis is not yet ready for SI.Communication to the motor module during ramp-up has not yet been activate...

  • Page 502

    NC alarms Alarms502 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA127202PROFIsafe: MD %1[%2]: address %3 errorParameters:%1 = MD name%2 = MD array index%3 = Parameterized PROFIsafe addressDefinitions:An incorrect PROFIsafe address was entered in the specified machine data. The value must be great...

  • Page 503

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1503NC alarms Remedy:Correct the MD.Program Continuation:Switch control OFF - ON.27205PROFIsafe: number of signals in MD %1 [%2] <> MD %3[%4]Parameters:%1 = MD name 1%2 = MD array index for MD name 1%3 = MD name 2%4 = MD array index for MD...

  • Page 504

    NC alarms Alarms504 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Reduce the number of sub slots by changing the splitting of F user data of the PROFIsafe module.Program Continuation:Switch control OFF - ON.27208PROFIsafe: MD %1[%2]: max. sub-slot address %3 exceeded.Parameters:%1 = MD na...

  • Page 505

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1505NC alarms Remedy:Check the PROFIsafe addresses in the NCK MD and S7 PROFIBUS configuration.Program Continuation:Switch control OFF - ON.27222PROFIsafe: S7 F module PROFIsafe address %1 unknownParameters:%1 = PROFIsafe addressDefinitions:The ...

  • Page 506

    NC alarms Alarms506 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Check and correct the S7 F parameterization and NCK MD.Program Continuation:Switch control OFF - ON.27225PROFIsafe: slave %1, configuration error %2Parameters:%1 = PROFIBUS slave address%2 = Configuration errorDefinitions:A...

  • Page 507

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1507NC alarms Remedy:- Check the PLC operating system and NCK software versions.- Upgrade the PLC operating system.- Delete the NCK F parameterization.Program Continuation:Switch control OFF - ON.27242PROFIsafe: F module %1, %2 faultyParameters:...

  • Page 508

    NC alarms Alarms508 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:An error occurred in the PROFIsafe communication between the F master and the specified F module which was detected by the component (master/slave) shown in parameter %2.The error code specifies the error type:- %3 = T...

  • Page 509

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1509NC alarms 27254PROFIsafe: F module %1, error on channel %2; %3<ALSI>Parameters:%1 = PROFIsafe address or name%2 = Channel type, channel number%3 = System variable array index extensionDefinitions:The F module signals that an error occu...

  • Page 510

    NC alarms Alarms510 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA127257PROFIsafe: %1 %2 reports system error %3 (%4)Parameters:%1 = Type of communication%2 = PROFIsafe address or name%3 = Error code%4 = ComponentDefinitions:A system error has been detected in the PROFIsafe communication. Dependi...

  • Page 511

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1511NC alarms Remedy:Correct cycle time via MD $MN_SAFE_SRDP_IPO_TIME_RATIO and/or $MN_IPO_CYCLE_TIMEProgram Continuation:Switch control OFF - ON.27301F_DP: MD %1[%2]: SPL interface faultyParameters:%1 = MD name%2 = MD array indexDefinitions:The...

  • Page 512

    NC alarms Alarms512 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA127303F_DP: Number of signals in MD %1 [%2] <> MD %3[%4]Parameters:%1 = MD name 1%2 = MD array index for MD name 1%3 = MD name 2%4 = MD array index for MD name 2Definitions:Different numbers of F user data signals have been p...

  • Page 513

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1513NC alarms Remedy:Correct the identifiers of the active SPL connections or deactivate SPL connections ($MN_SAFE_SDP/RDP_ENABLE_MASK).Program Continuation:Switch control OFF - ON.27350F_DP: %1 communication, connection %2 reports error %3Param...

  • Page 514

    NC alarms Alarms514 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Check the PROFIBUS communication and the communication partnerUser acknowledgment via DB18.FRDP_ACK_REI or NC-RESETNote to %3 = LS: Internal system error, can only be eliminated by PowerOn.Program Continuation:Alarm display...

  • Page 515

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1515NC alarms The name or the DP_DP_ID (identifier) of the SPL connection is displayed in %2.The PLC block that detected an error is displayed in %3.The detected cause of the error is displayed in %4.This alarm can be masked with MD $MN_SAFE_DIA...

  • Page 516

    NC alarms Alarms516 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Alarm display.Remedy:See drive documentation for fault codes/fault values.Program Continuation:Alarm display showing cause of alarm disappears. No further operator action necessary.27901PROFIBUS DP: SI fault on axis %1, c...

  • Page 517

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1517NC alarms 28002Error on activation of machine data, NCU network-wide machine data were modified by NCU %1Parameters:%1 = NCU numberDefinitions:During the activation of machine data with NEWCONFIG or during an operator panel RESET, NCU networ...

  • Page 518

    NC alarms Alarms518 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA128005NCU link: NCU %1 of the link network not running synchronouslyParameters:%1 = NCU numberDefinitions:Error message of the NCU link module. When the NCU link was powered up, the local NCU (indicated by the alarm) detected that ...

  • Page 519

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1519NC alarms Reaction:NC not ready.Channel not ready.NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm.Remedy:Check machine data configuration.Program Continuation:Switch control OFF - ON.28010NCU link: t...

  • Page 520

    NC alarms Alarms520 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:NC not ready.Channel not ready.NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm.Remedy:Check the hardware.Program Continuation:Switch control OFF - ON.28020NCU link: too many links...

  • Page 521

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1521NC alarms NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm.Remedy:Acknowledge the alarm on the NCU.Program Continuation:Restart part program.Clear alarm with the RESET key in all channels of this mode...

  • Page 522

    NC alarms Alarms522 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA129033[Channel %1: ] Axis exchange of axis %2 not possible, PLC axis movement not yet completedParameters:%1 = Channel number%2 = AxisDefinitions:A PLC axis has not yet reached its end position and cannot be returned to a channel o...

  • Page 523

    3AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1523Cycle alarms61000%[[Channel %1: ] Block %2: %]No tool offset activeParameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:D-...

  • Page 524

    Cycle alarms Alarms524 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161004[Channel %1: ] Block %2: Incorrect configuration of geometry axesParameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm d...

  • Page 525

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1525Cycle alarms 61009[Channel %1: ] Block %2: Active tool number = 0Parameters:%1 = Channel number%2 = Block number, labelDefinitions:No tool (T) has been programmed before the cycle call.Reaction:Interpreter stopNC Start disable in this channe...

  • Page 526

    Cycle alarms Alarms526 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161013[Channel %1: ] Block %2: Basic settings were changed, program cannot be executedParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:The basic settings are not compatible with the generated prog...

  • Page 527

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1527Cycle alarms 61018[Channel %1: ] Block %2: function %4 not executable with NCKParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Reaction:Interpreter stopNC Start disable in this channel.Interface signals are se...

  • Page 528

    Cycle alarms Alarms528 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:Program Continuation:Clear alarm with the RESET key. Restart part program61022[Channel %1: ] Block %2: Parameter %4 value ...

  • Page 529

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1529Cycle alarms Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:Program Continuation:Clear alarm with the RESET key. Restart part program61026[Channel %1: ] Block %2: Cycle cannot be exec...

  • Page 530

    Cycle alarms Alarms530 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:- use shorter program nameProgram Continuation:Clear alarm with the RESET key. Restart part program61030[Channel %1: ] Blo...

  • Page 531

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1531Cycle alarms Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:Program Continuation:Clear alarm with the RESET key. Restart part program61034[Channel %1: ] Block %2: File is full: %4Para...

  • Page 532

    Cycle alarms Alarms532 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:Program Continuation:Clear alarm with the RESET key. Restart part program61038[Channel %1: ] Block %2: Other file error: %...

  • Page 533

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1533Cycle alarms Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:Program Continuation:Clear alarm with the RESET key. Restart part program61042[Channel %1: ] Block %2: Program name %4 ille...

  • Page 534

    Cycle alarms Alarms534 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:Remove illegal character from file namePermitted characters are: letters, figures, underscore, slash with path nameProgram...

  • Page 535

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1535Cycle alarms 61048[Channel %1: ] Block %2: Multi-channel data not found in job list: %4Parameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alar...

  • Page 536

    Cycle alarms Alarms536 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161052[Channel %1: ] Block %2: Maximum spindle speed for main spindle not enteredParameters:%1 = Channel number%2 = Block number, labelDefinitions:Max. speed for main spindle was not entered.Reaction:Interpreter stopNC Start dis...

  • Page 537

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1537Cycle alarms 61056[channel %1: ] block %2: magazine location number too high: %4Parameters:%1 = Channel number%2 = Block number, labelDefinitions:The magazine location number entered was too high.Reaction:Interpreter stopNC Start disable in ...

  • Page 538

    Cycle alarms Alarms538 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161060%[[Channel %1: ] Block %2: %]Function requires tool managementParameters:%1 = Channel number%2 = Block number, labelDefinitions:--Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm di...

  • Page 539

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1539Cycle alarms 61064%[[Channel %1: ] Block %2: %]Invalid multitool location: %4Parameters:%1 = Channel number%2 = Block number, labelDefinitions:A multitool location was programmed, at which there is no multitool.Reaction:Interpreter stopNC St...

  • Page 540

    Cycle alarms Alarms540 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161103[Channel %1: ] Block %2: Number of holes is zeroParameters:%1 = Channel number%2 = Block number, labelDefinitions:Remedy:Check parameter NUM.Program Continuation:Clear alarm with the RESET key. Restart part program61104[Ch...

  • Page 541

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1541Cycle alarms 61107[Channel %1: ] Block %2: First drilling depth incorrectly definedParameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm di...

  • Page 542

    Cycle alarms Alarms542 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161111[Channel %1: ] Block %2: Infeed width is greater than the tool diameterParameters:%1 = Channel number%2 = Block number, labelDefinitions:The programmed infeed width is greater than the diameter of the active tool.Reaction:...

  • Page 543

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1543Cycle alarms 61115[Channel %1: ] Block %2: Approach or retract mode(straight / circle / plane / space) incorrectly definedParameters:%1 = Channel number%2 = Block number, labelDefinitions:The approach or retract mode to/from the contour has ...

  • Page 544

    Cycle alarms Alarms544 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161119[Channel %1: ] Block %2: Nominal or core diameter programmed incorrectlyParameters:%1 = Channel number%2 = Block number, labelDefinitions:The nominal or core diameter was incorrectly programmed.Reaction:Interpreter stopNC ...

  • Page 545

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1545Cycle alarms 61123[Channel %1: ] Block %2: CYCLE72 cannot be simulatedParameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:...

  • Page 546

    Cycle alarms Alarms546 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161127[Channel %1: ] Block %2: Wrong definition of tapping axis transformation ratio (machine data)Parameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Interpreter stopNC Start disable in this channel.Inter...

  • Page 547

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1547Cycle alarms 61131[Channel %1: ] Block %2: parameter _GEO incorrect, _GEO=%4Parameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.R...

  • Page 548

    Cycle alarms Alarms548 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161135[Channel %1: ] Block %2: incorrect parameter sequence for approaching target position: %4Parameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Interpreter stopNC Start disable in this channel.Interface...

  • Page 549

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1549Cycle alarms 61139[Channel %1: ] Block %2: error in function Tool monitoring in cyclesParameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm...

  • Page 550

    Cycle alarms Alarms550 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Check the set up of the counterspindle.Check machine data 20070 $MC_AXCONF_MACHAX_USED and 20080 $MC_AXCONF_CHANAX_NAME_TAB,Program Continuation:Clear alarm with the RESET key. Restart part program61143[Channel %1: ] Blo...

  • Page 551

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1551Cycle alarms Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:Check the set up of the B axis.Check machine data 20070 $MC_AXCONF_MACHAX_USED and 20080 $MC_AXCONF_CHANAX_NAME_TAB,Program...

  • Page 552

    Cycle alarms Alarms552 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161150[Channel %1: ] Block %2: Tool cannot be aligned - error code: %4Parameters:%1 = Channel number%2 = Block number, labelDefinitions:Remedy:Causes of error: 1st error code = A -> only new swivel plane permitted, see param...

  • Page 553

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1553Cycle alarms 61155[Channel %1: ] Block %2: Unit for plane infeed wrongly programmedParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Remedy:Unit for plane infeed possible only in mm or % of tool diameter61156[C...

  • Page 554

    Cycle alarms Alarms554 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161161[Channel %1: ] Block %2: Centering diameter or tool parameter (diameter, tip angle) are incorrectParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Remedy:- Diameter of centering with tip angl...

  • Page 555

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1555Cycle alarms 61167[Channel %1: ] Block %2: Transformation not set up: %4Parameters:%1 = Channel number%2 = Block number, labelDefinitions:Remedy:The specified transformation is not set up. Set up the transformation.61168[Channel %1: ] Block ...

  • Page 556

    Cycle alarms Alarms556 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161174[Channel %1: ] Block %2: Not possible to align milling tool with active turning toolParameters:%1 = Channel number%2 = Block number, labelDefinitions:It is not possible to align milling tools with an active turning tool.Re...

  • Page 557

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1557Cycle alarms 61178[Channel %1: ] Block %2: code page not presentParameters:%1 = Channel number%2 = Block number, labelDefinitions:The specified code page is not supported by the cycle.Reaction:Interpreter stopNC Start disable in this channel...

  • Page 558

    Cycle alarms Alarms558 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161183[Channel %1: ] Block %2: Swivel CYCLE800: Retraction mode parameter lies outside value range: %4Parameters:%1 = Channel number%2 = Block number, labelDefinitions:The value of the retraction mode parameter (_FR) lies outsid...

  • Page 559

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1559Cycle alarms Definitions:Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:Error code: See current cycles software version notes in siemense.txtProgram Continuation:Clear alarm with the ...

  • Page 560

    Cycle alarms Alarms560 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161191[Channel %1: ] Block %2: Multi-axis transformation not set up. Error code: %4Parameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Interpreter stopNC Start disable in this channel.Interface signals are...

  • Page 561

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1561Cycle alarms 61195[Channel %1: ] Block %2: Aligning a turning tool is only possible with active turning toolParameters:%1 = Channel number%2 = Block number, labelDefinitions:Aligning turning tools is only possible with one active turning too...

  • Page 562

    Cycle alarms Alarms562 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161199[Channel %1: ] Block %2: Swiveling - tool not allowed -> Error code: %4Parameters:%1 = Channel number%2 = Block number, labelDefinitions:Error is also output if no swivel data record is active and only tool approach is ...

  • Page 563

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1563Cycle alarms 61203[Channel %1: ] Block %2: No position cycleParameters:%1 = Channel number%2 = Block number, labelDefinitions:No positioning cycle was programmed in the machining block.Reaction:Interpreter stopNC Start disable in this channe...

  • Page 564

    Cycle alarms Alarms564 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161207[Channel %1: ] Block %2: No counterspindle step found for synchronizingParameters:%1 = Channel number%2 = Block number, labelDefinitions:No counterspindle step was found in any channel with which this channel could synchro...

  • Page 565

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1565Cycle alarms 61211[Channel %1: ] Block %2: Absolute reference missingParameters:%1 = Channel number%2 = Block number, labelDefinitions:An incremental indication was made, but the absolute reference is unknown.Reaction:Interpreter stopNC Star...

  • Page 566

    Cycle alarms Alarms566 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:Check the blank spigot dimensions. The blank spigot must be larger than the production part spigot.Remedy:Check parameters _AP1 and _AP2.61216%[[Channel %1: ] Block %2: %]Feed/tooth only possible with cutting toolsP...

  • Page 567

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1567Cycle alarms Remedy:Select a suitable tool.Program Continuation:Clear alarm with the RESET key. Restart part program61220[Channel %1: ] Block %2: Tool radius too smallParameters:%1 = Channel number%2 = Block number, labelDefinitions:The tool...

  • Page 568

    Cycle alarms Alarms568 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Enter a greater value for the approach path.Program Continuation:Clear alarm with the RESET key. Restart part program61224[Channel %1: ] Block %2: Retract path too smallParameters:%1 = Channel number%2 = Block number, la...

  • Page 569

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1569Cycle alarms Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:If possible, lower retraction plane. Select alternative solution for swiveling (direction +/-) or clamp on workpiece differ...

  • Page 570

    Cycle alarms Alarms570 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:Before a ShopMill program can be executed, it has to be tested by ShopMill.Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:The program first has to be simulat...

  • Page 571

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1571Cycle alarms 61235[Channel %1: ] Block %2: ShopTurn program %4 cannot be executed as not tested by ShopTurn.Parameters:%1 = Channel number%2 = Block number, label%4 = Program nameDefinitions:Before a ShopTurn program can be executed, it has ...

  • Page 572

    Cycle alarms Alarms572 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Please contact the responsible Siemens regional office.Program Continuation:Clear alarm with the RESET key. Restart part program61239[Channel %1: ] Block %2: Tool change point lies within retraction area!Parameters:%1 = ...

  • Page 573

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1573Cycle alarms Remedy:Check the programmed machining direction.Program Continuation:Clear alarm with the RESET key. Restart part program61243[Channel %1: ] Block %2: Correct tool change point, tool tip in retraction area!Parameters:%1 = Channe...

  • Page 574

    Cycle alarms Alarms574 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Increase safety clearance.Program Continuation:Clear alarm with the RESET key. Restart part program61247[Channel %1: ] Block %2: Blank radius too smallParameters:%1 = Channel number%2 = Block number, labelDefinitions:The...

  • Page 575

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1575Cycle alarms Remedy:Increase key width/edge length.Program Continuation:Clear alarm with the RESET key. Restart part program61251[Channel %1: ] Block %2: Width across flats/edge length too largeParameters:%1 = Channel number%2 = Block number...

  • Page 576

    Cycle alarms Alarms576 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:specify another Z1 position for gripping the counterspindle.Program Continuation:Clear alarm with the RESET key. Restart part program61255[Channel %1: ] Block %2: Error during cut-off: Tool broken?Parameters:%1 = Channel...

  • Page 577

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1577Cycle alarms Definitions:The parameters for the counterspindle chuck in the spindle chuck data have not been assigned.Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:Indicate parameter...

  • Page 578

    Cycle alarms Alarms578 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161262[Channel %1: ] Block %2: pitch not possible with selected toolParameters:%1 = Channel number%2 = Block number, labelDefinitions:The pitch of the tap does not match the programmed pitch.Reaction:Interpreter stopNC Start dis...

  • Page 579

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1579Cycle alarms 61266[Channel %1: ] Block %2: Illegal machining directionParameters:%1 = Channel number%2 = Block number, labelDefinitions:In face milling, the delimitations and the direction of machining do not match.Reaction:Interpreter stopN...

  • Page 580

    Cycle alarms Alarms580 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161270%[[Channel %1: ] Block %2: %]Chamfer width too smallParameters:%1 = Channel number%2 = Block number, labelDefinitions:Chamfer width selected too small.Reaction:Interpreter stopNC Start disable in this channel.Interface sig...

  • Page 581

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1581Cycle alarms 61274%[[Channel %1: ] Block %2: %]Invalid tool angleParameters:%1 = Channel number%2 = Block number, labelDefinitions:Invalid tool angle.Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm d...

  • Page 582

    Cycle alarms Alarms582 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161278[Channel %1: ] Block %2: If tool angle is larger than 90°, both tool diameters must be equalParameters:%1 = Channel number%2 = Block number, labelDefinitions:For tool angles larger than 90°, the two tool diameters must b...

  • Page 583

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1583Cycle alarms 61282[Channel %1: ] Block %2: end point of machining outside retraction planesParameters:%1 = Channel number%2 = Block number, labelDefinitions:The end point of machining is outside the retraction planes.Reaction:Interpreter sto...

  • Page 584

    Cycle alarms Alarms584 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161286[Channel %1: ] Block %2: machining not possible, check tool angle.Parameters:%1 = Channel number%2 = Block number, labelDefinitions:Machining not possible with the specified tool.Reaction:Interpreter stopNC Start disable i...

  • Page 585

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1585Cycle alarms 61290[Channel %1: ] Block %2:Tool spindle not set upParameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:CYCLE...

  • Page 586

    Cycle alarms Alarms586 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Program Continuation:Clear alarm with the RESET key. Restart part program61294[Channel %1: ] Block %2: Active radius/diameter setting does not match reset settingParameters:%1 = Channel number%2 = Block number, labelDefinitions...

  • Page 587

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1587Cycle alarms 61298[Channel %1: ] Block %2: No work offset entered for main spindleParameters:%1 = Channel number%2 = Block number, labelDefinitions:No work offset has been specified for the main spindle.Reaction:Interpreter stopNC Start disa...

  • Page 588

    Cycle alarms Alarms588 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:The measuring probe collided with an obstacle when being positioned.Remedy:- Check spigot diameter (may be too small)- Check measuring distance (may be too long)61303[Channel %1: ] Block %2: Safety margin exceededPa...

  • Page 589

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1589Cycle alarms 61307[Channel %1: ] Block %2: Incorrect measuring variantParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Remedy:For 840D sl - up to SW 2.6 SP1 and for 828D - up to SW 4.3:- The value of parameter...

  • Page 590

    Cycle alarms Alarms590 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161311[Channel %1: ] Block %2: No D number activeParameters:%1 = Channel number%2 = Block number, labelDefinitions:No tool offset for the measuring probe (for workpiece measurement) or no tool offset for the active tool (for too...

  • Page 591

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1591Cycle alarms 61316[Channel %1: ] Block %2: Center and radius cannot be determinedParameters:%1 = Channel number%2 = Block number, labelDefinitions:No circle can be calculated from the measured points, as all measured points lie on a straight...

  • Page 592

    Cycle alarms Alarms592 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:For 840D sl - up to SW 2.6 SP1 and for 828D - up to SW 4.3: - Check parameter _KNUMFor 840D sl - as from SW 2.7 and for 82...

  • Page 593

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1593Cycle alarms Remedy:For 840D sl - to SW 2.6 SP1 and for 828D - to SW 4.3 : - Milling measuring cycles: - Parameter for the measuring direction (_MD) has an incorrect value.For 840D sl - from SW 2.7 and for 828D - from SW 4.4 : - ...

  • Page 594

    Cycle alarms Alarms594 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161331[Channel %1: ] Block %2: Angle too large, change measuring axisParameters:%1 = Channel number%2 = Block number, labelDefinitions:Remedy:For 840D sl - up to SW 2.6 SP1 and for 828D - up to SW 4.3: - Parameter starting a...

  • Page 595

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1595Cycle alarms 61336[Channel %1: ] Block %2: Geometry axes do not existParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:No geometry axes configured.Remedy:Machine data in MD 20060 must be changed.61337[Channel %...

  • Page 596

    Cycle alarms Alarms596 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161341[Channel %1: ] Block %2: Probe not calibrated or the number of the field of the probe parameter is incorrectParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Remedy:Calibrate the probe before...

  • Page 597

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1597Cycle alarms Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:For 840D sl - up to SW 2.6 SP1 and for 828D - up to SW 4.3:: - Parameter _SETV[0] or _SETV[1] is empty or less than 0.For 8...

  • Page 598

    Cycle alarms Alarms598 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:For 840D sl - up to SW 2.6 SP1 and for 828D - up to SW 4.3: - Measuring feed and/or spindle speed during tool measurement with turning spindle not entered in GUD variable _MFS. - Check parameter _MFS[0]For 840D ...

  • Page 599

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1599Cycle alarms Definitions:The log file is already used by an NC program.Remedy:Check parameter _PROTNAME[1]61357%[[Channel %1: ] Block %2: %] Not enough NC memory or too many files, directories in the NCParameters:%1 = Channel number%2 = Bloc...

  • Page 600

    Cycle alarms Alarms600 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161362[Channel %1: ] Block %2: Cycle118: No. of values too largeParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:4th parameter for CYCLE118 is larger than 10.Remedy:Reduce the 4th parameter (PAR4)...

  • Page 601

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1601Cycle alarms 61367[channel %1: ] block %2: parameters %4 are identicalParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Remedy:For 840D sl - up to SW 2.6 SP1 and for 828D - up tp SW 4.3: - Specify different...

  • Page 602

    Cycle alarms Alarms602 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161372[Channel %1: ] Block %2: selected meas.variant requires SPOS-capable spindleParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Remedy:Change measuring variant or check machine equipment.61373[...

  • Page 603

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1603Cycle alarms 61378[Channel %1: ] Block %2: Tool spindle is not the master spindleParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Remedy:Before calling the measuring cycles, the tool spindle must be defined as...

  • Page 604

    Cycle alarms Alarms604 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161404[Channel %1: ] Block %2: Tool correction not executedParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Remedy:Check the dependent tool specifications.61405[Channel %1: ] Block %2: Tool enviro...

  • Page 605

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1605Cycle alarms 61410[Channel %1: ] Block %2 access to nonexistent tool element or propertyParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Remedy:The variable to be corrected requires an option or an increase in...

  • Page 606

    Cycle alarms Alarms606 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161416[Channel %1: ] Block %2: Probe number is greater than the maximum number of fieldsParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Remedy:Check parameter S_PRNUMMeasure workpiece: Parameter ...

  • Page 607

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1607Cycle alarms Remedy:Causes of error:1. Error code = A -> _OVR[] - parameter field too small. Check GUD definition. DEF CHAN REAL _OVR[72] (up to MZ06.03.xx.xx =32)61422[channel %1: ] block %2: parameter meas...

  • Page 608

    Cycle alarms Alarms608 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161426[Channel %1: ] Block %2: Sum of the active offsets does not equal zero - Error code: %4Parameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Remedy:Error causes:Check the overview of active offse...

  • Page 609

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1609Cycle alarms 61430[Channel %1: ] Block %2: Kinematic vectors not computed - Error code: %4Parameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Remedy:Causes of error: 1. Error code = A -> Plausibility of ...

  • Page 610

    Cycle alarms Alarms610 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161443[Channel %1: ] Block %2: Advance angle %4 or greater/less than +/-90° or +/-120°Parameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Remedy:For 840D sl - up to SW 2.6 SP1 and for 828D - up to ...

  • Page 611

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1611Cycle alarms Remedy:Reset simulationProgram Continuation:Clear alarm with the RESET key. Restart part program61502[Channel %1: ] Block %2: No tool offset activeParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:...

  • Page 612

    Cycle alarms Alarms612 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161507[Channel %1: ] Block %2: safety clearance is smaller than 1mmParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Remedy:Program Continuation:Clear alarm with the RESET key. Restart part program...

  • Page 613

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1613Cycle alarms 61512[Channel %1: ] Block %2: Incorrect longitudinal positionParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Remedy:Program Continuation:Clear alarm with the RESET key. Restart part program61513[...

  • Page 614

    Cycle alarms Alarms614 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161518[Channel %1: ] Block %2: Shoulder height of the grinding wheel must be greater than the grinding wheel radiusParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Remedy:Change shoulder height or...

  • Page 615

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1615Cycle alarms 61523[Channel %1: ] Block %2: Zero signal of calipers missingParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Remedy:Check calipers signalProgram Continuation:Clear alarm with the RESET key. Resta...

  • Page 616

    Cycle alarms Alarms616 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161529[Channel %1: ] Block %2: Dimensional notation INCH programmedParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Remedy:Basic system MD $MN_SCALING_SYSTEM_IS_METRIC does not correspond to progr...

  • Page 617

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1617Cycle alarms 61540[Channel %1: ] Block %2: Incorrect D number / dresser D field activeParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Remedy:A tool D number must be programmed that is < _GC_DNUMProgram Con...

  • Page 618

    Cycle alarms Alarms618 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161545[Channel %1: ] Block %2: Width of grinding wheel worn downParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Remedy:New grinding wheel required, or check limit values in the grinding wheel dat...

  • Page 619

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1619Cycle alarms 61555[Channel %1: ] Block %2: Diameter of grinding wheel ==0, GWPS cannot be calculatedParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Remedy:Check diameterProgram Continuation:Clear alarm with t...

  • Page 620

    Cycle alarms Alarms620 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161560[Channel %1: ] Block %2: Infeed in Z direction too big per stroke, or wheel too narrowParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Remedy:Reduce infeed path parameter or use other toolPr...

  • Page 621

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1621Cycle alarms 61601[Channel %1: ] Block %2: Finished part diameter too smallParameters:%1 = Channel number%2 = Block number, labelDefinitions:Remedy:Check parameter SPD or DIATH.Program Continuation:Clear alarm with the RESET key. Restart par...

  • Page 622

    Cycle alarms Alarms622 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161606[Channel %1: ] Block %2: Error during contour preparationParameters:%1 = Channel number%2 = Block number, labelDefinitions:An error has been found on conditioning the contour. This alarm is always related to one of NCK ala...

  • Page 623

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1623Cycle alarms 61611[Channel %1: ] Block %2: No point of intersection foundParameters:%1 = Channel number%2 = Block number, labelDefinitions:No intersection could be calculated with the contour.Reaction:Interpreter stopNC Start disable in this...

  • Page 624

    Cycle alarms Alarms624 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161615[Channel %1: ] Block %2: %4- Mirroring in the work offset is not permitted for the counterspindleParameters:%1 = Channel number%2 = Block number, labelDefinitions:The work offset for counterspindle machining must not have ...

  • Page 625

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1625Cycle alarms 61619[Channel %1: ] Block %2: Main spindle has not been correctly set upParameters:%1 = Channel number%2 = Block number, labelDefinitions:The main spindle has not been correctly set up.Reaction:Interpreter stopNC Start disable i...

  • Page 626

    Cycle alarms Alarms626 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Set up a tool with carrier with the rotary axes: B axis and tool spindle.Set the identifier "B axis kinematics".Program Continuation:Clear alarm with the RESET key. Restart part program61623[Channel %1: ] Block...

  • Page 627

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1627Cycle alarms 61626[Channel %1: ] Block %2: With the programmed angular values, the tool tip is not located in the turning plane %4Parameters:%1 = Channel number%2 = Block number, labelDefinitions:Angular values were programmed where the tool...

  • Page 628

    Cycle alarms Alarms628 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:- Check whether the labels exist in the machined part contourProgram Continuation:Clear alarm with the RESET key. Restart part program61703%[[Channel %1: ] Block %2: %]Label %4 not existing in the blank contourParameters...

  • Page 629

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1629Cycle alarms Remedy:- Check programming of machined part contourProgram Continuation:Clear alarm with the RESET key. Restart part program61707%[[Channel %1: ] Block %2: %]Error in the blank contour %4Parameters:%1 = Channel number%2 = Block ...

  • Page 630

    Cycle alarms Alarms630 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:- Calculation has been canceled by PI service; please try againProgram Continuation:Clear alarm with the RESET key. Restar...

  • Page 631

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1631Cycle alarms Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:Call the SIEMENS hotlineProgram Continuation:Clear alarm with the RESET key. Restart part program61730%[[Channel %1: ] Bloc...

  • Page 632

    Cycle alarms Alarms632 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:- Check programmed machining direction in connection with cutting edge position of the toolProgram Continuation:Clear alar...

  • Page 633

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1633Cycle alarms 61737%[[Channel %1: ] Block %2: %]Cutting depth smaller than minimum depth of cut of the toolParameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Interpreter stopNC Start disable in this channel.Interface s...

  • Page 634

    Cycle alarms Alarms634 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161741%[[Channel %1: ] Block %2: %]Axis in negative rangeParameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:...

  • Page 635

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1635Cycle alarms 61745%[[channel %1: ] block %2: %]Two-channel cutting in two guide channels (%4) activeParameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Interpreter stopNC Start disable in this channel.Interface signals...

  • Page 636

    Cycle alarms Alarms636 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:- Machining plane must be the same in guide and following channel.Program Continuation:Clear alarm with the RESET key. Restart part program61749%[[channel %1: ] block %2: %]Technology different in guide and following cha...

  • Page 637

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1637Cycle alarms Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:- Cutting edge position and cutting direction of the tools must be the same in guide and following channel.Program Continua...

  • Page 638

    Cycle alarms Alarms638 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Definitions:Multichannel machining with the programmed parameters would lead to a collision of the tools.Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:Adjust parameter ...

  • Page 639

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1639Cycle alarms 61801[Channel %1: ] Block %2: Wrong G code selectedParameters:%1 = Channel number%2 = Block number, labelDefinitions:In the program call CYCLE300<value> an impermissible numerical value was programmed for the entered CNC S...

  • Page 640

    Cycle alarms Alarms640 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161805[Channel %1: ] Block %2: Value programmed absolute and incrementalParameters:%1 = Channel number%2 = Block number, labelDefinitions:The programmed intermediate position is both absolutely as well as incrementally programme...

  • Page 641

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1641Cycle alarms 61809[Channel %1: ] Block %2: Drill position not permissibleParameters:%1 = Channel number%2 = Block number, labelDefinitions:--Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Re...

  • Page 642

    Cycle alarms Alarms642 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161813[Channel %1: ] Block %2: GUD value wrongly definedDefinitions:An impermissible numerical value wasentered in the cycles-setting data.Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm...

  • Page 643

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1643Cycle alarms 61817[Channel %1: ] Block %2: Axis coordinates within protection zoneParameters:%1 = Channel number%2 = Block number, labelDefinitions:--Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm d...

  • Page 644

    Cycle alarms Alarms644 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161852[channel %1: ] block %2: transformation not set up for this plane: %4Parameters:%1 = Channel number%2 = Block number, labelDefinitions:Transformation not set up for the plane used. Change plane.Reaction:Interpreter stopNC ...

  • Page 645

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1645Cycle alarms 61856[Channel %1: ] Block %2: Absolute input of the work offset values not enabledParameters:%1 = Channel number%2 = Block number, labelDefinitions:The absolute input of the work offset value has not been enabled.Reaction:Inter...

  • Page 646

    Cycle alarms Alarms646 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161860[Channel %1: ] Block %2: Turning only possible on a main spindleParameters:%1 = Channel number%2 = Block number, labelDefinitions:For turning, a main spindle was not selected for clamping.Reaction:Interpreter stopNC Start ...

  • Page 647

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1647Cycle alarms Remedy:Delete block.Program Continuation:Clear alarm with the RESET key. Restart part program61864[Channel %1: ] Block %2: The selection, tailstock yes/no must be identical in all channelsParameters:%1 = Channel number%2 = Block...

  • Page 648

    Cycle alarms Alarms648 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161900%[[Channel %1: ] Block %2: %]Name of program to be generated is missingParameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.A...

  • Page 649

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1649Cycle alarms 61904%[[Channel %1: ] Block %2: %]Label %4 not existing in the island contourParameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.A...

  • Page 650

    Cycle alarms Alarms650 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161908%[[Channel %1: ] Block %2: %]Blank contour missingParameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:-...

  • Page 651

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1651Cycle alarms 61912%[[Channel %1: ] Block %2: %]Error in spigot contour %4Parameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Reme...

  • Page 652

    Cycle alarms Alarms652 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161916%[[Channel %1: ] Block %2: %]Calculation has been canceledParameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display....

  • Page 653

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1653Cycle alarms Program Continuation:Clear alarm with the RESET key. Restart part program61920%[[Channel %1: ] block %2: %]System error contour milling %4Parameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Interpreter sto...

  • Page 654

    Cycle alarms Alarms654 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:- Modify contour programmingProgram Continuation:Clear alarm with the RESET key. Restart part program61933%[[Channel %1: ] Block %2: %]Too many contour elementsParameters:%1 = Channel number%2 = Block number, labelDefini...

  • Page 655

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1655Cycle alarms Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:- Modify contour programming, replace G0 by G1Program Continuation:Clear alarm with the RESET key. Restart part program6193...

  • Page 656

    Cycle alarms Alarms656 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161940%[[Channel %1: ] Block %2: %]Specified starting point programmed incorrectlyParameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Interpreter stopNC Start disable in this channel.Interface signals are ...

  • Page 657

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1657Cycle alarms 61944%[[Channel %1: ] Block %2: %]Ramp path too shortParameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm display.Remedy:- Ch...

  • Page 658

    Cycle alarms Alarms658 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA161948%[[Channel %1: ] Block %2: %]No material available for machiningParameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Interpreter stopNC Start disable in this channel.Interface signals are set.Alarm di...

  • Page 659

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1659Cycle alarms 61952%[[Channel %1: ] Block %2: %]Radius of res. material cutter too small in relation to ref. cutterParameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Interpreter stopNC Start disable in this channel.Int...

  • Page 660

    Cycle alarms Alarms660 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA162103[Channel %1: ] Block %2: No finishing allowance programmedParameters:%1 = Channel number%2 = Block number, labelDefinitions:No finishing allowance is programmed, although it is necessary for this machining.Reaction:Alarm d...

  • Page 661

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1661Cycle alarms 62108[Channel %1: ] Block %2: error in function Tool monitoring in cyclesParameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Alarm display.Remedy:Program Continuation:Clear alarm with the Delete key or NC ...

  • Page 662

    Cycle alarms Alarms662 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA162184[Channel %1: ] Block %2 : replace swivel head: %4Parameters:%1 = Channel number%2 = Block number, labelDefinitions:Reaction:Alarm display.Remedy:--Program Continuation:Clear alarm with the Delete key or NC START.62185[Chan...

  • Page 663

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1663Cycle alarms 62201[Channel %1: ] Block %2: Z offset does not influence the retraction planes.Parameters:%1 = Channel number%2 = Block number, labelDefinitions:The retraction planes refer to the workpiece. Therefore, programmable offsets do n...

  • Page 664

    3AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA166462305[Channel %1: ] Block %2: Dimension too smallParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Remedy:The difference between actual and setpoint value is smaller than lower tolerance limit (parameter _TLL)...

  • Page 665

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1665Cycle alarms 62311[Channel %1: ] Block %2: The maximum number of characters per line _PROTFORM[1] is adjusted.Parameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Max. number of characters per line _PROTFORM[1] ha...

  • Page 666

    Cycle alarms Alarms666 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA162316[Channel %1: ] Block %2: Overwrite TRAORIdata, yes -> NC start, no -> resetParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Remedy:62317[Channel %1: ] Block %2: Tolerance of the linear...

  • Page 667

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1667Cycle alarms 62500[Channel %1: ] Block %2: GWPS has been limitedParameters:%1 = Channel number%2 = Block number, label channel numberDefinitions:Remedy:Check limit value for GWPS and program a lower value in the NC program if necessaryProgra...

  • Page 668

    Cycle alarms Alarms668 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Error code = -7:The 5-axis transformation ( 24100 $MC_TRAFO_TYPE_x ) selected for the clearance control in MD $MC_CLC_AXNO is not configured in the channel.Error code = -8:More than one of the axes involved in the clearance con...

  • Page 669

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1669Cycle alarms Reaction:Interpreter stopAlarm display.Remedy:Modify part program: Switch off active G41/G42 before CLC(0) or do not switch of clearance control, but just "freeze" temporarily (CLC_GAIN=0.0) or cancel the position offs...

  • Page 670

    Cycle alarms Alarms670 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1"Closed-loop control in programmable direction" reports an error:Error ID:1:The clearance control direction has not been defined. Probably, [ 0,0,0 ] has beenprogrammed for the three simulated axes specifying the dire...

  • Page 671

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1671Cycle alarms Reaction:Alarm display.NC Stop on alarm.Remedy:The part program can be continued with NC start. The overlaid motion then returns to the control distance.Program Continuation:Clear alarm with the Delete key or NC START.75050[Chan...

  • Page 672

    Cycle alarms Alarms672 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA175061[Channel %1: ] MCSC: MD modification on active coupling axis %2Parameters:%1 = Channel number%2 = Axis nameDefinitions:Machine data MD 63000 CC_MASTER_AXIS has been changed when the coupling was active.Reaction:Alarm displ...

  • Page 673

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1673Cycle alarms Reaction:The NC switches to follow-up mode.Channel not ready.NC Start disable in this channel.Interface signals are set.Alarm display.NC Stop on alarm.Remedy:Change current tool, if required.Program Continuation:Clear alarm with...

  • Page 674

    Cycle alarms Alarms674 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1This is not permissible, because a change to the machine data directly affects the current axis position, which is transformed from the basic coordinate system into the machine coordinate system in real time. Changing the trans...

  • Page 675

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1675Cycle alarms Definitions:When preparing the block it is recognized that the software limit switch of an axis is exceeded.Reaction:NC Stop on alarm at block end.Correction block is reorganized.Local alarm reaction.NC Start disable in this cha...

  • Page 676

    Cycle alarms Alarms676 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA175274[Channel %1: ] RCTR: Excessive velocity near pole, error code %2 old value %3 new value %4Parameters:%1 = Channel number%2 = Error code%3 = Old value%4 = New valueDefinitions:Excessive velocity of the machine axes involved...

  • Page 677

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1677Cycle alarms 75501[Channel %1: ] HSLC: CC_FASTON_CONT velocity too highParameters:%1 = Channel numberDefinitions:The path-related switching signal output switched on by the part rogramm command CC_FASTON_CONT( PATH_DISTANCE_ON, PATH_DISTANCE...

  • Page 678

    Cycle alarms Alarms678 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA175601[Channel %1: ] RESU: block %2 invalid parameter in CC_PREPRE()Parameters:%1 = Channel number%2 = Block number, labelDefinitions:Only the values <arg> = -1 0 or 1 are valid parameters for programming CC_STOPRE( <...

  • Page 679

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1679Cycle alarms 75607[Channel %1: ] RESU: resynchronisation not possibleParameters:%1 = Channel numberDefinitions:The block search triggered by the compile cycle has been terminated with an error. It can have the following cause: The control is...

  • Page 680

    Cycle alarms Alarms680 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA175651[Channel %1: ] PROT: Incorrect configuration no. %2Parameters:%1 = Channel number%2 = Error codeDefinitions:Invalid configuration of the axis collision protection PROTSignificance of the displayed error numbers:1:The axes ...

  • Page 681

    4AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1681HMI alarms120200Image preparation suppressedDefinitions:The control is so heavily loaded by the processing of a subroutine, that it cannot keep all the display values up-to-date.Reaction:Alarm display.Remedy:The alarm disappears automatical...

  • Page 682

    HMI alarms Alarms682 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1120403Bus%1.Slave%2: %3: Check/acknowledge topology!Parameters:%1 = Bus number%2 = Slave address%3 = Name of the affected drive deviceDefinitions:The drive device with the bus number and slave address specified in the alarm has d...

  • Page 683

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1683HMI alarms 120406SINAMICS: Firmware update of DRIVE-CLiQ components completed.%nSwitch off/on drive system!Definitions:Firmware update of all DRIVE-CLiQ components completed.Reaction:Alarm display.Remedy:Switch off/on drive system including ...

  • Page 684

    HMI alarms Alarms684 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1149006The job fetched from the server does not contain any data.Definitions:-Remedy:-Program Continuation:Internal149007The server certificate has expired, or the date and time settings on the computer are incorrect.Definitions:-...

  • Page 685

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1685HMI alarms 149202The boot script could not start the service script.Definitions:-Remedy:-Program Continuation:Internal149203The service script could not start the data transfer service script.Definitions:-Remedy:-Program Continuation:Interna...

  • Page 686

    HMI alarms Alarms686 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1149310NC monitoring canceled on account of access error to the controller.Definitions:-Remedy:-Program Continuation:Internal149311NC monitoring failed while generating the data access object.Definitions:-Remedy:-Program Continuat...

  • Page 687

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1687HMI alarms 149322NC monitoring canceled because the timers could not be started.Definitions:-Remedy:-Program Continuation:Internal149500An HMI restart is required to complete the installation of the application.Definitions:-Remedy:-Program C...

  • Page 688

    HMI alarms Alarms688 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1150202Waiting for a connection to %1Parameters:%1 = Source URL of the component involvedDefinitions:The operator panel is connected to the NC and PLC by a communications bus.This alarm occurs if the MMC is started for the first t...

  • Page 689

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1689HMI alarms 150300%1 is activeDefinitions:The alarm signalizes that a defined energy state has been reached.Energy states can be configured via an HMI screen form in commissioning.The HMI screen forms can be accessed with the shortcut "C...

  • Page 690

    HMI alarms Alarms690 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1

  • Page 691

    5AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1691Drive and I/O alarms300402System error in drive link. Error codes %1, %2Parameters:%1 = Error code 1%2 = Error code 2Definitions:An internal software error or serious error condition has occurred, which could possibly be rectified by a hard...

  • Page 692

    Drive and I/O alarms Alarms692 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1- 18320 $MM_NUM_FILES_IN_FILESYSTEM- 18321 $MM_MAXNUM_SYSTEM_FILES_IN_FILESYSTEM- 18350 $MM_USER_FILE_MEM_MINIMUM- and, if necessary, of- 18270 $MM_NUM_SUBDIR_PER_DIR,- 18310 $MM_NUM_DIR_IN_FILESYSTEM,- Power On- Reload...

  • Page 693

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1693Drive and I/O alarms Definitions:An attempt to read a data block, e.g. a drive boot file, from the file system has failed. The data block or the file system is damaged.Reaction:Interface signals are set.Alarm display.Remedy:If the error occu...

  • Page 694

    Drive and I/O alarms Alarms694 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Reaction:Channel not ready.NC Start disable in this channel.Interface signals are set.Alarm display.Remedy:Remedy for 1-111. Check the control project, check MD11240 $MN_PROFIBUS_SDB_NUMBER, and reload it when using a u...

  • Page 695

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1695Drive and I/O alarms Reaction:Channel not ready.NC Start disable in this channel.Interface signals are set.Alarm display.Remedy:- For error cause 01:- Check the electrical and fault-related specifications for PROFIBUS/PROFINET, assess the ca...

  • Page 696

    Drive and I/O alarms Alarms696 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1- 102 = CF card: /oem/sinumerik/sdb/...- 103 = CF card: /user/sinumerik/sdb/...Reaction: PROFIBUS/PROFINET is inactive or working with the default SDB.Reaction:Channel not ready.NC Start disable in this channel.Interfac...

  • Page 697

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1697Drive and I/O alarms - 01 = SDB contains slave/device without diagnostics slot, slave/device address- 02 = SDB contains too many slot entries, identifier- 03 = SDB contains no equidistance data, no function- 04 = PNIO: SDB contains different...

  • Page 698

    Drive and I/O alarms Alarms698 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1If no inconsistencies can be found in the parameters, compare these machine data with the configuration in SDB (STEP 7 project). In particular, check that the lengths configured for the individual slots do not result in...

  • Page 699

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1699Drive and I/O alarms Reaction:Channel not ready.NC Start disable in this channel.Interface signals are set.Alarm display.Remedy:Enter correct base addresses in the machine data:- For length=1: Correct machine data MN_HW_ASSIGN_DIG_FASTIN.- F...

  • Page 700

    Drive and I/O alarms Alarms700 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1380075PROFIBUS/PROFINET: DP I/O failure bus %2 slave/device %1Parameters:%1 = Slave/device address%2 = Number of the affected busDefinitions:Failure of a PROFIBUS/PROFINET slot used by the NCK for digital or analog I/Os...

  • Page 701

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1701Drive and I/O alarms Definitions:Contents of fault memory of assigned drive.Reaction:Alarm display.Remedy:See drive documentation for fault codes/fault values.Program Continuation:Alarm display showing cause of alarm disappears. No further o...

  • Page 702

    Drive and I/O alarms Alarms702 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1

  • Page 703

    6AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA17036AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1703SINAMICS alarmsProduct: ALL_840, Version: 4502400, Language: engObjects: A_INF, A_INF_840, B_INF, B_INF_840, CU_I_840, CU_LINK, CU_NX_840, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU_S120_...

  • Page 704

    SINAMICS alarms Alarms704 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms704 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1201002<location>Internal software errorMessage value:%1Drive object:All objectsReaction:OFF2Acknowledge:IMMEDIATELYCause:An internal software err...

  • Page 705

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1705SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1705SINAMICS alarms xxxx = 0012 hex = 18 dec:Firmware version is too old and is not accepted by the component.xxxx = 0013 hex = 19 dec:Firmware version is not suitable for t...

  • Page 706

    SINAMICS alarms Alarms706 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms706 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:A DRIVE-CLiQ component must be powered up again (POWER ON) (e.g. due to a firmware update).Alarm value (r2124, interpret decimal):Component numbe...

  • Page 707

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1707SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1707SINAMICS alarms Remedy:- check the communication cable.- download the project again.- boot from previously saved files (power-down/power-up or p0976).- when loading into...

  • Page 708

    SINAMICS alarms Alarms708 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms708 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:- carry out a POWER ON (power off/on) for all components.- upgrade firmware to later version.- contact the Hotline.201016<location>Firmwar...

  • Page 709

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1709SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1709SINAMICS alarms 201020<location>Writing to RAM disk unsuccessfulMessage value:-Drive object:All objectsReaction:NONEAcknowledge:NONECause:A write access to the int...

  • Page 710

    SINAMICS alarms Alarms710 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms710 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:With the "OFF in REMOTE" mode active, no sign-of-life was received within 3 seconds.Remedy:- Check the data cable connection at the ser...

  • Page 711

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1711SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1711SINAMICS alarms 201035<location>ACX: Parameter back-up file corruptedMessage value:%1Drive object:All objectsReaction:NONEAcknowledge:NONECause:When the Control Un...

  • Page 712

    SINAMICS alarms Alarms712 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms712 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:An error has occurred when downloading PSxxxyyy.ACX or PTxxxyyy.ACX files from the non-volatile memory.Fault value (r0949, interpret hexadecimal)...

  • Page 713

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1713SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1713SINAMICS alarms 201040<location>Save parameter settings and carry out a POWER ONMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, CU_I_840, CU_LINK, ...

  • Page 714

    SINAMICS alarms Alarms714 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms714 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1201042<location>Parameter error during project downloadMessage value:Parameter: %1, Index: %2, fault cause: %3Drive object:All objectsReaction:In...

  • Page 715

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1715SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1715SINAMICS alarms 127: Write access only in the commissioning state, device (device: p0009 not equal to 0).129: Parameter may not be written in download.130: Transfer of t...

  • Page 716

    SINAMICS alarms Alarms716 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms716 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1201044<location>CU: Descriptive data errorMessage value:%1Drive object:All objectsReaction:OFF2Acknowledge:POWER ONCause:An error was detected wh...

  • Page 717

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1717SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1717SINAMICS alarms 201054<location>CU: System limit exceededMessage value:%1Drive object:All objectsReaction:OFF2Acknowledge:IMMEDIATELYCause:At least one system over...

  • Page 718

    SINAMICS alarms Alarms718 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms718 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Contact the Hotline.201057<location>CU: Internal error (different DRIVE-CLiQ type for the slave)Message value:%1Drive object:A_INF, A_INF_...

  • Page 719

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1719SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1719SINAMICS alarms 201060<location>CU: Internal error (parameter group not available)Message value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840...

  • Page 720

    SINAMICS alarms Alarms720 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms720 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:- carry out a POWER ON (power off/on) for all components.- upgrade firmware to later version.- contact the Hotline.201068<location>CU: Dat...

  • Page 721

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1721SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1721SINAMICS alarms 201099<location>Tolerance window of time synchronization exitedMessage value:-Drive object:All objectsReaction:NONEAcknowledge:NONECause:The time m...

  • Page 722

    SINAMICS alarms Alarms722 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms722 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1201107<location>CU: Data save in the non-volatile memory unsuccessfulMessage value:%1Drive object:All objectsReaction:NONEAcknowledge:IMMEDIATELY...

  • Page 723

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1723SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1723SINAMICS alarms 201120<location>Terminal initialization has failedMessage value:%1Drive object:All objectsReaction:OFF1 (OFF2)Acknowledge:IMMEDIATELY (POWER ON)Cau...

  • Page 724

    SINAMICS alarms Alarms724 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms724 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1201123<location>Power unit does not support digital inputs/outputsMessage value:-Drive object:SERVO, SERVO_840Reaction:OFF1 (OFF2)Acknowledge:IMM...

  • Page 725

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1725SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1725SINAMICS alarms 201200<location>CU: Time slice management internal software errorMessage value:%1Drive object:All objectsReaction:OFF2Acknowledge:IMMEDIATELY (POWE...

  • Page 726

    SINAMICS alarms Alarms726 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms726 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1201222<location>CU: Basic clock cycle too low (computing time for communication not available)Message value:%1Drive object:A_INF, A_INF_840, B_IN...

  • Page 727

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1727SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1727SINAMICS alarms 45: A chassis parallel unit was identified on the DRIVE-CLiQ line as a node. Further, the highest common denominator of the sampling times of all of the ...

  • Page 728

    SINAMICS alarms Alarms728 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms728 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1201251<location>CU: CU-EEPROM incorrect read-write dataMessage value:%1Drive object:All objectsReaction:NONEAcknowledge:NONECause:Error when read...

  • Page 729

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1729SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1729SINAMICS alarms Cause:A function requested by the Control Unit is not supported by a DRIVE-CLiQ component.Fault value (r0949, interpret decimal):1: The component does no...

  • Page 730

    SINAMICS alarms Alarms730 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms730 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1201306<location>Firmware of the DRIVE-CLiQ component being updatedMessage value:%1Drive object:All objectsReaction:NONEAcknowledge:NONECause:Firm...

  • Page 731

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1731SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1731SINAMICS alarms 201316<location>Drive object inactive and again ready for operationMessage value:-Drive object:All objectsReaction:NONEAcknowledge:NONECause:If, wh...

  • Page 732

    SINAMICS alarms Alarms732 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms732 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1201319<location>Inserted component not initializedMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, ENC, ENC_840, HUB, S_I...

  • Page 733

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1733SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1733SINAMICS alarms 201322<location>Topology: Drive object number present twice in configurationMessage value:%1Drive object:All objectsReaction:NONEAcknowledge:NONECa...

  • Page 734

    SINAMICS alarms Alarms734 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms734 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1201325<location>Topology: Component number not present in target topologyMessage value:Component number: %1Drive object:All objectsReaction:NONEA...

  • Page 735

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1735SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1735SINAMICS alarms aa = 07 hex = 7 dec:The actual topology contains an illegal combination of components.- bb = 01 hex = 1 dec: Active Line Module (ALM) and Basic Line Modu...

  • Page 736

    SINAMICS alarms Alarms736 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms736 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA13yy:Cyclic communication is fully utilized.4yy:The DRIVE-CLiQ cycle starts before the earliest end of the application. An additional dead time must be ...

  • Page 737

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1737SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1737SINAMICS alarms 201354<location>Topology: Actual topology indicates an illegal componentMessage value:Fault cause: %1, component number: %2Drive object:All objects...

  • Page 738

    SINAMICS alarms Alarms738 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms738 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1201356<location>Topology: There is a defective DRIVE-CLiQ componentMessage value:Fault cause: %1, Component number: %2, Connection number: %3Driv...

  • Page 739

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1739SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1739SINAMICS alarms 201360<location>Topology: Actual topology not permissibleMessage value:Fault cause: %1, preliminary component number: %2Drive object:All objectsRea...

  • Page 740

    SINAMICS alarms Alarms740 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms740 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:The detected actual topology contains SINUMERIK and SIMOTION components.The drive system is no longer booted. In this state, the drive control (c...

  • Page 741

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1741SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1741SINAMICS alarms Cause:When detecting the actual topology, a ring-type connection was detected.Fault value (r0949, interpret hexadecimal):ccbbaaaa hex:cc = connection num...

  • Page 742

    SINAMICS alarms Alarms742 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms742 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1aa = component number of the component shifted in the target topologyNote:The connection in the actual topology where the shifted component was detecte...

  • Page 743

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1743SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1743SINAMICS alarms aa = component number of the component shifted in the target topologyNote:The connection in the actual topology where the shifted component was detected ...

  • Page 744

    SINAMICS alarms Alarms744 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms744 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1aa = component number of the component shifted in the target topologyNote:The connection in the actual topology where the shifted component was detecte...

  • Page 745

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1745SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1745SINAMICS alarms aa = component number of the component shifted in the target topologyNote:The connection in the actual topology where the shifted component was detected ...

  • Page 746

    SINAMICS alarms Alarms746 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms746 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1aa = component number of the component shifted in the target topologyNote:The connection in the actual topology where the shifted component was detecte...

  • Page 747

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1747SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1747SINAMICS alarms Connection changed over for a multi-component slave (e.g. Double Motor Module), defective EEPROM data in the electronic rating plate, or only part of a m...

  • Page 748

    SINAMICS alarms Alarms748 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms748 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1ddccbbaa hex:cc = number of differencesbb = component classaa = component number of the componentNote:The component class is described in F01375.The dr...

  • Page 749

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1749SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1749SINAMICS alarms Cause:A topology comparison has found differences between the actual and target topology for several components. A component was connected to another con...

  • Page 750

    SINAMICS alarms Alarms750 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms750 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Read out the fault value and remove one of the specified connections.Then download the target topology again using the commissioning software.No...

  • Page 751

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1751SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1751SINAMICS alarms Cause:The topology comparison has detected a Sensor Module in the target topology that is not available in the actual topology.Alarm value (r2124, interp...

  • Page 752

    SINAMICS alarms Alarms752 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms752 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1201485<location>Topology: Comparison CX32 missing in the actual topologyMessage value:Component number: %1Drive object:All objectsReaction:NONEAc...

  • Page 753

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1753SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1753SINAMICS alarms Remedy:- delete the option board in the commissioning software project and download the new configuration to the drive unit.- re-configure the drive unit...

  • Page 754

    SINAMICS alarms Alarms754 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms754 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1201505<location>BICO: Interconnection cannot be establishedMessage value:Parameter: %1Drive object:All objectsReaction:NONEAcknowledge:IMMEDIATEL...

  • Page 755

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1755SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1755SINAMICS alarms Cause:The maximum number of BICO interconnections (signal sinks) when de-activating a drive object was exceeded.When de-activating a drive object, all BI...

  • Page 756

    SINAMICS alarms Alarms756 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms756 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1201513<location>BICO: Interconnection cross DO with different scalingsMessage value:Parameter: %1Drive object:All objectsReaction:NONEAcknowledge...

  • Page 757

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1757SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1757SINAMICS alarms 201590<location>Drive: Motor maintenance interval expiredMessage value:Fault cause: %1 binDrive object:A_INF, A_INF_840, B_INF, B_INF_840, ENC, ENC...

  • Page 758

    SINAMICS alarms Alarms758 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms758 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11: SI monitoring clock cycle (r9780, r9880).2: SI enable safety functions (p9601, p9801). Crosswise data comparison is only carried out for the support...

  • Page 759

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1759SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1759SINAMICS alarms Re fault value = 2000, 2001, 2002, 2004, 2005:- check the tolerance time SGE changeover and if required, increase the value (p9650/p9850, p9652/p9852).- ...

  • Page 760

    SINAMICS alarms Alarms760 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms760 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1201621<location>SI CU: Safe Stop 1 activeMessage value:-Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:NONEAcknowledge:NONECa...

  • Page 761

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1761SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1761SINAMICS alarms For fault value = 20:Fault in "brake open" state.- Short-circuit in brake winding.Re fault value = 30, 31:Fault in "close holding brake&qu...

  • Page 762

    SINAMICS alarms Alarms762 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms762 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1- replace the Control Unit.Note:CU: Control UnitMM: Motor ModuleSI: Safety Integrated201650<location>SI CU: Acceptance test requiredMessage value...

  • Page 763

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1763SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1763SINAMICS alarms Re fault value = 2003, 2004, 2005:- Carry out an acceptance test and generate an acceptance report.The procedure when carrying out an acceptance test as ...

  • Page 764

    SINAMICS alarms Alarms764 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms764 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1General:- carry out a POWER ON (power off/on) for all components.- upgrade the Motor Module software.- upgrade the Control Unit software.- upgrade the ...

  • Page 765

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1765SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1765SINAMICS alarms For motion monitoring functions that are not enabled (p9601.2 = p9801.2 = 0, p9501 = 0), the following applies:- Minimum setting for the monitoring clock...

  • Page 766

    SINAMICS alarms Alarms766 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms766 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Note:An actual value sensing clock cycle (p9511) that is set too low, can sporadically mean that safety messages C01711/C30711 are output with message ...

  • Page 767

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1767SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1767SINAMICS alarms The following applies for p9501.30 = 1 (F-DI via PROFIsafe is enabled):- PROFIsafe telegram 900 must be configured.For p9501.30 = 0 (F-DI not enabled via...

  • Page 768

    SINAMICS alarms Alarms768 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms768 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1201656<location>SI CU: Motor Module parameter errorMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:OFF2Acknowl...

  • Page 769

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1769SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1769SINAMICS alarms 201658<location>SI CU: PROFIsafe telegram number not equalMessage value:-Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:OFF2Ack...

  • Page 770

    SINAMICS alarms Alarms770 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms770 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA125: An attempt was made to parameterize a PROFIsafe telegram although this cannot be supported.26: At a digital input of the Control Unit, an attempt w...

  • Page 771

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1771SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1771SINAMICS alarms Cause:The write request for one or several Safety Integrated parameters on the Control Unit (CU) was rejected.Note:This fault does not result in a safety...

  • Page 772

    SINAMICS alarms Alarms772 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms772 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Note:CU: Control UnitESR: Extended Stop and RetractMM: Motor ModuleSBA: Safe Brake AdapterSBC: Safe Brake ControlSI: Safety IntegratedSS1: Safe Stop 1 ...

  • Page 773

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1773SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1773SINAMICS alarms As a consequence, inconsistent parameterization can occur in both monitoring channels, which in turn results in additional error messages.Especially for ...

  • Page 774

    SINAMICS alarms Alarms774 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms774 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Re fault value = 200000 hex, 400000 hex, 8000yy hex (yy any):- ensure that the Control Unit is connected to the Power Module.Re fault value = 800004 he...

  • Page 775

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1775SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1775SINAMICS alarms 7: Non-safety relevant component of the encoder coarse position for the linear DRIVE-CLiQ encoder not valid.8: Parameterized Safety comparison algorithm ...

  • Page 776

    SINAMICS alarms Alarms776 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms776 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:The existing Motor Module software does not support safe motion monitoring or is not compatible to the software on the Control Unit or there is a...

  • Page 777

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1777SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1777SINAMICS alarms Remedy:- Deselect the monitoring function involved (p9501, p9601).- set the matching PROFIsafe telegram (p9611).Note:SI: Safety IntegratedSLS: Safely-Lim...

  • Page 778

    SINAMICS alarms Alarms778 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms778 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1xxxx = 9544:For linear axes, the maximum value is limited to 1 mm.xxxx = 9547:p9547 is too low.xxxx = 9585:For Safety without encoder and synchronous m...

  • Page 779

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1779SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1779SINAMICS alarms yyyy = 5:To transfer the SLS limit values via PROFIsafe (p9501.24 = 1), also enable PROFIsafe (p9601.3 =1) and motion monitoring functions integrated in ...

  • Page 780

    SINAMICS alarms Alarms780 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms780 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SLS: Safely-Limited Speed / SG: Safely reduced speedSP: Safe PositionSee also: p9501 (SI Motion enable safety functions (Control Unit)), p9503 (SI Moti...

  • Page 781

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1781SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1781SINAMICS alarms Remedy:Correct the limit values for SLS and carry out a POWER ON.Note:SI: Safety IntegratedSLS: Safely-Limited Speed / SG: Safely reduced speedSee also: ...

  • Page 782

    SINAMICS alarms Alarms782 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms782 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:- It is not permissible to enable actual value synchronization for a 1-encoder system.- It is not permissible to simultaneously enable actual val...

  • Page 783

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1783SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1783SINAMICS alarms Cause:There is not sufficient memory space in the NVRAM on the drive to save parameters r9781 and r9782 (safety logbook).Note:This fault does not result ...

  • Page 784

    SINAMICS alarms Alarms784 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms784 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1201693<location>SI CU: Safety parameter settings changed, warm restart/POWER ON requiredMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_I...

  • Page 785

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1785SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1785SINAMICS alarms Then carry out an acceptance test (refer to the Safety Integrated Function Manual).For SINUMERIK, the following applies:HMI supports the replacement of c...

  • Page 786

    SINAMICS alarms Alarms786 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms786 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1201698<location>SI CU: Commissioning mode activeMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, SERVO, SERVO_84...

  • Page 787

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1787SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1787SINAMICS alarms - subsequent response to the message C01701 "SI Motion CU: STOP B initiated".- subsequent response to the message C01715 "SI Motion CU: Sa...

  • Page 788

    SINAMICS alarms Alarms788 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms788 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:Motion monitoring functions with encoder (p9506 = 0) or encoderless with set acceleration monitoring (p9506 = 3):SAM - safe acceleration monitori...

  • Page 789

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1789SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1789SINAMICS alarms This message can be acknowledged as follows:- motion monitoring functions integrated in the drive: Via Terminal Module 54F (TM54F) or PROFIsafe- motion m...

  • Page 790

    SINAMICS alarms Alarms790 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms790 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1201711<location>SI Motion CU: Defect in a monitoring channelMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:NO...

  • Page 791

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1791SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1791SINAMICS alarms 44 ... 57: GeneralPossible cause 1 (during commissioning or parameter modification)The tolerance value for the monitoring function is not the same on the...

  • Page 792

    SINAMICS alarms Alarms792 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms792 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1255: Setting, behavior during pulse suppression (p9509/p9309).256: Status image of monitoring functions SOS, SLS, SLP, test stop, SBR, SDI (result list...

  • Page 793

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1793SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1793SINAMICS alarms 6064: Destination address and PROFIsafe address are different (F_Dest_Add).6065: Destination address not valid (F_Dest_Add).6066: Source address not vali...

  • Page 794

    SINAMICS alarms Alarms794 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms794 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Re message value = 1005:- For safe motion monitoring functions without encoder: check the conditions for pulse enable.- For safe motion monitoring func...

  • Page 795

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1795SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1795SINAMICS alarms PROFIsafe slave and update.Re message value = 5065:- check the configuration and communication at the PROFIsafe slave (cons. No. / CRC).- check the setti...

  • Page 796

    SINAMICS alarms Alarms796 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms796 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1- Reduce the difference of the actual position from CU (r9713[0] and the second channel r9713[1] for a 2-encoder system.Re message value = 7001:- Incre...

  • Page 797

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1797SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1797SINAMICS alarms 46: SI digital inputs debounce time (p10017, p10117)47: Selection F-DI for PROFIsafe (p10050, p10150)48: Screen form of the F-DIs used (p10006, p10022 .....

  • Page 798

    SINAMICS alarms Alarms798 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms798 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1This message can be acknowledged as follows:- motion monitoring functions with SINUMERIK: Via the machine control panelNote:SI: Safety IntegratedSLP: S...

  • Page 799

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1799SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1799SINAMICS alarms 201745<location>SI Motion CU: Checking braking torque for the brake testMessage value:-Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACRe...

  • Page 800

    SINAMICS alarms Alarms800 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms800 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1201770<location>SI Motion CU: Discrepancy error of the failsafe inputs or outputsMessage value:%1Drive object:SERVO, SERVO_AC, VECTOR, VECTOR_ACR...

  • Page 801

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1801SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1801SINAMICS alarms Cause:The test stop for the fail-safe digital inputs (F-DI) and/or fail-safe digital outputs (F-DO) is presently being performed.Note:F-DI: Failsafe Digi...

  • Page 802

    SINAMICS alarms Alarms802 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms802 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1DI expected states in table format:Test stop state: Expectation Mode 1 / Mode 2 / Mode 3 / Mode 45: -/1/1/-7: -/0/0/-9: -/0/1/-11: -/0/1/-13: -/1/1/-Ex...

  • Page 803

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1803SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1803SINAMICS alarms 201796<location>SI CU: Wait for communicationMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:NONEAcknowledge:NON...

  • Page 804

    SINAMICS alarms Alarms804 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms804 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Not necessary.The message is withdrawn when the test stop is finished.Note:SI: Safety Integrated201799<location>SI Motion CU: Acceptance t...

  • Page 805

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1805SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1805SINAMICS alarms 201840<location>SMI: Component found without motor dataMessage value:Component number: %1Drive object:All objectsReaction:NONEAcknowledge:NONECause...

  • Page 806

    SINAMICS alarms Alarms806 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms806 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Check the bus configuration on the master and the slave sides.Re alarm value = 1, 2:- Check the list of the drive objects with process data exch...

  • Page 807

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1807SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1807SINAMICS alarms 201903<location>COMM INT: Receive configuration data invalidMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, CU_I_840, CU_LINK, CU_...

  • Page 808

    SINAMICS alarms Alarms808 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms808 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1201911<location>PB/PN clock cycle synchronous operation clock cycle failureMessage value:-Drive object:All objectsReaction:Infeed: OFF1Servo: OFF...

  • Page 809

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1809SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1809SINAMICS alarms Remedy:- wait until the control has re-booted.- restore data transfer to the control.201914<location>COMM INT: Monitoring time configuration expire...

  • Page 810

    SINAMICS alarms Alarms810 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms810 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1201921<location>PROFIBUS: Receive setpoints after ToMessage value:-Drive object:All objectsReaction:NONEAcknowledge:NONECause:Output data of PROF...

  • Page 811

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1811SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1811SINAMICS alarms Cause:There is no clock synchronization or clock synchronous sign of life and DSC is selected.Note:DSC: Dynamic Servo ControlSee also: p0922, p1190, p119...

  • Page 812

    SINAMICS alarms Alarms812 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms812 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:- check the master application and bus configuration.- check the consistency between the clock cycle input when configuring the slave and clock ...

  • Page 813

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1813SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1813SINAMICS alarms Cause:At this drive object, the connection to at least one Publisher for PROFIBUS peer-to-peer data transfer in cyclic operation has been aborted.Fault v...

  • Page 814

    SINAMICS alarms Alarms814 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms814 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Upgrade the firmware of the component specified in the fault value.Note:If required, also upgrade additional components in the DRIVE-CLiQ line.2...

  • Page 815

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1815SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1815SINAMICS alarms 201980<location>PN: Interruption cyclic connectionMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN,...

  • Page 816

    SINAMICS alarms Alarms816 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms816 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1201989<location>PROFINET: Internal cyclic data transfer errorMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP...

  • Page 817

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1817SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1817SINAMICS alarms Remedy:Use the existing drive object with the corresponding number.Note:The alarm is reset as follows:- remove the cause of this alarm.- restart the func...

  • Page 818

    SINAMICS alarms Alarms818 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms818 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1202009<location>Function generator: Illegal modeMessage value:%1Drive object:All objectsReaction:NONEAcknowledge:NONECause:The set operating mode...

  • Page 819

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1819SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1819SINAMICS alarms Cause:The master control and/or enable signals are missing to connect to the specified drive.See also: p4815 (Function generator drive number)Remedy:Fetc...

  • Page 820

    SINAMICS alarms Alarms820 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms820 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Check and adapt the value for the period.Note:The alarm is reset as follows:- remove the cause of this alarm.- restart the function generator.Se...

  • Page 821

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1821SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1821SINAMICS alarms 202041<location>Function generator: Illegal value for bandwidthMessage value:-Drive object:All objectsReaction:NONEAcknowledge:NONECause:The bandwi...

  • Page 822

    SINAMICS alarms Alarms822 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms822 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1202055<location>Trace: Recording time too shortMessage value:-Drive object:All objectsReaction:NONEAcknowledge:NONECause:The trace duration is to...

  • Page 823

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1823SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1823SINAMICS alarms 202059<location>Trace: Time slice clock cycle for 2 x 8 recording channels not validMessage value:-Drive object:All objectsReaction:NONEAcknowledge...

  • Page 824

    SINAMICS alarms Alarms824 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms824 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1202063<location>Trace: Invalid data typeMessage value:%1Drive object:All objectsReaction:NONEAcknowledge:NONECause:The specified data type to sel...

  • Page 825

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1825SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1825SINAMICS alarms 202099<location>Trace: Insufficient Control Unit memoryMessage value:-Drive object:All objectsReaction:NONEAcknowledge:NONECause:The memory space s...

  • Page 826

    SINAMICS alarms Alarms826 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms826 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1202151<location>OA: Internal software errorMessage value:%1Drive object:All objectsReaction:Infeed: OFF2 (NONE, OFF1)Servo: OFF2 (NONE, OFF1, OFF...

  • Page 827

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1827SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1827SINAMICS alarms Remedy:Perform the remedy according to the results of the troubleshooting.If necessary, start the action again.203001<location>NVRAM checksum incor...

  • Page 828

    SINAMICS alarms Alarms828 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms828 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:The wire-break monitoring for an analog input has responded.The input current of the analog input has exceeded the threshold value parameterized ...

  • Page 829

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1829SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1829SINAMICS alarms 203510<location>TM: Calibration data not plausibleMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, CU_I_840, CU_LINK, CU_NX_840, EN...

  • Page 830

    SINAMICS alarms Alarms830 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms830 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1203590<location>TM: Module not readyMessage value:%1Drive object:All objectsReaction:Infeed: OFF2 (NONE)Servo: NONE (ENCODER, IASC/DCBRAKE, OFF1,...

  • Page 831

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1831SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1831SINAMICS alarms 205001<location>Power unit: Overtemperature depletion layer chipMessage value:-Drive object:VECTOR, VECTOR_ACReaction:NONEAcknowledge:NONECause:Ala...

  • Page 832

    SINAMICS alarms Alarms832 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms832 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1205004<location>Power unit: Rectifier overtemperatureMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, SERVO, SER...

  • Page 833

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1833SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1833SINAMICS alarms Cause:The temperature difference between the chip and heat sink has exceeded the permissible limit value (r0293) (chassis power units only).Depending on ...

  • Page 834

    SINAMICS alarms Alarms834 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms834 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1205053<location>Parallel circuit: Inadmissible DC link voltage dissymmetryMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, ...

  • Page 835

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1835SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1835SINAMICS alarms Cause:The code numbers of the power units do not match.Fault value (r0949, interpret decimal):Parameter in which the first different power unit code numb...

  • Page 836

    SINAMICS alarms Alarms836 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms836 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1205059<location>Parallel circuit: VSM firmware versions differMessage value:Parameter: %1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, ...

  • Page 837

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1837SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1837SINAMICS alarms 206000<location>Infeed: Precharging monitoring time expiredMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840Reaction...

  • Page 838

    SINAMICS alarms Alarms838 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms838 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1206050<location>Infeed: Smart Mode not supportedMessage value:-Drive object:A_INF, A_INF_840, S_INF, S_INF_840Reaction:OFF2Acknowledge:IMMEDIATEL...

  • Page 839

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1839SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1839SINAMICS alarms Cause:The filtered (steady-state) value of line supply voltage is lower than the alarm threshold (p0282).Alarm condition: Vrms < p0282 * p0210Alarm va...

  • Page 840

    SINAMICS alarms Alarms840 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms840 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Bit 10: Smart Mode: Line currents not symmetricalBit 11: Smart Mode: Line supply voltage detection faultBit 14: Recharging current faultRemedy:Generall...

  • Page 841

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1841SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1841SINAMICS alarms 206211<location>Infeed: Summation current impermissibly highMessage value:%1Drive object:A_INF, A_INF_840, S_INF, S_INF_840Reaction:OFF2Acknowledge...

  • Page 842

    SINAMICS alarms Alarms842 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms842 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1206250<location>Infeed: Defective capacitor(s) in at least one phase of line filterMessage value:%1Drive object:A_INF, A_INF_840, S_INF, S_INF_84...

  • Page 843

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1843SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1843SINAMICS alarms Cause:After the temperature monitoring responded, the temperature in the line filter was permanently exceeded.Note:The temperature monitoring is only ava...

  • Page 844

    SINAMICS alarms Alarms844 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms844 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:The filtered (steady-state) value of the rms line supply voltage Vrms is higher than the alarm threshold (p0281).Alarm condition: Vrms > p0281...

  • Page 845

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1845SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1845SINAMICS alarms The following applies for the extended tolerance range: 75 % * p0210 < Vrms < 120 % * p0210Alarm value (r2124, floating point):Line supply voltage ...

  • Page 846

    SINAMICS alarms Alarms846 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms846 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Alarm value (r2124, floating point):Actual line frequency determined.See also: p0284 (Line supply frequency exceeded, alarm threshold)Remedy:- check th...

  • Page 847

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1847SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1847SINAMICS alarms Cause:A transformer data identification type or a transformer test operation has been selected or is active.Alarm value (r2124, interpret decimal):11: Id...

  • Page 848

    SINAMICS alarms Alarms848 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms848 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1206503<location>Infeed: Line black start unsuccessfulMessage value:%1Drive object:A_INF, A_INF_840, S_INFReaction:OFF1 (NONE, OFF2)Acknowledge:IM...

  • Page 849

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1849SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1849SINAMICS alarms Remedy:- check the DC link for a ground fault. A ground fault can destroy parts and components!- Check the monitoring time setting and if required increa...

  • Page 850

    SINAMICS alarms Alarms850 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms850 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1206849<location>Infeed: Short-circuit operation activeMessage value:-Drive object:A_INF, A_INF_840Reaction:NONEAcknowledge:NONECause:The current ...

  • Page 851

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1851SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1851SINAMICS alarms 1: Current threshold value exceeded (p3678[1]).2: Voltage threshold value of the phase voltage monitoring fallen below (p3678[0]).See also: p3678 (Filter...

  • Page 852

    SINAMICS alarms Alarms852 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms852 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1206901<location>Braking Module: Pre-alarm I2t shutdownMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840Reaction:N...

  • Page 853

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1853SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1853SINAMICS alarms Remedy:Reduce the number of braking operations.206907<location>Braking Module internal overtemperatureMessage value:-Drive object:B_INF, B_INF_840R...

  • Page 854

    SINAMICS alarms Alarms854 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms854 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1206922<location>Braking resistor phase failureMessage value:%1Drive object:VECTOR, VECTOR_ACReaction:NONEAcknowledge:IMMEDIATELYCause:A phase fai...

  • Page 855

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1855SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1855SINAMICS alarms - check the parameters of the motor temperature model (p5350 and following).- check the encoder (p0404).See also: p0604, p0605, p0606, p0612, p0617, p061...

  • Page 856

    SINAMICS alarms Alarms856 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms856 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207012<location>Drive: Motor temperature model 1/3 overtemperatureMessage value:%1Drive object:VECTOR, VECTOR_ACReaction:NONEAcknowledge:NONECaus...

  • Page 857

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1857SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1857SINAMICS alarms 207015<location>Drive: Motor temperature sensor alarmMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:NONEAcknowl...

  • Page 858

    SINAMICS alarms Alarms858 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms858 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207018<location>Additional temperature fault threshold exceededMessage value:%1Drive object:SERVO, SERVO_840, SERVO_ACReaction:OFF1 (ENCODER, NON...

  • Page 859

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1859SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1859SINAMICS alarms 27: A value was entered as string in the tag value that is not "DEFAULT".31: Entered drive object type unknown.32: A device was not able to be ...

  • Page 860

    SINAMICS alarms Alarms860 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms860 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:Open-loop/closed-loop control parameters have had to be changed for the following reasons:1. As a result of other parameters, they have exceeded ...

  • Page 861

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1861SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1861SINAMICS alarms 207088<location>Units changeover: Parameter limit violation due to units changeoverMessage value:Parameter: %1Drive object:A_INF, A_INF_840, B_INF,...

  • Page 862

    SINAMICS alarms Alarms862 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms862 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:When resetting drive parameter (p0976) sampling times cannot be reset using p0111, p0112, p0115.Fault value (r0949, interpret decimal):Parameter ...

  • Page 863

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1863SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1863SINAMICS alarms 207220<location>Drive: Master control by PLC missingMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, ENC, ENC_840, S_INF, S_INF_840,...

  • Page 864

    SINAMICS alarms Alarms864 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms864 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:- check the transfer of the feedback signals.- check the switch.207312<location>Bypass LSS:Message value:Fault cause: %1 binDrive object:V...

  • Page 865

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1865SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1865SINAMICS alarms Cause:- The specified number of restart attempts (p1211) has been completely used up because within the monitoring time (p1213) the faults were not able ...

  • Page 866

    SINAMICS alarms Alarms866 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms866 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207330<location>Flying restart: Measured search current too lowMessage value:-Drive object:VECTOR, VECTOR_ACReaction:OFF2 (NONE, OFF1)Acknowledge...

  • Page 867

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1867SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1867SINAMICS alarms 207351<location>Drive: Measuring probe parameterized to a digital outputMessage value:%1Drive object:SERVO, SERVO_840Reaction:NONEAcknowledge:NONEC...

  • Page 868

    SINAMICS alarms Alarms868 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms868 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207401<location>Drive: DC link voltage maximum controller de-activatedMessage value:-Drive object:VECTOR, VECTOR_ACReaction:NONEAcknowledge:NONEC...

  • Page 869

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1869SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1869SINAMICS alarms Remedy:- check the line supply voltage.- check the infeed.- reduce the lower DC link threshold (p1248).- switch out (disable) the DC link voltage monitor...

  • Page 870

    SINAMICS alarms Alarms870 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms870 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:During kinetic buffering the speed fell below minimum speed (p1257 or p1297 for vector drives with U/f control) and the line supply did not retur...

  • Page 871

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1871SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1871SINAMICS alarms Cause:The condition "I_act = 0 and Uq_set_1 longer than 16 ms at its limit" is present and can be caused by the following:- motor not connected...

  • Page 872

    SINAMICS alarms Alarms872 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms872 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:An incorrect commutation angle was detected that can result in a positive coupling in the speed controller.Possible causes:- The phase sequence o...

  • Page 873

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1873SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1873SINAMICS alarms 207414<location>Drive: Encoder serial number changedMessage value:-Drive object:SERVO, SERVO_840, SERVO_ACReaction:ENCODER (NONE, OFF2)Acknowledge:...

  • Page 874

    SINAMICS alarms Alarms874 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms874 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207416<location>Drive: Flux controller configurationMessage value:Parameter: %1, Index: %2, fault cause: %3Drive object:VECTOR, VECTOR_ACReaction...

  • Page 875

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1875SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1875SINAMICS alarms Remedy:For fault value = 0:Once the pulse technique has been de-selected automatically (p1750.5=0), there are two possible options:- acknowledge the faul...

  • Page 876

    SINAMICS alarms Alarms876 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms876 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207422<location>Drive: Reference model natural frequency > Shannon frequencyMessage value:-Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VE...

  • Page 877

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1877SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1877SINAMICS alarms Remedy:Re bit 0:Only use the APC function in operation with an encoder.Re bit 1, 2:Check the load measuring system.207425<location>Drive: APC monit...

  • Page 878

    SINAMICS alarms Alarms878 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms878 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207429<location>Drive: DSC without encoder not possibleMessage value:-Drive object:SERVO, SERVO_840, SERVO_ACReaction:OFF2Acknowledge:IMMEDIATELY...

  • Page 879

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1879SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1879SINAMICS alarms Rotary induction motor connected to the high-frequency converter:p1082 [rpm] <= maximum (2.11383E5 / (r0313 * root((r0377 [mH] + r0382 [mH]) * p0234 [...

  • Page 880

    SINAMICS alarms Alarms880 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms880 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207435<location>Drive: Setting the ramp-function generator for sensorless vector controlMessage value:Parameter: %1Drive object:VECTOR, VECTOR_AC...

  • Page 881

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1881SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1881SINAMICS alarms Cause:The calculation of the jerk time Tr = max(p2572, p2573) / p2574 resulted in an excessively high value so that the jerk time is internally limited t...

  • Page 882

    SINAMICS alarms Alarms882 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms882 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207443<location>LR: Reference point coordinate not in the permissible rangeMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTO...

  • Page 883

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1883SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1883SINAMICS alarms 207448<location>Load gear: Position tracking, linear axis has exceeded the maximum rangeMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_...

  • Page 884

    SINAMICS alarms Alarms884 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms884 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207450<location>LR: Standstill monitoring has respondedMessage value:-Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:OFF1 (OF...

  • Page 885

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1885SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1885SINAMICS alarms 207453<location>LR: Position actual value preprocessing errorMessage value:-Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:OFF1...

  • Page 886

    SINAMICS alarms Alarms886 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms886 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207457<location>EPOS: Combination of input signals illegalMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:NONE...

  • Page 887

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1887SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1887SINAMICS alarms Cause:During the search for reference, when the axis reached the zero mark it also reached the end of the traversing range without detecting an edge at t...

  • Page 888

    SINAMICS alarms Alarms888 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms888 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:The traversing block does not contain valid information.Alarm value (r2124, interpret decimal):Number of the traversing block with invalid inform...

  • Page 889

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1889SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1889SINAMICS alarms Remedy:- correct the traversing block.- add the missing traversing block.207469<location>EPOS: Traversing block < target position < software ...

  • Page 890

    SINAMICS alarms Alarms890 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms890 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:In the traversing block the positioning mode ABS_POS or ABS_NEG were parameterized with the modulo correction not activated.Alarm value (r2124, i...

  • Page 891

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1891SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1891SINAMICS alarms 207477<location>EPOS: Target position < software limit switch minusMessage value:-Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReac...

  • Page 892

    SINAMICS alarms Alarms892 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms892 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207481<location>EPOS: Axis position < software limit switch minusMessage value:-Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReac...

  • Page 893

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1893SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1893SINAMICS alarms 207485<location>EPOS: Fixed stop not reachedMessage value:-Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:OFF1 (OFF2, OFF3)Ackn...

  • Page 894

    SINAMICS alarms Alarms894 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms894 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207489<location>EPOS: Reference point correction outside the windowMessage value:-Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReact...

  • Page 895

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1895SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1895SINAMICS alarms 207493<location>LR: Overflow of the value range for position actual valueMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC...

  • Page 896

    SINAMICS alarms Alarms896 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms896 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207495<location>LR: Reference function interruptedMessage value:-Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:NONEAcknowled...

  • Page 897

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1897SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1897SINAMICS alarms Remedy:De-activate the measuring probe evaluation (BI: p2509 = 0 signal).Re alarm value = 6:Set the input terminal for the measuring probe (p0488, p0489 ...

  • Page 898

    SINAMICS alarms Alarms898 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms898 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207502<location>Drive: Encoder Data Set EDS not configuredMessage value:Drive data set: %1Drive object:All objectsReaction:OFF2Acknowledge:IMMEDI...

  • Page 899

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1899SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1899SINAMICS alarms Cause:In the U/f/SLVC mode, an attempt was made to execute a traversing block with the "fixed stop" task. This is not possible.Alarm value (r21...

  • Page 900

    SINAMICS alarms Alarms900 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms900 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207511<location>Drive: Encoder used a multiple number of timesMessage value:%1Drive object:All objectsReaction:NONEAcknowledge:IMMEDIATELYCause:E...

  • Page 901

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1901SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1901SINAMICS alarms 16/16: p0186[0] = 0, p0186[1] = 1, p0186[2] = 2 ... p0186[15] = 1532/32: p0186[0] = 0, p0186[1] = 1, p0186[2] = 2 ... p0186[31] = 312/1: p0186[0, 1] = 04...

  • Page 902

    SINAMICS alarms Alarms902 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms902 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207517<location>Drive: Encoder data set changeover incorrectly parameterizedMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, ENC,...

  • Page 903

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1903SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1903SINAMICS alarms 207520<location>Drive: Motor cannot be changed overMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:NONEAcknowled...

  • Page 904

    SINAMICS alarms Alarms904 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms904 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207541<location>Drive: Data set changeover not possibleMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, ENC, ENC_840, S_INF, S_INF...

  • Page 905

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1905SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1905SINAMICS alarms 207552<location>Drive encoder: Encoder configuration not supportedMessage value:Fault cause: %1, component number: %2, encoder data set: %3Drive ob...

  • Page 906

    SINAMICS alarms Alarms906 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms906 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207555<location>Drive encoder: Configuration position trackingMessage value:Component number: %1, encoder data set: %2, drive data set: %3, fault...

  • Page 907

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1907SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1907SINAMICS alarms 207557<location>Encoder 1: Reference point coordinate not in the permissible rangeMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, ...

  • Page 908

    SINAMICS alarms Alarms908 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms908 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207561<location>Drive encoder: Number of multiturn pulses is not to the power of twoMessage value:Encoder data set: %1Drive object:A_INF, A_INF_8...

  • Page 909

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1909SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1909SINAMICS alarms Cause:An incorrect configuration was identified for the "Absolute position for incremental encoder" function.Fault value (r0949, interpret deci...

  • Page 910

    SINAMICS alarms Alarms910 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms910 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207569<location>Encoder could not be identifiedMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, ENC, ENC_840, S_INF, S_INF_840, SE...

  • Page 911

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1911SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1911SINAMICS alarms 207577<location>Encoder 1: Measuring probe evaluation not possibleMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReactio...

  • Page 912

    SINAMICS alarms Alarms912 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms912 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:When evaluating the measuring probe, an error occurred.Alarm value (r2124, interpret decimal):6: The input terminal for the measuring probe is no...

  • Page 913

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1913SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1913SINAMICS alarms 207583<location>Encoder 3: Position actual value preprocessing errorMessage value:-Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReacti...

  • Page 914

    SINAMICS alarms Alarms914 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms914 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207587<location>Encoder 1: Position actual value preprocessing does not have a valid encoderMessage value:-Drive object:SERVO, SERVO_840, SERVO_A...

  • Page 915

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1915SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1915SINAMICS alarms Remedy:To changeover the drive data set, initially, exit the "operation" mode.207591<location>Encoder 2: Drive Data Set changeover in ope...

  • Page 916

    SINAMICS alarms Alarms916 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms916 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:The value range (-2147483648 ... 2147483647) for the position actual value representation was exceeded.When the overflow occurs, the "refere...

  • Page 917

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1917SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1917SINAMICS alarms 207597<location>Encoder 2: Reference function interruptedMessage value:-Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:NONEAckn...

  • Page 918

    SINAMICS alarms Alarms918 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms918 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA15. Direct encoder without position tracking:p2506 * p0433 / p0432p2506 * p0433 * p0421 / p0432 for multiturn encoders6. Direct encoder with position tr...

  • Page 919

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1919SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1919SINAMICS alarms 5. Direct encoder without position tracking:p2506 * p0433 / p0432p2506 * p0433 * p0421 / p0432 for multiturn encoders6. Direct encoder with position trac...

  • Page 920

    SINAMICS alarms Alarms920 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms920 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207801<location>Drive: Motor overcurrentMessage value:-Drive object:VECTOR, VECTOR_ACReaction:OFF2 (NONE, OFF1, OFF3)Acknowledge:IMMEDIATELYCause...

  • Page 921

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1921SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1921SINAMICS alarms 207805<location>Drive: Power unit overload I2tMessage value:-Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:NONEAcknowledge:NON...

  • Page 922

    SINAMICS alarms Alarms922 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms922 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207810<location>Drive: Power unit EEPROM without rated dataMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, SERV...

  • Page 923

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1923SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1923SINAMICS alarms Remedy:Connect the original power unit and power up the Control Unit again (POWER ON) or set p0201 to r0200 and exit commissioning with p0010 = 0.For inf...

  • Page 924

    SINAMICS alarms Alarms924 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms924 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Re alarm value = 1:- In p0600 set an encoder with temperature sensor.Re alarm value = 2:- interconnect p0603 with the temperature signal.Re alar...

  • Page 925

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1925SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1925SINAMICS alarms 207841<location>Drive: Infeed operation withdrawnMessage value:-Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:OFF2 (NONE, OFF1...

  • Page 926

    SINAMICS alarms Alarms926 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms926 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207860<location>External fault 1Message value:-Drive object:All objectsReaction:Infeed: OFF2 (NONE, OFF1)Servo: OFF2 (IASC/DCBRAKE, NONE, OFF1, O...

  • Page 927

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1927SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1927SINAMICS alarms 207899<location>Drive: Stall monitoring not possibleMessage value:Parameter: %1Drive object:VECTOR, VECTOR_ACReaction:NONEAcknowledge:NONECause:Sta...

  • Page 928

    SINAMICS alarms Alarms928 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms928 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:Motor has been operating at the torque limit longer than the time specified in p2177 and below the speed threshold in p2175.This signal can also ...

  • Page 929

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1929SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1929SINAMICS alarms 207902<location>Drive: Motor stalledMessage value:%1Drive object:SERVO, SERVO_840, SERVO_ACReaction:OFF2 (IASC/DCBRAKE, NONE, OFF1, OFF3, STOP1, ST...

  • Page 930

    SINAMICS alarms Alarms930 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms930 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:It should always be carefully ensured that the motor data identification (p1910) as well as the rotating measurement (p1960) were carried out (a...

  • Page 931

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1931SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1931SINAMICS alarms Remedy:- increase p2163 and/or p2166.- increase the torque/current/power limits.- for closed-loop torque control: The speed setpoint should track the spe...

  • Page 932

    SINAMICS alarms Alarms932 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms932 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1zzzz = 00C9 hex = 201 dec:Internal voltage protection: The maximum output current of the Motor Module (r0209) is less than 1.8 x motor short-circuit cu...

  • Page 933

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1933SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1933SINAMICS alarms - if the Motor Module does support the autonomous, internal voltage protection (r0192.10 = 1), in order to ensure safe, reliable functioning when the lin...

  • Page 934

    SINAMICS alarms Alarms934 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms934 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207910<location>Drive: Motor overtemperatureMessage value:%1Drive object:VECTOR, VECTOR_ACReaction:NONEAcknowledge:NONECause:KTY or no sensor:The...

  • Page 935

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1935SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1935SINAMICS alarms 207918<location>Three-phase setpoint generator operation selected/activeMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_IN...

  • Page 936

    SINAMICS alarms Alarms936 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms936 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207923<location>Drive: Torque/speed too lowMessage value:-Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:OFF1 (NONE, OFF2, OF...

  • Page 937

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1937SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1937SINAMICS alarms 207927<location>DC braking activeMessage value:-Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:NONEAcknowledge:NONECause:The mo...

  • Page 938

    SINAMICS alarms Alarms938 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms938 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA180: When using the Safe Brake Adaptor (SBA), a fault has occurred in the brake control of the Control Unit.90: Brake released for service purposes (X4)...

  • Page 939

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1939SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1939SINAMICS alarms Cause:A connected motor holding brake has been detected with an S120 Combi. However, this brake has not been assigned to just one Combi feed drive and, t...

  • Page 940

    SINAMICS alarms Alarms940 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms940 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1For fault value = 14:Check whether the power unit supports the brake control for a parallel connection (r9771.14).Check whether there is a DRIVE-CLiQ c...

  • Page 941

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1941SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1941SINAMICS alarms 207942<location>Sync-line-drive: Setpoint frequency is completely different than the target frequencyMessage value:-Drive object:VECTOR, VECTOR_ACR...

  • Page 942

    SINAMICS alarms Alarms942 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms942 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Fault value (r0949, interpret decimal):Parameter number involved.The following motor parameters can be incorrect for fault value 307:p0304, p0305, p030...

  • Page 943

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1943SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1943SINAMICS alarms 1539:The friction torque is less than the minimum from the lower effective torque limit (p1539) and zero. This is the reason that the output of the frict...

  • Page 944

    SINAMICS alarms Alarms944 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms944 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11910: Motor data identification activated.1960: Speed controller optimization activated.3820 ... 3829: Speed (p382x) cannot be approached.3840: Frictio...

  • Page 945

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1945SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1945SINAMICS alarms Cause:The speed actual value was inverted and the associated angular commutation offset is not equal to zero and is therefore possibly incorrect.Remedy:A...

  • Page 946

    SINAMICS alarms Alarms946 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms946 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA111: Stage 2: The ratio between the measured current and zero current is too low.12: Stage 1: The maximum current was exceeded.13: Stage 2: The maximum ...

  • Page 947

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1947SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1947SINAMICS alarms Cause:A fault has occurred during the automatic encoder adjustment.Fault value (r0949, interpret decimal):1: Current controller limited2: Motor shaft loc...

  • Page 948

    SINAMICS alarms Alarms948 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms948 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:The automatic determination of the angular commutation offset (encoder adjustment) is activated (p1990 = 1).The automatic determination is carrie...

  • Page 949

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1949SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1949SINAMICS alarms 207980<location>Drive: Rotating measurement activatedMessage value:-Drive object:SERVO, SERVO_840, SERVO_ACReaction:NONEAcknowledge:NONECause:The r...

  • Page 950

    SINAMICS alarms Alarms950 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms950 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:A fault has occurred during the encoder test.Fault value (r0949, interpret decimal):1: The speed did not reach a steady-state condition.2: The sp...

  • Page 951

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1951SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1951SINAMICS alarms Remedy:For fault value = 1:- the total drive moment of inertia is far higher than that of the motor (p0341, p0342).De-select rotating measurement (p1960)...

  • Page 952

    SINAMICS alarms Alarms952 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms952 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Re fault value = 4, 7:- adapt the speed setpoint (p1965) or maximum limit (p1082, p1083 and p1086).For fault value = 8:- the total drive moment of iner...

  • Page 953

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1953SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1953SINAMICS alarms Remedy:For fault value = 1:Enable the direction (p1110 or p1111).207987<location>Drive: Rotating measurement, no encoder availableMessage value:%1D...

  • Page 954

    SINAMICS alarms Alarms954 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms954 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1For fault value = 7:- increase p1082 if this is technically permissible.- reduce p1965 so that the q leakage inductance is recorded at lower speeds.For...

  • Page 955

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1955SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1955SINAMICS alarms 192: Speed setpoint not reached.193: Inadmissible motion of the motor when identifying the voltage emulation error.194: Supplementary torque (r1515) not ...

  • Page 956

    SINAMICS alarms Alarms956 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms956 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1For fault value = 160:- extend accelerating time when determining kT, moment of inertia and reluctance torque, e.g. by increasing max. speed (p1082), i...

  • Page 957

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1957SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1957SINAMICS alarms 7: Identified total leakage reactance lies outside the expected range 4 ... 100 % of Zn.8: Identified stator leakage reactance lies outside the expected ...

  • Page 958

    SINAMICS alarms Alarms958 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms958 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1207991<location>Drive: Motor data identification activatedMessage value:-Drive object:VECTOR, VECTOR_ACReaction:NONEAcknowledge:NONECause:The mot...

  • Page 959

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1959SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1959SINAMICS alarms 207995<location>Drive: Pole position identification not successfulMessage value:%1Drive object:SERVO, SERVO_840, SERVO_ACReaction:OFF2Acknowledge:I...

  • Page 960

    SINAMICS alarms Alarms960 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms960 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1For fault value = 8:- reduce the currents for the pole position identification routine (p0329, p0325, p1993).- the power unit cannot provide the necess...

  • Page 961

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1961SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1961SINAMICS alarms For fault value = 208:- set the measuring current (p3096).For fault value = 209:- check parameter setting p3095.- check the brake or brake control.For fa...

  • Page 962

    SINAMICS alarms Alarms962 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms962 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:Closed-loop control is enabled on a SERVO drive object type. To select motor data identification, pulses must be suppressed for all SERVO drive o...

  • Page 963

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1963SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1963SINAMICS alarms 208501<location>COMM BOARD: Setpoint timeoutMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S12...

  • Page 964

    SINAMICS alarms Alarms964 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms964 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1208510<location>COMM BOARD: Send configuration data invalidMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, ...

  • Page 965

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1965SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1965SINAMICS alarms 208520<location>COMM BOARD: Non-cyclic channel errorMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_P...

  • Page 966

    SINAMICS alarms Alarms966 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms966 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:The assignment of the hardware to the PZD interface has been incorrectly parameterized.Alarm value (r2124, interpret decimal):1: Only one of the ...

  • Page 967

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1967SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1967SINAMICS alarms 208562<location>PROFINET: Syntax error in configuration fileMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU...

  • Page 968

    SINAMICS alarms Alarms968 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms968 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1208565<location>CBE20: Consistency error affecting adjustable parametersMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, ...

  • Page 969

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1969SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1969SINAMICS alarms 208701<location>CAN: NMT state changeMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, ...

  • Page 970

    SINAMICS alarms Alarms970 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms970 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1208751<location>CAN: Telegram lossMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S120_DP, CU...

  • Page 971

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1971SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1971SINAMICS alarms 208754<location>CAN: Incorrect communications modeMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, ...

  • Page 972

    SINAMICS alarms Alarms972 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms972 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:For online operation, the appropriate COB-ID must be set invalid before mapping.Example:Mapping for RPDO 1 should be changed (p8710[0]).--> se...

  • Page 973

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1973SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1973SINAMICS alarms 208802<location>PROFIenergy not possible to switch off incremental encoder supplyMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, C...

  • Page 974

    SINAMICS alarms Alarms974 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms974 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1213001<location>Error in license checksumMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU_S_AC_PN, CU_S120...

  • Page 975

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1975SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1975SINAMICS alarms Remedy:- enter and activate the license key for options that require a license.- if necessary, de-activate unlicensed options.213100<location>Know-...

  • Page 976

    SINAMICS alarms Alarms976 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms976 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:An error was identified when checking the consistency of the protected files. As a consequence, the project on the memory card cannot be run.Faul...

  • Page 977

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1977SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1977SINAMICS alarms 230002<location>Power unit: DC link voltage, overvoltageMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, SERVO, S...

  • Page 978

    SINAMICS alarms Alarms978 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms978 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:The power unit has detected an undervoltage condition in the DC link.- line supply failure- line supply voltage below the permissible value.- lin...

  • Page 979

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1979SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1979SINAMICS alarms 230005<location>Power unit: Overload I2tMessage value:%1Drive object:VECTOR, VECTOR_ACReaction:OFF2Acknowledge:IMMEDIATELYCause:The power unit was ...

  • Page 980

    SINAMICS alarms Alarms980 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms980 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:- check the electrical cabinet design and cable routing for EMC compliance- for projects with the VECTOR drive object, check whether p0117 = 6 h...

  • Page 981

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1981SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1981SINAMICS alarms Bit 5: Inverter 4Bit 6: Inverter 5Bit 7: Inverter 6Bit 8: Rectifier 1Bit 9: Rectifier 2Remedy:Contact the manufacturer.230013<location>Power unit: ...

  • Page 982

    SINAMICS alarms Alarms982 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms982 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1- The motor is correctly connected, but the drive has stalled in U/f control. In this case, a current of 0 A is possibly measured in one phase due to a...

  • Page 983

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1983SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1983SINAMICS alarms The following applies to Motor Modules:- check the motor data and if required, recalculate the controller parameters (p0340 = 3). As an alternative, run ...

  • Page 984

    SINAMICS alarms Alarms984 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms984 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Additional cause for CU310/CUA31:- when the brake is applied, this causes the hardware DC current monitoring to respond.Additional cause for parallel s...

  • Page 985

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1985SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1985SINAMICS alarms Remedy:- adapt the load duty cycle.- check whether the fan is running.- check the fan elements.- check whether the ambient temperature is in the permissi...

  • Page 986

    SINAMICS alarms Alarms986 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms986 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1230027<location>Power unit: Precharging DC link time monitoringMessage value:Enable signals: %1, Status: %2Drive object:A_INF, A_INF_840, B_INF, ...

  • Page 987

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1987SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1987SINAMICS alarms Re 5):- carefully observe the permissible pre-charging frequency (refer to the appropriate Equipment Manual).Re 6):- check the total capacitance of the D...

  • Page 988

    SINAMICS alarms Alarms988 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms988 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Check the motor data and if required, recalculate the control parameters (p0340 = 3). As an alternative, run a motor data identification (p1910 ...

  • Page 989

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1989SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1989SINAMICS alarms 230035<location>Power unit: Air intake overtemperatureMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, SERVO, SER...

  • Page 990

    SINAMICS alarms Alarms990 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms990 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:- check whether the fan is running.- check the fan elements.- check whether the ambient temperature is in the permissible range.- check the moto...

  • Page 991

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1991SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1991SINAMICS alarms Fault value (r0949, interpret hexadecimal):yyxxxx hex: yy = channel, xxxx = voltage [0.1 V]yy = 0: 24 V power supplyyy = 1: 48 V power supplyRemedy:- Che...

  • Page 992

    SINAMICS alarms Alarms992 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms992 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1230042<location>Power unit: Fan operating time reached or exceededMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_8...

  • Page 993

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1993SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1993SINAMICS alarms 230044<location>Power unit: Overvolt 24/48 V alarmMessage value:Channel: %1, voltage: %2 [0.1 V]Drive object:SERVO, SERVO_840, SERVO_ACReaction:NON...

  • Page 994

    SINAMICS alarms Alarms994 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms994 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:- Check the power supply of the power unit.- carry out a POWER ON (power off/on) for the component.- replace the module if necessary.230046<l...

  • Page 995

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1995SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1995SINAMICS alarms Cause:The feedback signal from the external fan indicates a fault.- fan faulty, blocked.- feedback signal inaccurate.Remedy:- check the external fan and ...

  • Page 996

    SINAMICS alarms Alarms996 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms996 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1230053<location>FPGA data faultyMessage value:%1Drive object:All objectsReaction:NONEAcknowledge:POWER ONCause:The FPGA data of the power unit ar...

  • Page 997

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1997SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1997SINAMICS alarms Remedy:- check the line phase connection.- check the motor feeder cable connections.If there is no phase failure of the line or motor, then line asymmetr...

  • Page 998

    SINAMICS alarms Alarms998 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms998 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1230070<location>Cycle requested by the power unit module not supportedMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_I...

  • Page 999

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1999SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1999SINAMICS alarms 230073<location>Actual value/setpoint preprocessing no longer synchronousMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_I...

  • Page 1000

    SINAMICS alarms Alarms1000 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1000 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Additional causes for a parallel switching device (r0108.15 = 1):- a power unit has tripped (powered down) due to a ground fault.- the closed-loop ci...

  • Page 1001

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11001SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11001SINAMICS alarms For a parallel switching device (r0108.15 = 1) the following additionally applies:- check the ground fault monitoring thresholds (p0287).- check the se...

  • Page 1002

    SINAMICS alarms Alarms1002 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1002 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:- check the device supply voltage (p0210).- check the dimensioning of the line reactor.See also: p0210 (Drive unit line supply voltage)230600&...

  • Page 1003

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11003SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11003SINAMICS alarms 4: SI transition period STOP F to STOP A (p9658, p9858).5: SI enable Safe Brake Control (p9602, p9802).6: SI Motion enable, safety-relevant functions (...

  • Page 1004

    SINAMICS alarms Alarms1004 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1004 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1230620<location>SI MM: Safe Torque Off activeMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, SERVO, SERVO_840...

  • Page 1005

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11005SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11005SINAMICS alarms - de-select all drive functions that are not absolutely necessary.- reduce the number of drives.- check the electrical cabinet design and cable routing...

  • Page 1006

    SINAMICS alarms Alarms1006 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1006 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Operation with Safe Brake Module or Safe Brake Adapter:- check the Safe Brake Module or Safe Brake Adapter connection.- Replace the Safe Brake Module...

  • Page 1007

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11007SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11007SINAMICS alarms 230649<location>SI MM: Internal software errorMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, SERVO, SERVO_840...

  • Page 1008

    SINAMICS alarms Alarms1008 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1008 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Re fault value = 2003, 2005:- Carry out an acceptance test and generate an acceptance report.The procedure when carrying out an acceptance test as we...

  • Page 1009

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11009SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11009SINAMICS alarms 230655<location>SI MM: Align monitoring functionsMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, SERVO, SERVO_...

  • Page 1010

    SINAMICS alarms Alarms1010 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1010 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1- exit the safety commissioning mode (p0010 = 0).- save all parameters (p0977 = 1 or "copy RAM to ROM").- carry out a POWER ON (power off/o...

  • Page 1011

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11011SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11011SINAMICS alarms or:- use a Motor Module that supports the required function.- upgrade the Motor Module software.- upgrade the Control Unit software.Note:CU: Control Un...

  • Page 1012

    SINAMICS alarms Alarms1012 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1012 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA12 hex:- parameters p9500 and p9300 are not the same (if Safety message C30711 is displayed at the same time).Additional values:- defect before the la...

  • Page 1013

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11013SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11013SINAMICS alarms Cause:The monitoring function enabled in p9301 and p9801 is not supported by the currently set PROFIsafe telegram (p9811).Note:This fault does not resu...

  • Page 1014

    SINAMICS alarms Alarms1014 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1014 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1xxxx = 9801:yyyy = 1:If motion monitoring functions integrated in the drive (p9801.2 = 1) and extended functions without selection (p9801.5 = 1) are ...

  • Page 1015

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11015SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11015SINAMICS alarms 27: This hardware does not support onboard F-DI and F-DO.30: The firmware version of the Motor Module is older than the version of the Control Unit.33:...

  • Page 1016

    SINAMICS alarms Alarms1016 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1016 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1230685<location>SI Motion MM: Safely-Limited Speed limit value too highMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_...

  • Page 1017

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11017SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11017SINAMICS alarms Fault value (r0949, interpret decimal):Parameter number with the incorrect value.See also: p9301 (SI Motion enable safety functions (Motor Module))Reme...

  • Page 1018

    SINAMICS alarms Alarms1018 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1018 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1230701<location>SI Motion MM: STOP B initiatedMessage value:-Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:NONE (OFF3)Ackn...

  • Page 1019

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11019SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11019SINAMICS alarms 230707<location>SI Motion MM: Tolerance for safe operating stop exceededMessage value:-Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC...

  • Page 1020

    SINAMICS alarms Alarms1020 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1020 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:- remove the cause of the fault at the control.- carry out a diagnostics routine for messages C30714, C30715, C30716.This message can only be ...

  • Page 1021

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11021SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11021SINAMICS alarms 1001: Initialization error of watchdog timer.1003:Reference tolerance exceeded.When the user agreement is set, the difference between the new reference...

  • Page 1022

    SINAMICS alarms Alarms1022 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1022 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1230712<location>SI Motion MM: Defect in F-IO processingMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:NONEA...

  • Page 1023

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11023SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11023SINAMICS alarms Cause:The axis has moved past a parameterized position that is monitored by the "SLP" function.Message value (r9749, interpret decimal):10: S...

  • Page 1024

    SINAMICS alarms Alarms1024 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1024 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1230770<location>SI Motion MM: Discrepancy error affecting the fail-safe inputs/outputsMessage value:%1Drive object:SERVO, SERVO_AC, VECTOR, VEC...

  • Page 1025

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11025SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11025SINAMICS alarms Cause:The test stop for the fail-safe digital inputs (F-DI) and/or fail-safe digital outputs (F-DO) is presently being performed.Note:F-DI: Failsafe Di...

  • Page 1026

    SINAMICS alarms Alarms1026 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1026 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1DI expected states in table format:Test stop state: Expectation Mode 1 / Mode 2 / Mode 3 / Mode 45: -/1/1/-7: -/0/0/-9: -/0/1/-11: -/0/1/-13: -/1/1/-...

  • Page 1027

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11027SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11027SINAMICS alarms 230799<location>SI Motion MM: Acceptance test mode activeMessage value:-Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:NONEAc...

  • Page 1028

    SINAMICS alarms Alarms1028 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1028 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:A time slice overflow has occurred.Remedy:- carry out a POWER ON (power off/on) for all components.- upgrade firmware to later version.- contac...

  • Page 1029

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11029SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11029SINAMICS alarms 230810<location>Power unit: Watchdog timerMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, SERVO, SERVO_840, SER...

  • Page 1030

    SINAMICS alarms Alarms1030 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1030 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1230835<location>Power unit DRIVE-CLiQ: Cyclic data transfer errorMessage value:Component number: %1, fault cause: %2Drive object:A_INF, A_INF_8...

  • Page 1031

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11031SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11031SINAMICS alarms 66 (= 42 hex):Send error: The telegram buffer memory contains an error.67 (= 43 hex):Send error: The telegram buffer memory contains an error.Note rega...

  • Page 1032

    SINAMICS alarms Alarms1032 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1032 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1230851<location>Power unit DRIVE-CLiQ (CU): Sign-of-life missingMessage value:Component number: %1, fault cause: %2Drive object:A_INF, A_INF_84...

  • Page 1033

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11033SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11033SINAMICS alarms 16 (= 10 hex):The receive telegram is too early.17 (= 11 hex):CRC error and the receive telegram is too early.18 (= 12 hex):The telegram is shorter tha...

  • Page 1034

    SINAMICS alarms Alarms1034 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1034 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA133 (= 21 hex):The cyclic telegram has not been received.34 (= 22 hex):Timeout in the telegram receive list.64 (= 40 hex):Timeout in the telegram send...

  • Page 1035

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11035SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11035SINAMICS alarms 97 (= 61 hex):Time taken to exchange characteristic data too long.Note regarding the message value:The individual information is coded as follows in th...

  • Page 1036

    SINAMICS alarms Alarms1036 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1036 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1230899<location>Power unit: Unknown faultMessage value:New message: %1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, SERVO,...

  • Page 1037

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11037SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11037SINAMICS alarms 230919<location>Power unit: Temperature monitoring failedMessage value:%1Drive object:SERVO, SERVO_840, SERVO_ACReaction:NONEAcknowledge:NONECaus...

  • Page 1038

    SINAMICS alarms Alarms1038 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1038 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1230999<location>Power unit: Unknown alarmMessage value:New message: %1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, SERVO,...

  • Page 1039

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11039SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11039SINAMICS alarms Fault value (r0949, interpret decimal):Number of increments after POWER ON or since the last zero mark that was detected (4 increments = 1 encoder puls...

  • Page 1040

    SINAMICS alarms Alarms1040 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1040 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:Serial communication protocol transfer error between the encoder and evaluation module.Fault value (r0949, interpret binary):Bit 0: Alarm bit i...

  • Page 1041

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11041SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11041SINAMICS alarms Cause:The absolute encoder fault word supplies fault bits that have been set.Fault value (r0949, interpret binary):yyyyxxxx hex: yyyy = supplementary i...

  • Page 1042

    SINAMICS alarms Alarms1042 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1042 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:For fault value, bit 0 = 1:In the case of an EnDat encoder, F31111 may provide further details.231115<location>Encoder 1: Amplitude erro...

  • Page 1043

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11043SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11043SINAMICS alarms A signal level of 500 mV peak value corresponds to the numerical value 5333 hex = 21299 dec.Note:The analog values of the amplitude error are not measu...

  • Page 1044

    SINAMICS alarms Alarms1044 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1044 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:- check the tachometer feeder cable for interruptions.- check the grounding of the tachometer shielding.- if required, increase the maximum sp...

  • Page 1045

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11045SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11045SINAMICS alarms Cause:For the actual value sensing, an error was detected on the module.As a result of this error, it must be assumed that the actual value sensing sup...

  • Page 1046

    SINAMICS alarms Alarms1046 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1046 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1231125<location>Encoder 1: Amplitude error track A or B overcontrolledMessage value:A track: %1, B-track: %2Drive object:A_INF, A_INF_840, B_IN...

  • Page 1047

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11047SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11047SINAMICS alarms 231129<location>Encoder 1: Position difference, hall sensor/track C/D and A/B too largeMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_IN...

  • Page 1048

    SINAMICS alarms Alarms1048 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1048 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1231131<location>Encoder 1: Deviation, position incremental/absolute too largeMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, E...

  • Page 1049

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11049SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11049SINAMICS alarms Bit 17: Signal amplitude (--> F3x135, x = 1, 2, 3)Bit 18: Singleturn position 1 (--> F3x135, x = 1, 2, 3)Bit 19: Overvoltage (--> F3x135, x = ...

  • Page 1050

    SINAMICS alarms Alarms1050 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1050 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1231137<location>Encoder 1: Internal fault when determining the positionMessage value:Fault cause: %1 binDrive object:A_INF, A_INF_840, B_INF, B...

  • Page 1051

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11051SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11051SINAMICS alarms 231151<location>Encoder 1: Encoder speed for initialization AB too highMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, ENC, ENC_...

  • Page 1052

    SINAMICS alarms Alarms1052 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1052 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1231161<location>Encoder 1: Analog sensor channel B failedMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, ENC, ENC_840, S_INF, ...

  • Page 1053

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11053SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11053SINAMICS alarms The zero mark distance for the zero mark monitoring is set in p0425 (rotary encoder) or p0424 (linear encoder).Alarm value (r2124, interpret decimal):L...

  • Page 1054

    SINAMICS alarms Alarms1054 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1054 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:The encoder has reached one of its function limits. A service is recommended.Alarm value (r2124, interpret decimal):1 : Incremental signals3 : ...

  • Page 1055

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11055SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11055SINAMICS alarms Bit 4: SAR_converter error.Bit 5: Fault for the register data transfer.Bit 6: Internal error identified at the error pin (nErr).Bit 7: Temperature thre...

  • Page 1056

    SINAMICS alarms Alarms1056 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1056 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:The amplitude (root of A^2 + B^2) for encoder 1 exceeds the permissible tolerance.Alarm value (r2124, interpret hexadecimal):yyyyxxxx hex:yyyy ...

  • Page 1057

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11057SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11057SINAMICS alarms xxxx2: Maximum of the offset correction, track Bxxx1x: Minimum of the offset correction, track Axxx2x: Maximum of the offset correction, track Axx1xx: ...

  • Page 1058

    SINAMICS alarms Alarms1058 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1058 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1231429<location>Encoder 1: Position difference, hall sensor/track C/D and A/B too largeMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_...

  • Page 1059

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11059SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11059SINAMICS alarms Cause:For track A/B, pulses have been lost or too many have been counted. These pulses are presently being corrected.Alarm value (r2124, interpret deci...

  • Page 1060

    SINAMICS alarms Alarms1060 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1060 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:The input voltage of the analog sensor is outside the permissible limits.Alarm value (r2124, interpret decimal):1: Input voltage outside detect...

  • Page 1061

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11061SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11061SINAMICS alarms Cause:The position value has exceeded the permissible range of -0.5 ... +0.5.Alarm value (r2124, interpret decimal):1: Position value from the LVDT sen...

  • Page 1062

    SINAMICS alarms Alarms1062 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1062 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:When powered down, the drive/encoder was moved through a distance greater than was parameterized in the tolerance window. It is possible that t...

  • Page 1063

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11063SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11063SINAMICS alarms Remedy:Replace encoder.231800<location>Encoder 1: Group signalMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, ENC, ENC_840, S_INF...

  • Page 1064

    SINAMICS alarms Alarms1064 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1064 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1x = A:Time slice overflow of the average time slice.x = C:Time slice overflow of the slow time slice.yx = 3E7:Timeout when waiting for SYNO (e.g. une...

  • Page 1065

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11065SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11065SINAMICS alarms 231806<location>Encoder 1: Initialization errorMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, ENC, ENC_840, S_INF, S_INF_840, S...

  • Page 1066

    SINAMICS alarms Alarms1066 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1066 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:The serial number of the motor encoder of a synchronous motor has changed. The change was only checked for encoders with serial number (e.g. En...

  • Page 1067

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11067SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11067SINAMICS alarms 231813<location>Encoder 1: Hardware logic unit failedMessage value:Fault cause: %1 binDrive object:A_INF, A_INF_840, B_INF, B_INF_840, ENC, ENC_8...

  • Page 1068

    SINAMICS alarms Alarms1068 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1068 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1231835<location>Encoder 1 DRIVE-CLiQ: Cyclic data transfer errorMessage value:Component number: %1, fault cause: %2Drive object:A_INF, A_INF_84...

  • Page 1069

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11069SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11069SINAMICS alarms Cause:Fault detected on the DRIVE-CLiQ component concerned. Faulty hardware cannot be excluded.Fault cause:32 (= 20 hex):Error in the telegram header.3...

  • Page 1070

    SINAMICS alarms Alarms1070 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1070 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA111500 ... 11899: Calibration data from EEPROM incorrect.11900 ... 11999: Configuration data from EEPROM incorrect.12000 ... 12008: Communication with...

  • Page 1071

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11071SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11071SINAMICS alarms 9 (= 09 hex):The error bit in the receive telegram is set.16 (= 10 hex):The receive telegram is too early.17 (= 11 hex):CRC error and the receive teleg...

  • Page 1072

    SINAMICS alarms Alarms1072 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1072 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1231885<location>Encoder 1 DRIVE-CLiQ (CU): Cyclic data transfer errorMessage value:Component number: %1, fault cause: %2Drive object:A_INF, A_I...

  • Page 1073

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11073SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11073SINAMICS alarms 231887<location>Encoder 1 DRIVE-CLiQ (CU): Component faultMessage value:Component number: %1, fault cause: %2Drive object:A_INF, A_INF_840, B_INF...

  • Page 1074

    SINAMICS alarms Alarms1074 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1074 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1231896<location>Encoder 1 DRIVE-CLiQ (CU): Inconsistent component propertiesMessage value:Component number: %1Drive object:A_INF, A_INF_840, B_...

  • Page 1075

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11075SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11075SINAMICS alarms 231903<location>Encoder 1: I2C-BUS error occurredMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, ENC, ENC_840, S_INF, S_INF_840,...

  • Page 1076

    SINAMICS alarms Alarms1076 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1076 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:- check whether the connected encoder type matches the encoder that has been parameterized.- correct the parameter specified by the fault valu...

  • Page 1077

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11077SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11077SINAMICS alarms 231916<location>Encoder 1: Parameterization faultMessage value:Parameter: %1, supplementary information: %2Drive object:A_INF, A_INF_840, B_INF, ...

  • Page 1078

    SINAMICS alarms Alarms1078 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1078 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:When evaluating the temperature sensor, an error occurred.Fault cause:1 (= 01 hex):Wire breakage or sensor not connected (KTY: R > 1630 Ohm)...

  • Page 1079

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11079SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11079SINAMICS alarms 231950<location>Encoder 1: Internal software errorMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, ENC, ENC_840, S_INF, S_INF_840...

  • Page 1080

    SINAMICS alarms Alarms1080 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1080 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1232101<location>Encoder 2: Zero mark failedMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:OFF1 (IASC/DCBRAK...

  • Page 1081

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11081SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11081SINAMICS alarms Cause:Serial communication protocol transfer error between the encoder and evaluation module.Fault value (r0949, interpret binary):Bit 0: Alarm bit in ...

  • Page 1082

    SINAMICS alarms Alarms1082 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1082 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Bit 1: Signal amplitude too low.Bit 2: Position value incorrect.Bit 3: Encoder power supply overvoltage condition.Bit 4: Encoder power supply undervo...

  • Page 1083

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11083SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11083SINAMICS alarms 232115<location>Encoder 2: Amplitude error track A or B (A^2 + B^2)Message value:A track: %1, B-track: %2Drive object:SERVO, SERVO_840, SERVO_AC,...

  • Page 1084

    SINAMICS alarms Alarms1084 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1084 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1232117<location>Encoder 2: Inversion error signals A/B/RMessage value:Fault cause: %1 binDrive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTO...

  • Page 1085

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11085SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11085SINAMICS alarms Bit 3: Overcurrent condition for encoder power supply on cable resolver excitation positive.Bit 4: The 24 V power supply through the Power Module (PM) ...

  • Page 1086

    SINAMICS alarms Alarms1086 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1086 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1232123<location>Encoder 2: Signal level A/B unipolar outside toleranceMessage value:Fault cause: %1 binDrive object:SERVO, SERVO_840, SERVO_AC,...

  • Page 1087

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11087SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11087SINAMICS alarms xxxx = Amplitude, i.e. root from A^2 + B^2 (16 bits without sign)The nominal signal level of the encoder must lie in the range 375 mV to 600 mV (500 mV...

  • Page 1088

    SINAMICS alarms Alarms1088 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1088 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:- check that the encoder cables are routed in compliance with EMC.- check the plug connections- if the Hall sensor is used as an equivalent fo...

  • Page 1089

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11089SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11089SINAMICS alarms Bit 16: Lighting (--> F3x135, x = 1, 2, 3)Bit 17: Signal amplitude (--> F3x135, x = 1, 2, 3)Bit 18: Singleturn position 1 (--> F3x135, x = 1, ...

  • Page 1090

    SINAMICS alarms Alarms1090 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1090 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1232137<location>Encoder 2: Internal fault when determining the positionMessage value:Fault cause: %1 binDrive object:SERVO, SERVO_840, SERVO_AC...

  • Page 1091

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11091SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11091SINAMICS alarms 232152<location>Encoder 2: Maximum input frequency exceededMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:ENC...

  • Page 1092

    SINAMICS alarms Alarms1092 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1092 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1232163<location>Encoder 2: Analog sensor position value exceeds limit valueMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VEC...

  • Page 1093

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11093SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11093SINAMICS alarms 232405<location>Encoder 2: Temperature in the encoder evaluation inadmissibleMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VEC...

  • Page 1094

    SINAMICS alarms Alarms1094 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1094 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1232411<location>Encoder 2: Absolute encoder signals internal alarmsMessage value:Fault cause: %1 bin, additional information: %2Drive object:SE...

  • Page 1095

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11095SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11095SINAMICS alarms The nominal signal level of the encoder must lie in the range 375 mV to 600 mV (500 mV -25/+20 %).The response thresholds are < 230 mV (observe the ...

  • Page 1096

    SINAMICS alarms Alarms1096 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1096 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1232419<location>Encoder 2: Track A or B outside toleranceMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:NON...

  • Page 1097

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11097SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11097SINAMICS alarms Cause:The measured zero mark distance does not correspond to the parameterized zero mark distance.This alarm is triggered with active square-wave encod...

  • Page 1098

    SINAMICS alarms Alarms1098 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1098 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1232432<location>Encoder 2: Rotor position adaptation corrects deviationMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_...

  • Page 1099

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11099SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11099SINAMICS alarms 232460<location>Encoder 2: Analog sensor channel A failedMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:NONEA...

  • Page 1100

    SINAMICS alarms Alarms1100 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1100 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1232463<location>Encoder 2: Analog sensor position value exceeds limit valueMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VEC...

  • Page 1101

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11101SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11101SINAMICS alarms Cause:When powered down, the drive/encoder was moved through a distance greater than was parameterized in the tolerance window. It is possible that the...

  • Page 1102

    SINAMICS alarms Alarms1102 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1102 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1232800<location>Encoder 2: Group signalMessage value:-Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:OFF1 (IASC/DCBRAKE, NO...

  • Page 1103

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11103SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11103SINAMICS alarms 232804<location>Encoder 2: Checksum errorMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:OFF1 (IASC/DCBRAKE, N...

  • Page 1104

    SINAMICS alarms Alarms1104 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1104 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Bit 16: Internal fault - fault when reading a register (CAFE)Bit 17: Internal fault - fault when writing a register (CAFE)Bit 18: Internal fault: No ...

  • Page 1105

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11105SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11105SINAMICS alarms 232813<location>Encoder 2: Hardware logic unit failedMessage value:Fault cause: %1 binDrive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACR...

  • Page 1106

    SINAMICS alarms Alarms1106 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1106 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:A DRIVE-CLiQ communication error has occurred from the Control Unit to the encoder concerned. The nodes do not send and receive in synchronism....

  • Page 1107

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11107SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11107SINAMICS alarms 232845<location>Encoder 2 DRIVE-CLiQ: Cyclic data transfer errorMessage value:Component number: %1, fault cause: %2Drive object:SERVO, SERVO_840,...

  • Page 1108

    SINAMICS alarms Alarms1108 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1108 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Upgrade the firmware of the component involved.232860<location>Encoder 2 DRIVE-CLiQ (CU): Telegram errorMessage value:Component number: ...

  • Page 1109

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11109SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11109SINAMICS alarms Cause:The DRIVE-CLiQ communication from the DRIVE-CLiQ component involved to the Control Unit signals that the supply voltage has failed.Fault cause:9 ...

  • Page 1110

    SINAMICS alarms Alarms1110 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1110 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1232887<location>Encoder 2 DRIVE-CLiQ (CU): Component faultMessage value:Component number: %1, fault cause: %2Drive object:SERVO, SERVO_840, SER...

  • Page 1111

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11111SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11111SINAMICS alarms Cause:The properties of the DRIVE-CLiQ component (Sensor Module for encoder 2), specified by the fault value, have changed in an incompatible fashion w...

  • Page 1112

    SINAMICS alarms Alarms1112 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1112 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1232905<location>Encoder 2: Parameterization errorMessage value:Parameter: %1, supplementary information: %2Drive object:SERVO, SERVO_840, SERVO...

  • Page 1113

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11113SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11113SINAMICS alarms 1005:The type of measuring unit (incremental) is not supported by the EnDat 2.2 converter.1006:The maximum duration (31.25 µs) of the EnDat transfer w...

  • Page 1114

    SINAMICS alarms Alarms1114 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1114 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1232920<location>Encoder 2: Temperature sensor faultMessage value:Fault cause: %1, channel number: %2Drive object:SERVO, SERVO_840, SERVO_AC, VE...

  • Page 1115

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11115SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11115SINAMICS alarms Remedy:- Check the clamped tool.- Check the tolerance and if required, adapt (p5040).- Check the thresholds and if required, adapt (p5041).- Check anal...

  • Page 1116

    SINAMICS alarms Alarms1116 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1116 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:- check that the encoder cables are routed in compliance with EMC.- check the plug connections. check the encoder type (encoder with equidista...

  • Page 1117

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11117SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11117SINAMICS alarms 233110<location>Encoder 3: Serial communications errorMessage value:Fault cause: %1 binDrive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_AC...

  • Page 1118

    SINAMICS alarms Alarms1118 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1118 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1233111<location>Encoder 3: Absolute encoder internal faultMessage value:Fault cause: %1 bin, additional information: %2Drive object:SERVO, SERV...

  • Page 1119

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11119SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11119SINAMICS alarms Cause:The encoder sends a set error bit via the serial protocol.Fault value (r0949, interpret binary):Bit 0: Fault bit in the position protocol.Remedy:...

  • Page 1120

    SINAMICS alarms Alarms1120 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1120 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:- check that the encoder cables and shielding are routed in compliance with EMC.- check the plug connections- replace the encoder or encoder c...

  • Page 1121

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11121SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11121SINAMICS alarms Cause:A power supply fault was detected for encoder 3.Fault value (r0949, interpret binary):Bit 0: Undervoltage condition on the sense line.Bit 1: Over...

  • Page 1122

    SINAMICS alarms Alarms1122 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1122 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1233123<location>Encoder 3: Signal level A/B unipolar outside toleranceMessage value:Fault cause: %1 binDrive object:SERVO, SERVO_840, SERVO_AC,...

  • Page 1123

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11123SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11123SINAMICS alarms Cause:The amplitude (root of A^2 + B^2 or |A| + |B|) for encoder 3 exceeds the permissible tolerance.Fault value (r0949, interpret hexadecimal):yyyyxxx...

  • Page 1124

    SINAMICS alarms Alarms1124 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1124 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Fault value (r0949, interpret hexadecimal):yyyyxxxx hexyyyy: Determined mechanical zero mark position (can only be used for track C/D).xxxx: Deviatio...

  • Page 1125

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11125SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11125SINAMICS alarms Bit 4: Position value (reserved)Bit 5: Overvoltage (reserved)Bit 6: Undervoltage (reserved)Bit 7: Overcurrent (reserved)Bit 8: Battery (reserved)Bit 16...

  • Page 1126

    SINAMICS alarms Alarms1126 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1126 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1233137<location>Encoder 3: Internal fault when determining the positionMessage value:Fault cause: %1 binDrive object:SERVO, SERVO_840, SERVO_AC...

  • Page 1127

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11127SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11127SINAMICS alarms 233152<location>Encoder 3: Maximum input frequency exceededMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:ENC...

  • Page 1128

    SINAMICS alarms Alarms1128 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1128 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1233163<location>Encoder 3: Analog sensor position value exceeds limit valueMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VEC...

  • Page 1129

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11129SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11129SINAMICS alarms 233405<location>Encoder 3: Temperature in the encoder evaluation inadmissibleMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VEC...

  • Page 1130

    SINAMICS alarms Alarms1130 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1130 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1233411<location>Encoder 3: Absolute encoder signals internal alarmsMessage value:Fault cause: %1 bin, additional information: %2Drive object:SE...

  • Page 1131

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11131SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11131SINAMICS alarms The nominal signal level of the encoder must lie in the range 375 mV to 600 mV (500 mV -25/+20 %).The response thresholds are < 230 mV (observe the ...

  • Page 1132

    SINAMICS alarms Alarms1132 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1132 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1233419<location>Encoder 3: Track A or B outside toleranceMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:NON...

  • Page 1133

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11133SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11133SINAMICS alarms Cause:The measured zero mark distance does not correspond to the parameterized zero mark distance.This alarm is triggered with active square-wave encod...

  • Page 1134

    SINAMICS alarms Alarms1134 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1134 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1233432<location>Encoder 3: Rotor position adaptation corrects deviationMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_...

  • Page 1135

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11135SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11135SINAMICS alarms 233460<location>Encoder 3: Analog sensor channel A failedMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:NONEA...

  • Page 1136

    SINAMICS alarms Alarms1136 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1136 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1233463<location>Encoder 3: Analog sensor position value exceeds limit valueMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VEC...

  • Page 1137

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11137SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11137SINAMICS alarms Cause:When powered down, the drive/encoder was moved through a distance greater than was parameterized in the tolerance window. It is possible that the...

  • Page 1138

    SINAMICS alarms Alarms1138 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1138 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1233800<location>Encoder 3: Group signalMessage value:-Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:OFF1 (IASC/DCBRAKE, NO...

  • Page 1139

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11139SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11139SINAMICS alarms 233804<location>Encoder 3: Checksum errorMessage value:%1Drive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACReaction:OFF1 (IASC/DCBRAKE, N...

  • Page 1140

    SINAMICS alarms Alarms1140 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1140 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Bit 17: Internal fault - fault when writing a register (CAFE)Bit 18: Internal fault: No mid-voltage matching availableBit 19: Internal error - ADC ac...

  • Page 1141

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11141SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11141SINAMICS alarms 233813<location>Encoder 3: Hardware logic unit failedMessage value:Fault cause: %1 binDrive object:SERVO, SERVO_840, SERVO_AC, VECTOR, VECTOR_ACR...

  • Page 1142

    SINAMICS alarms Alarms1142 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1142 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:A DRIVE-CLiQ communication error has occurred from the Control Unit to the encoder concerned. The nodes do not send and receive in synchronism....

  • Page 1143

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11143SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11143SINAMICS alarms 233845<location>Encoder 3 DRIVE-CLiQ: Cyclic data transfer errorMessage value:Component number: %1, fault cause: %2Drive object:SERVO, SERVO_840,...

  • Page 1144

    SINAMICS alarms Alarms1144 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1144 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Upgrade the firmware of the component involved.233860<location>Encoder 3 DRIVE-CLiQ (CU): Telegram errorMessage value:Component number: ...

  • Page 1145

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11145SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11145SINAMICS alarms Cause:The DRIVE-CLiQ communication from the DRIVE-CLiQ component involved to the Control Unit signals that the supply voltage has failed.Fault cause:9 ...

  • Page 1146

    SINAMICS alarms Alarms1146 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1146 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1233887<location>Encoder 3 DRIVE-CLiQ (CU): Component faultMessage value:Component number: %1, fault cause: %2Drive object:SERVO, SERVO_840, SER...

  • Page 1147

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11147SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11147SINAMICS alarms Cause:The properties of the DRIVE-CLiQ component (Sensor Module for encoder 3), specified by the fault value, have changed in an incompatible fashion w...

  • Page 1148

    SINAMICS alarms Alarms1148 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1148 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1233905<location>Encoder 3: Parameterization errorMessage value:Parameter: %1, supplementary information: %2Drive object:SERVO, SERVO_840, SERVO...

  • Page 1149

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11149SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11149SINAMICS alarms 1006:The maximum duration (31.25 µs) of the EnDat transfer was exceeded.2001:The set combination of current controller cycle, DP cycle and Safety cycl...

  • Page 1150

    SINAMICS alarms Alarms1150 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1150 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1233920<location>Encoder 3: Temperature sensor faultMessage value:Fault cause: %1, channel number: %2Drive object:SERVO, SERVO_840, SERVO_AC, VE...

  • Page 1151

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11151SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11151SINAMICS alarms Remedy:- Check the clamped tool.- Check the tolerance and if required, adapt (p5040).- Check the thresholds and if required, adapt (p5041).- Check anal...

  • Page 1152

    SINAMICS alarms Alarms1152 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1152 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1234211<location>VSM: Temperature alarm threshold exceededMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, VEC...

  • Page 1153

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11153SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11153SINAMICS alarms Cause:A DRIVE-CLiQ communications error has occurred from the Control Unit to the Voltage Sensing Module (VSM).Fault cause:10 (= 0A hex):The sign-of-li...

  • Page 1154

    SINAMICS alarms Alarms1154 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1154 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:Internal parameter data is corrupted.Fault value (r0949, interpret hexadecimal):01: EEPROM access error.02: Too many blocks in the EEPROM.Remed...

  • Page 1155

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11155SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11155SINAMICS alarms 9 (= 09 hex):The error bit in the receive telegram is set.16 (= 10 hex):The receive telegram is too early.Note regarding the message value:The individu...

  • Page 1156

    SINAMICS alarms Alarms1156 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1156 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1234837<location>VSM DRIVE-CLiQ: Component faultMessage value:Component number: %1, fault cause: %2Drive object:A_INF, A_INF_840, B_INF, B_INF_8...

  • Page 1157

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11157SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11157SINAMICS alarms Remedy:- replace the Voltage Sensing Module (VSM).- if required, upgrade the firmware in the Voltage Sensing Module.- contact the Hotline.234851<loc...

  • Page 1158

    SINAMICS alarms Alarms1158 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1158 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA118 (= 12 hex):The telegram is shorter than that specified in the length byte or in the receive list and the receive telegram is too early.19 (= 13 he...

  • Page 1159

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11159SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11159SINAMICS alarms 33 (= 21 hex):The cyclic telegram has not been received.34 (= 22 hex):Timeout in the telegram receive list.64 (= 40 hex):Timeout in the telegram send l...

  • Page 1160

    SINAMICS alarms Alarms1160 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1160 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA196 (= 60 hex):Response received too late during runtime measurement.97 (= 61 hex):Time taken to exchange characteristic data too long.Note regarding ...

  • Page 1161

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11161SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11161SINAMICS alarms 234899<location>VSM: Unknown faultMessage value:New message: %1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, VECTOR, VECTOR_...

  • Page 1162

    SINAMICS alarms Alarms1162 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1162 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1234905<location>VSM: Parameter accessMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, VECTOR, VECTOR_ACReactio...

  • Page 1163

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11163SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11163SINAMICS alarms Remedy:- replace the firmware on the Voltage Sensing Module by an older firmware version (r0148).- upgrade the firmware on the Control Unit (r0018).235...

  • Page 1164

    SINAMICS alarms Alarms1164 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1164 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:A fault on the Terminal Module 54F (TM54) was acknowledged using the safe acknowledgement (P10006).An additional acknowledgement is also requir...

  • Page 1165

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11165SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11165SINAMICS alarms Slave fault state: (test actions)(test actions) | corresponding step for the master: (test actions)(test actions) | Description00 hex: (L1+OFF)(L2+ON) ...

  • Page 1166

    SINAMICS alarms Alarms1166 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1166 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1235015<location>TM54F: Motor Module replaced or configuration inconsistentMessage value:Fault cause: %1 binDrive object:A_INF, A_INF_840, B_INF...

  • Page 1167

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11167SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11167SINAMICS alarms 235016<location>TM54F: Net data communication with drive not establishedMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_...

  • Page 1168

    SINAMICS alarms Alarms1168 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1168 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1235051<location>TM54F: Defect in a monitoring channelMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, SERVO, ...

  • Page 1169

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11169SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11169SINAMICS alarms bb = C3 ... CA hex: new data to calculate the drive groups p10030 ... p10031bb = CB hex: p10032bb = CC hex: p10033bb = CD hex: p10009bb = CE ... CF dri...

  • Page 1170

    SINAMICS alarms Alarms1170 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1170 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1235054<location>TM54F: Temperature alarm threshold exceededMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, S...

  • Page 1171

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11171SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11171SINAMICS alarms Remedy:- check the safety-relevant parameters and if required, correct.- set the reference checksum to the actual checksum.- acknowledge the hardware r...

  • Page 1172

    SINAMICS alarms Alarms1172 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1172 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:The safety input terminals or output terminals show a different state longer than that parameterized in p10002.Fault value (r0949, interpret he...

  • Page 1173

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11173SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11173SINAMICS alarms Only for internal Siemens troubleshooting.Note:F-DI: Failsafe Digital InputF-DO: Failsafe Digital OutputRemedy:Check that the firmware version of the T...

  • Page 1174

    SINAMICS alarms Alarms1174 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1174 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1235208<location>TM: Temperature fault/alarm threshold channel 1 exceededMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF,...

  • Page 1175

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11175SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11175SINAMICS alarms 235210<location>TM: Temperature fault/alarm threshold channel 3 exceededMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S...

  • Page 1176

    SINAMICS alarms Alarms1176 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1176 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:The temperature measured using the temperature sensing of the Terminal Module (TM) (r4105[1]) has exceeded the threshold value to initiate this...

  • Page 1177

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11177SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11177SINAMICS alarms 235220<location>TM: Frequency limit reached for signal outputMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, SE...

  • Page 1178

    SINAMICS alarms Alarms1178 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1178 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1TM41 DAC: order no. = 6SL3055-0AA00-3PA1The following applies for TM41 SAC:- minimum/maximum value for p0408: 1000/8192The following applies for TM41...

  • Page 1179

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11179SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11179SINAMICS alarms 235225<location>TM: Zero mark synchronization held - encoder not in the ready stateMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840...

  • Page 1180

    SINAMICS alarms Alarms1180 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1180 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1235228<location>TM: Sampling time p4099[3] invalidMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, SERVO, SER...

  • Page 1181

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11181SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11181SINAMICS alarms 235230<location>TM: Hardware faultMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, ...

  • Page 1182

    SINAMICS alarms Alarms1182 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1182 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1235233<location>DRIVE-CLiQ component does not support functionMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840...

  • Page 1183

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11183SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11183SINAMICS alarms 235401<location>TM: Temperature fault/alarm threshold channel 5 exceededMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S...

  • Page 1184

    SINAMICS alarms Alarms1184 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1184 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1235403<location>TM: Temperature fault/alarm threshold channel 7 exceededMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF,...

  • Page 1185

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11185SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11185SINAMICS alarms 235405<location>TM: Temperature fault/alarm threshold channel 9 exceededMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S...

  • Page 1186

    SINAMICS alarms Alarms1186 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1186 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1235407<location>TM: Temperature fault/alarm threshold channel 11 exceededMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF...

  • Page 1187

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11187SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11187SINAMICS alarms Cause:The temperature (r4105[5]) measured using the temperature sensing of the Terminal Module 150 (TM150) has exceeded the threshold value to initiate...

  • Page 1188

    SINAMICS alarms Alarms1188 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1188 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1235414<location>TM: Temperature alarm threshold channel 8 exceededMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF...

  • Page 1189

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11189SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11189SINAMICS alarms 235417<location>TM: Temperature alarm threshold channel 11 exceededMessage value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_...

  • Page 1190

    SINAMICS alarms Alarms1190 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1190 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1235802<location>TM: Time slice overflowMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, SERVO, SERVO_840, SERV...

  • Page 1191

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11191SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11191SINAMICS alarms 235807<location>TM: Sequence control time monitoringMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, SERVO, SERV...

  • Page 1192

    SINAMICS alarms Alarms1192 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1192 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:A DRIVE-CLiQ communication error has occurred from the Control Unit to the Terminal Module involved. The nodes do not send and receive in synch...

  • Page 1193

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11193SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11193SINAMICS alarms Remedy:- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).- check the electrical cabinet design and cable routing for EMC compliance- if ...

  • Page 1194

    SINAMICS alarms Alarms1194 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1194 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Note regarding the message value:The individual information is coded as follows in the message value (r0949/r2124):0000yyxx hex: yy = component numbe...

  • Page 1195

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11195SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11195SINAMICS alarms 235875<location>TM DRIVE-CLiQ (CU): Supply voltage failedMessage value:Component number: %1, fault cause: %2Drive object:A_INF, A_INF_840, B_INF,...

  • Page 1196

    SINAMICS alarms Alarms1196 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1196 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:A DRIVE-CLiQ communication error has occurred from the Terminal Module involved (TM) to the Control Unit.Data were not able to be sent.Fault ca...

  • Page 1197

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11197SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11197SINAMICS alarms 235896<location>TM DRIVE-CLiQ (CU): Inconsistent component propertiesMessage value:Component number: %1Drive object:A_INF, A_INF_840, B_INF, B_IN...

  • Page 1198

    SINAMICS alarms Alarms1198 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1198 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1235904<location>TM: EEPROMMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, SERVO, SERVO_840, SERVO_AC, TM120, ...

  • Page 1199

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11199SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11199SINAMICS alarms Cause:The Terminal Module was not successfully initialized.Alarm value (r2124, interpret hexadecimal):01: TM17 or TM41 - incorrect configuration reques...

  • Page 1200

    SINAMICS alarms Alarms1200 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1200 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1235921<location>TM: Error temperature sensor channel 1Message value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, SERVO,...

  • Page 1201

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11201SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11201SINAMICS alarms 235924<location>TM: Error temperature sensor channel 4Message value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, SERVO, S...

  • Page 1202

    SINAMICS alarms Alarms1202 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1202 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1235927<location>TM: Error temperature sensor channel 7Message value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, SERVO,...

  • Page 1203

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11203SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11203SINAMICS alarms 235930<location>TM: Error temperature sensor channel 10Message value:%1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, SERVO, ...

  • Page 1204

    SINAMICS alarms Alarms1204 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1204 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1235999<location>TM: Unknown alarmMessage value:New message: %1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF, S_INF_840, SERVO, SERVO_8...

  • Page 1205

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11205SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11205SINAMICS alarms Cause:The 24 V power supply on the DRIVE-CLiQ Hub Module has exceeded the fault threshold.Fault value (r0949, interpret decimal):Actual operating volta...

  • Page 1206

    SINAMICS alarms Alarms1206 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1206 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:A DRIVE-CLiQ communications error has occurred from the Control Unit to the DRIVE-CLiQ Hub Module involved.Fault cause:10 (= 0A hex):The sign-o...

  • Page 1207

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11207SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11207SINAMICS alarms Remedy:- check whether the permissible ambient temperature for the component is maintained.- replace the DRIVE-CLiQ Hub Module.236820<location>Hu...

  • Page 1208

    SINAMICS alarms Alarms1208 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1208 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA164 (= 40 hex):Timeout in the telegram send list.Note regarding the message value:The individual information is coded as follows in the message value ...

  • Page 1209

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11209SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11209SINAMICS alarms 236845<location>Hub DRIVE-CLiQ: Cyclic data transfer errorMessage value:Component number: %1, fault cause: %2Drive object:A_INF, A_INF_840, B_INF...

  • Page 1210

    SINAMICS alarms Alarms1210 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1210 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA16 (= 06 hex):The address of the power unit in the telegram and in the receive list do not match.9 (= 09 hex):The error bit in the receive telegram is...

  • Page 1211

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11211SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11211SINAMICS alarms Cause:DRIVE-CLiQ communication error from DRIVE-CLiQ Hub Module in question to the Control Unit.The nodes do not send and receive in synchronism.Fault ...

  • Page 1212

    SINAMICS alarms Alarms1212 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1212 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA167 (= 43 hex):Send error: The telegram buffer memory contains an error.96 (= 60 hex):Response received too late during runtime measurement.97 (= 61 h...

  • Page 1213

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11213SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11213SINAMICS alarms 236899<location>Hub: Unknown faultMessage value:New message: %1Drive object:A_INF, A_INF_840, B_INF, B_INF_840, HUB, S_INF, S_INF_840, SERVO, SER...

  • Page 1214

    SINAMICS alarms Alarms1214 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1214 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1237001<location>HF damping module: overcurrentMessage value:Fault cause: %1 binDrive object:SERVO, SERVO_840, SERVO_ACReaction:OFF2Acknowledge:...

  • Page 1215

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11215SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11215SINAMICS alarms Remedy:- check whether the fan is running.- check the fan elements.- check whether the ambient temperature is in the permissible range.Notice:This faul...

  • Page 1216

    SINAMICS alarms Alarms1216 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1216 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Contact the manufacturer.Note:HF choke module (reactor module)HF Damping Module237024<location>HF Damping Module: Overtemperature therma...

  • Page 1217

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11217SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11217SINAMICS alarms 237034<location>HF Damping Module: Internal overtemperatureMessage value:%1Drive object:SERVO, SERVO_840, SERVO_ACReaction:NONEAcknowledge:NONECa...

  • Page 1218

    SINAMICS alarms Alarms1218 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1218 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1237041<location>HF Damping Module: 24 V undervoltage alarmMessage value:%1Drive object:SERVO, SERVO_840, SERVO_ACReaction:NONEAcknowledge:NONEC...

  • Page 1219

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11219SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11219SINAMICS alarms Remedy:- check the 24 V DC voltage supply of the HF Damping Module.- carry out a POWER ON (power off/on) for the component.- replace the module if nece...

  • Page 1220

    SINAMICS alarms Alarms1220 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1220 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:The temperature of the HF Damping Module heat sink has exceeded the permissible limit value.- insufficient cooling, fan failure.- overload.- am...

  • Page 1221

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11221SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11221SINAMICS alarms 237312<location>HF Choke Module: Overtemperature or fan failureMessage value:-Drive object:SERVO, SERVO_840, SERVO_ACReaction:NONEAcknowledge:NON...

  • Page 1222

    SINAMICS alarms Alarms1222 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1222 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1237800<location>HF Damping Module: Group signalMessage value:-Drive object:SERVO, SERVO_840, SERVO_ACReaction:NONEAcknowledge:NONECause:The HF ...

  • Page 1223

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11223SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11223SINAMICS alarms Remedy:Replace the module.Note:HF Damping Module237820<location>HF Damping Module: Telegram errorMessage value:Component number: %1, fault cause:...

  • Page 1224

    SINAMICS alarms Alarms1224 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1224 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA164 (= 40 hex):Timeout in the telegram send list.Note regarding the message value:The individual information is coded as follows in the message value ...

  • Page 1225

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11225SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11225SINAMICS alarms 237845<location>HF Damping Module: Cyclic data transmission errorMessage value:Component number: %1, fault cause: %2Drive object:SERVO, SERVO_840...

  • Page 1226

    SINAMICS alarms Alarms1226 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1226 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1237860<location>HF Damping Module (CU): Telegram errorMessage value:Component number: %1, fault cause: %2Drive object:SERVO, SERVO_840, SERVO_A...

  • Page 1227

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11227SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11227SINAMICS alarms 9 (= 09 hex):The power supply voltage for the components has failed.Note regarding the message value:The individual information is coded as follows in ...

  • Page 1228

    SINAMICS alarms Alarms1228 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1228 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1237887<location>HF Damping Module (CU): Component faultedMessage value:Component number: %1, fault cause: %2Drive object:SERVO, SERVO_840, SERV...

  • Page 1229

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11229SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11229SINAMICS alarms Cause:The properties of the DRIVE-CLiQ component (HF Damping Module), specified by the fault value, have changed in an incompatible fashion with respec...

  • Page 1230

    SINAMICS alarms Alarms1230 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1230 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1237950<location>HF Damping Module: Internal software errorMessage value:%1Drive object:SERVO, SERVO_840, SERVO_ACReaction:OFF2Acknowledge:POWER...

  • Page 1231

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11231SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11231SINAMICS alarms Cause:A fault has occurred at the drive object at the DRIVE-CLiQ socket X101.Fault value (r0949, interpret decimal):First fault that has occurred for t...

  • Page 1232

    SINAMICS alarms Alarms1232 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1232 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1240100<location>Alarm at DRIVE-CLiQ socket X100Message value:%1Drive object:All objectsReaction:NONEAcknowledge:NONECause:An alarm has occurred...

  • Page 1233

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11233SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11233SINAMICS alarms 240104<location>Alarm at DRIVE-CLiQ socket X104Message value:%1Drive object:All objectsReaction:NONEAcknowledge:NONECause:An alarm has occurred a...

  • Page 1234

    SINAMICS alarms Alarms1234 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1234 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1240820<location>CX32 DRIVE-CLiQ: Telegram errorMessage value:Component number: %1, fault cause: %2Drive object:All objectsReaction:OFF2Acknowle...

  • Page 1235

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11235SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11235SINAMICS alarms 240835<location>CX32 DRIVE-CLiQ: Cyclic data transfer errorMessage value:Component number: %1, fault cause: %2Drive object:All objectsReaction:OF...

  • Page 1236

    SINAMICS alarms Alarms1236 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1236 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA167 (= 43 hex):Send error: The telegram buffer memory contains an error.Note regarding the message value:The individual information is coded as follow...

  • Page 1237

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11237SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11237SINAMICS alarms 2 (= 02 hex):Telegram is shorter than specified in the length byte or in the receive list.3 (= 03 hex):Telegram is longer than specified in the length ...

  • Page 1238

    SINAMICS alarms Alarms1238 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1238 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1240885<location>CX32 DRIVE-CLiQ (CU): Cyclic data transfer errorMessage value:Component number: %1, fault cause: %2Drive object:All objectsReac...

  • Page 1239

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11239SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11239SINAMICS alarms 35 (= 23 hex):Receive error: The telegram buffer memory contains an error.66 (= 42 hex):Send error: The telegram buffer memory contains an error.67 (= ...

  • Page 1240

    SINAMICS alarms Alarms1240 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1240 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:The conductivity of the cooling liquid has exceeded the selected fault threshold (p0269[2]).See also: p0261 (Cooling unit, starting time 2), p0...

  • Page 1241

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11241SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11241SINAMICS alarms 249155<location>Cooling unit: Power Stack Adapter, firmware version too oldMessage value:-Drive object:A_INF, A_INF_840, B_INF, B_INF_840, S_INF,...

  • Page 1242

    SINAMICS alarms Alarms1242 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1242 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Cause:Conductivity monitoring is set for the cooling liquid (r0267.7, from p0266[7]).See also: p0261 (Cooling unit, starting time 2), p0262 (Cooling ...

  • Page 1243

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11243SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11243SINAMICS alarms 249201<location>Excitation group signal alarmMessage value:-Drive object:VECTOR, VECTOR_ACReaction:NONEAcknowledge:NONECause:The "excitation...

  • Page 1244

    SINAMICS alarms Alarms1244 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1244 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1250003<location>COMM BOARD: Alarm 3Message value:Info. 1: %1, info. 2: %2Drive object:A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, ...

  • Page 1245

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11245SINAMICS alarms AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11245SINAMICS alarms 250006<location>COMM BOARD: Alarm 6Message value:Info. 1: %1, info. 2: %2Drive object:A_INF, A_INF_840, B_INF, B_INF_840, CU_LINK, CU_S_AC_DP, CU...

  • Page 1246

    SINAMICS alarms Alarms1246 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SINAMICS alarms Alarms1246 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1

  • Page 1247

    7AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11247PLC alarms400102Delete DB 2 in the PLC and restartDefinitions:The DB created by the basic program and the existing DB differ in size.Reaction:Alarm display.Remedy:Displayed DB must be deleted via STEP7. Possibly max. program size of the us...

  • Page 1248

    PLC alarms Alarms1248 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1Remedy:Displayed DB must be deleted via STEP7. Possibly max. program size of the user program exceeded.Program Continuation:Internal400120Delete DB 20 in the PLC and restartDefinitions:The DB created by the basic program and the...

  • Page 1249

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11249PLC alarms 400126Delete DB 26 in the PLC and restartDefinitions:The DB created by the basic program and the existing DB differ in size.Reaction:Alarm display.Remedy:Displayed DB must be deleted via STEP7. Possibly max. program size of the u...

  • Page 1250

    PLC alarms Alarms1250 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1400132Delete DB 32 in the PLC and restartDefinitions:The DB created by the basic program and the existing DB differ in size.Reaction:Alarm display.Remedy:Displayed DB must be deleted via STEP7. Possibly max. program size of the ...

  • Page 1251

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11251PLC alarms 400138Delete DB 38 in the PLC and restartDefinitions:The DB created by the basic program and the existing DB differ in size.Reaction:Alarm display.Remedy:Displayed DB must be deleted via STEP7. Possibly max. program size of the u...

  • Page 1252

    PLC alarms Alarms1252 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1400144Delete DB 44 in the PLC and restartDefinitions:The DB created by the basic program and the existing DB differ in size.Reaction:Alarm display.Remedy:Displayed DB must be deleted via STEP7. Possibly max. program size of the ...

  • Page 1253

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11253PLC alarms 400150Delete DB 50 in the PLC and restartDefinitions:The DB created by the basic program and the existing DB differ in size.Reaction:Alarm display.Remedy:Displayed DB must be deleted via STEP7. Possibly max. program size of the u...

  • Page 1254

    PLC alarms Alarms1254 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1400156Delete DB 56 in the PLC and restartDefinitions:The DB created by the basic program and the existing DB differ in size.Reaction:Alarm display.Remedy:Displayed DB must be deleted via STEP7. Possibly max. program size of the ...

  • Page 1255

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11255PLC alarms 400171Delete DB 71 in the PLC and restartDefinitions:The DB created by the basic program and the existing DB differ in size.Reaction:Alarm display.Remedy:Displayed DB must be deleted via STEP7. Possibly max. program size of the u...

  • Page 1256

    PLC alarms Alarms1256 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1400201PLC STOP due to DB loading in the RUN state: DB%ZParameters:%Z = Data blockDefinitions:An existing DB was reloaded in the RUN state.Reaction:Alarm display.Remedy:Restart required.Program Continuation:Switch control OFF - O...

  • Page 1257

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11257PLC alarms Reaction:Alarm display.Remedy:Increase FB1 parameter for the NCK runup timeout NCRunupTimeout. Switch the control OFF - ONProgram Continuation:Internal400252Error in internal communication with NCKDefinitions:An error has occured...

  • Page 1258

    PLC alarms Alarms1258 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1400257Error in internal communication with NCK2Definitions:An error has occured during data transmission between the PLC and the NCK. (FM-NC only)Reaction:Alarm display.Remedy:NCK restartProgram Continuation:Internal400260Failur...

  • Page 1259

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11259PLC alarms 400265Pointer parameter machine control panel 2 incorrectDefinitions:A pointer is incorrect in the MCP 2 parameter range.Reaction:Alarm display.Remedy:Correct the PLC configuration in the FB1 parameters.Program Continuation:Switc...

  • Page 1260

    PLC alarms Alarms1260 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1400271Direct keys 1 communication error, internal error code: %ZDefinitions:Communication error between CP and PLC.Reaction:Alarm display.Remedy:Check OpKey parameterProgram Continuation:Internal400272Direct keys 2 communication...

  • Page 1261

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11261PLC alarms 400551Fault on MPI/DP busDefinitions:Error detected on I/O busReaction:Alarm display.Remedy:Check I/Os, rectify I/O faultProgram Continuation:Internal400552Fault on DP busDefinitions:Error detected on I/O busReaction:Alarm displa...

  • Page 1262

    PLC alarms Alarms1262 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1400604Set change with M06 in the machine dataDefinitions:With the magazine type used (box magazine, chain), changing is possible only with M06. If necessary, also check for impermissible settings at revolver magazines.Reaction:A...

  • Page 1263

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11263PLC alarms 401006FC 10 system error 0x8086Definitions:System error SFC52 has occurred.Reaction:Alarm display.Remedy:Restart, contact the Siemens AG A&D MC Hotline with the error text. Program Continuation:Switch control OFF - ON.401007F...

  • Page 1264

    PLC alarms Alarms1264 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1401901Parameter BAGNo impermissible in FC19Definitions:The parameterized mode group, channel does not exist.Reaction:Alarm display.Remedy:Correct the parameter.Program Continuation:Switch control OFF - ON.401902Parameter ChanNo ...

  • Page 1265

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11265PLC alarms 402601Parameter BAGNo impermissible in FC26Definitions:The parameterized mode group, channel does not exist.Reaction:Alarm display.Remedy:Correct the parameter.Program Continuation:Switch control OFF - ON.402602Parameter ChanNo i...

  • Page 1266

    PLC alarms Alarms1266 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1403073Delete DB 1073 in the PLC and restartDefinitions:The DB created by the basic program and the existing DB differ in size.Reaction:Alarm display.Remedy:Displayed DB must be deleted via STEP7. Possibly max. program size of th...

  • Page 1267

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11267PLC alarms 410150Area in M group decoder list is too largeDefinitions:Number of M groups in PLC too large.Reaction:Alarm display.Remedy:Reduce the number of groupsProgram Continuation:Internal410151Magazine data for tool management missing ...

  • Page 1268

    PLC alarms Alarms1268 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1410903M:N: HMI 2 does not respond to displacementDefinitions:The HMI that is to be switched over does not respondReaction:Alarm display.Remedy:Reactuate channel menu on HMIProgram Continuation:Internal410904M:N: HMI 2 does not g...

  • Page 1269

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11269PLC alarms 411502Incorrect basic PLC program versionDefinitions:FB 15 does not match the basic program used.Reaction:Alarm display.Remedy:Load the basic program that matches the NCK version.Program Continuation:Internal411503Error in the ha...

  • Page 1270

    PLC alarms Alarms1270 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1428603Module failure of the DP masterDefinitions:OB82 or OB86 has been triggered.Reaction:Alarm display.Remedy:Rectify the cause of the error displayedProgram Continuation:Switch control OFF - ON.428604Failure of a DP slaveDefin...

  • Page 1271

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11271PLC alarms 428621Failure of expansion unitDefinitions:OB82 or OB86 has been triggered.Reaction:Alarm display.Remedy:Rectify the cause of the error displayedProgram Continuation:Switch control OFF - ON.428622Restoration of expansion unit, di...

  • Page 1272

    PLC alarms Alarms1272 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1428627Restoration of DP slave, parameterization error, bus: %2, slave: %1Definitions:OB82 or OB86 has been triggered.Reaction:Alarm display.Remedy:Rectify the cause of the error displayedProgram Continuation:Switch control OFF -...

  • Page 1273

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11273PLC alarms Remedy:Rectify the cause of the error displayedProgram Continuation:Switch control OFF - ON.428634Restoration of PROFINET device, parameterization error, device %ZDefinitions:OB82 or OB86 has been triggered.Reaction:Alarm display...

  • Page 1274

    PLC alarms Alarms1274 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1810005Operational state sequence event, error analysis via STEP7 requiredDefinitions:Reduced PLC error message. STEP7 is required for exact analysis.Reaction:Alarm display.Remedy:Diagnose with STEP7.Program Continuation:Internal...

  • Page 1275

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11275PLC alarms 830000Message: HiGraph group no. %A graph no. %N status %ZDefinitions:-Reaction:Alarm display.Remedy:-Program Continuation:Internal

  • Page 1276

    PLC alarms Alarms1276 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1

  • Page 1277

    8AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11277System responses8.1System reactions to SINUMERIK alarmsIdentifierCOMPBLOCKWITHREORGEffectsBlock preparation has detected an error, which can be rectified by modifying the program. Reorganization is performed after a program modification....

  • Page 1278

    System responses8.1 System reactions to SINUMERIK alarmsAlarms1278 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1IdentifierNOREADY | BAGREACTIONVIEWEffectsMode group ready off: Active fast braking (i.e. with maximum braking current) of the drives in this mode group, the controller enable of the ...

  • Page 1279

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11279System responses8.1 System reactions to SINUMERIK alarmsIdentifierSHOWALARMAUTOEffectsThe alarm is displayed whenever bit 0 of machine data ENABLE_ALARM_MASK is set. The reaction should be set whenever an alarm should only occur during auto...

  • Page 1280

    System responses8.2 Cancel criteria for alarmsAlarms1280 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA18.2Cancel criteria for alarmsIdentifierCANCELCLEAREffectsThe alarm is cleared in any channel when the Cancel key is pressed. It is also cleared by the Start part program key.• Clear the alarm...

  • Page 1281

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11281System responses8.3 System reactions for SINAMICS alarms8.3System reactions for SINAMICS alarmsIdentifierNOCLEAREffectsThe clear information is only required for the internal pseudo alarm number EXBSAL_NOMOREALARMS.DesignationNONEResponseNo...

  • Page 1282

    System responses8.3 System reactions for SINAMICS alarmsAlarms1282 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1DesignationOFF3ResponseBrake along the OFF3 deceleration ramp followed by pulse disableDescriptionClosed loop speed control (p1300 = 20, 21)• n_set=0 is input immediately to brake t...

  • Page 1283

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11283System responses8.3 System reactions for SINAMICS alarmsAcknowledging faultsSpecifies the default method of acknowledging faults after the cause has been removed.Reference to SINAMICS parametersIn the "Cause" and "Remedy"...

  • Page 1284

    System responses8.3 System reactions for SINAMICS alarmsAlarms1284 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1

  • Page 1285

    AAlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11285Appendix AA.1List of abbreviationsAbbreviationSource of abbreviationMeaningADI4Analog Drive Interface for 4 axesACAdaptive ControlALMActive Line ModuleInfeed module for drivesASAutomation SystemASCIIAmerican Standard Code for Information I...

  • Page 1286

    Appendix AA.1 List of abbreviationsAlarms1286 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1CSBCentral Service BoardPLC moduleCTSClear To SendSignal from serial data interfacesCUTCOMCutter radius compensation Tool radius compensationDBData blockData block in the PLCDBBData-block byte Data block ...

  • Page 1287

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11287Appendix AA.1 List of abbreviationsFIPOFine InterPOlatorFMFunction ModuleFM-NCFunction Module Numerical ControlNumerical ControlFPUFloating-point unitFloating Point UnitFRAFrame blockFRAMEData setCoordinate conversion with the components wo...

  • Page 1288

    Appendix AA.1 List of abbreviationsAlarms1288 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1LEDLight Emitting DiodeLight Emitting DiodeLFLine FeedPMSLSBLeast Significant BitLeast significant bitLUDLocal User DataUser dataMACMedia Access ControlMAINMain programMain program (OB1, PLC)MBMegabyteMCI...

  • Page 1289

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11289Appendix AA.1 List of abbreviationsPNPROFINETPOPOWER ONPOUProgram Organization UnitUnit in the PLC user programPPUPanel Processing UnitPanel-based controlPTPPoint-to-pointPoint-to-PointPZDProcess data for drivesQECQuadrant Error Compensatio...

  • Page 1290

    Appendix AA.1 List of abbreviationsAlarms1290 Diagnostics Manual, 03/2013, 6FC5398-6BP40-3BA1SYNACTSYNACT synchronized actionSynchronized ActionTBTerminal Board (SINAMICS)TEATesting Data Active Identifier for machine dataTCPTool Center PointTool tipTCUThin Client UnitTEATesting Data ActiveIdentif...

  • Page 1291

    AlarmsDiagnostics Manual, 03/2013, 6FC5398-6BP40-3BA11291Appendix AA.2 OverviewA.2Overview

x