    Installation InstructionsIndustrial MonitorsCatalog Numbers 6186-M12AL, 6186-M12ALTR, 6186-M15AL, 6186-M15SS, 6186-M15ALTR, 6186-M15SSTR, 6186-MALTC, 6186-M17AL, 6186-M17SS, 6186-M17ALTR, 6186-M17SSTR, 6186-M17ALTC, 6186-M19AL, 6186-M19SS, 6186-M19ALTR, 6186-M19SSTRAbout This PublicationThis docu...

  • Page 2

    2 Industrial MonitorsPublication 6186M-IN001L-EN-P - July 2008Important User InformationSolid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publi...

  • Page 3

    Industrial Monitors 3Publication 6186M-IN001L-EN-P - July 2008Hazardous LocationsThis equipment is suitable for hazardous locations specified on the product nameplate:• Class I, Division 2 Groups A, B, C, D.• Class II, Division 2 Groups F, G.• Class III, Division 1.• nonhazardous loca...

  • Page 4

    4 Industrial MonitorsPublication 6186M-IN001L-EN-P - July 2008Environnements dangereuxCet équipement peut être utilisé dans les environnements suivants :• Classe I, Division 2, Groupes A, B, C et D .• Classe II, Division 2, Groupes F et G .• Classe III, Division 1 .• non dangereux....

  • Page 5

    Industrial Monitors 5Publication 6186M-IN001L-EN-P - July 2008European Union Directive Compliance This product meets the European Union Directive requirements when installed within the European Union or EEA regions and has the CE mark. A copy of the Declaration of Conformity is available at ...

  • Page 6

    6 Industrial MonitorsPublication 6186M-IN001L-EN-P - July 2008Environment and Enclosure InformationReview the information on enclosures and environments before installing the product. ATTENTIONEnvironment and EnclosureThis equipment is intended for use in a Pollution Degree 2 industrial envir...

  • Page 7

    Industrial Monitors 7Publication 6186M-IN001L-EN-P - July 2008Before You BeginBefore unpacking the product, inspect the shipping carton for damage. If damage is visible, immediately contact the shipper and request assistance. Otherwise, proceed with unpacking.Keep the original packing materia...

  • Page 8

    8 Industrial MonitorsPublication 6186M-IN001L-EN-P - July 2008Installation GuidelinesFollow these guidelines to make sure your product provides safe and reliable service.• The installation site must have sufficient power.• The enclosure must have sufficient space around air inlets and out...

  • Page 9

    Industrial Monitors 9Publication 6186M-IN001L-EN-P - July 2008Installing the MonitorThere are various ways to install the monitors.• Panel mount• Rack mount• Bench or tabletop mountReview each mounting type and product dimensions before installation.Panel MountingThe monitors install di...

  • Page 10

    10 Industrial MonitorsPublication 6186M-IN001L-EN-P - July 2008Mounting GuidelinesObserve these guidelines when installing the monitor in a panel.• Confirm that there is adequate space behind the panel.– Allow a minimum of 51 mm (2.0 in.) around the back, sides, and bottom, and 77 mm (3.0...

  • Page 11

    Industrial Monitors 11Publication 6186M-IN001L-EN-P - July 2008Mount the Monitor in a PanelFollow these directions to mount the monitor in a panel.1. Cut the panel opening by using the appropriate cutout dimensions.2. Attach the cables to the monitor if access to the rear of the monitor will ...

  • Page 12

    12 Industrial MonitorsPublication 6186M-IN001L-EN-P - July 20086. Tighten the clips gradually, one at a time, in the specified sequence, beginning with the center clips and continuing to the corner clips.Repeat this process at least three times until the clips are hand-tight and the gasket is...

  • Page 13

    Industrial Monitors 13Publication 6186M-IN001L-EN-P - July 2008Mounting GuidelinesObserve these guidelines when installing the monitor in a rack.• The height of the cabinet must accommodate the monitor’s panel height.• The depth of the cabinet must accommodate the monitor’s depth plus...

  • Page 14

    14 Industrial MonitorsPublication 6186M-IN001L-EN-P - July 2008Bench or Tabletop MountingUse the optional bench/tabletop adapter for monitors, catalog number 6189V-MBA, to mount your monitor on a bench or tabletop arm.Mounting GuidelinesObserve these guidelines when installing the monitor on ...

  • Page 15

    Industrial Monitors 15Publication 6186M-IN001L-EN-P - July 2008Product DimensionsThe product dimensions for the monitors are in mm (in.). 1200M MonitorMounting Clip Slots for Panel Mounting315 (12.40)224 (8.82)110 (4.33)110 (4.33)340 (13.39)8 (0.31)31.20 (1.23)56.10 (2.21)235 (9.25)260 (10.2...

  • Page 16

    16 Industrial MonitorsPublication 6186M-IN001L-EN-P - July 20081500M MonitorMounting Clip Slots for Panel Mounting29.5 (1.16)383.6 (15.10)281.9 (11.10)160 (6.30)409.2 (16.11)308.6 (12.15)140 (5.51)282.6 (11.13)58(2.28)10 (0.39)160 (6.30)58 (2.8)68(2.67)

  • Page 17

    Industrial Monitors 17Publication 6186M-IN001L-EN-P - July 20081700M MonitorMounting Clip Slots for Panel Mounting422 (16.63)326.25 (12.85)150 (5.91)150 (5.91)10 (0.39)68.10(2.68)30.0 (1.18)356 (14.03)58.10 (2.29)160 (6.30)328 )12.92)452 (17.81)58.10 (2.29)

  • Page 18

    18 Industrial MonitorsPublication 6186M-IN001L-EN-P - July 20081900M Monitor447 (17.60)320 (12.60)116 (4.57)110 (4.33)482.60 (19.0073.10 (2.88)360 (14.17)120 (4.72)Mounting Clip Slots for Panel Mounting399.30 (15.73)116 (4.57)120 (4.72)33.6 (1.32)10.0(0.39)

  • Page 19

    Industrial Monitors 19Publication 6186M-IN001L-EN-P - July 2008Monitor ConnectionsUse the connectors on the rear of the monitor to connect to:• analog video source (HD-15 VGA connector).• digital video source (DVI connector).• serial port on computer for touchscreen interface.• power ...

  • Page 20

    20 Industrial MonitorsPublication 6186M-IN001L-EN-P - July 2008Connect to an Analog Video SourceAll monitors support analog video. Your monitor is shipped with a high-quality analog video cable. Use this video cable to connect a computer to the monitor.Follow these steps to connect the monito...

  • Page 21

    Industrial Monitors 21Publication 6186M-IN001L-EN-P - July 2008Connect to a Digital Video SourceAll monitors support digital video. Use a digital video cable to connect a computer to the DVI connector on the monitor. This cable is not supplied, but can be purchased as an accessory.Follow thes...

  • Page 22

    22 Industrial MonitorsPublication 6186M-IN001L-EN-P - July 2008Connect AC PowerWith the AC power adapter, the monitor can use a single-phase AC power supply, providing 90…264V AC at 47…63 Hz.Power must be available at a grounded outlet nearby. Whenever possible, connect the monitor to the...

  • Page 23

    Industrial Monitors 23Publication 6186M-IN001L-EN-P - July 2008Connect DC PowerThe monitors connect to a DC power source using a DC input terminal block.Follow these steps to connect power to the monitor.1. Turn off the main power switch or breaker.2. Route the power wires from your DC power ...

  • Page 24

    24 Industrial MonitorsPublication 6186M-IN001L-EN-P - July 2008Secure the CablesSecure cables to the three cable restraints on the monitor using the supplied cable ties. Securing the cables provides strain relief on the cables and avoids loose, hanging cables.Backlight Assembly DisposalShip o...

  • Page 25

    Industrial Monitors 25Publication 6186M-IN001L-EN-P - July 2008SpecificationsIndustrial Monitors - 1200M, 1500M, 1700M, 1900MAttributeValueDisplay Display typeColor active matrix TFTTouch screen description 1200M, 1900M 1500M, 1700M Resistive antiglare Resistive antiglare or capacitive antigl...

  • Page 26

    26 Industrial MonitorsPublication 6186M-IN001L-EN-P - July 2008ElectricalInput voltage, AC90…264V AC, autorangingLine frequency47…63 HzPower consumption 1200M 1500M 1700M, 1900M 13.5 W 18 W 36 WInput voltage, DC 1200M, 1500M, 1700M, 1900M 9…36V DCMechanicalDimensions (HxWxD), approx. 12...

  • Page 27

    Industrial Monitors 27Publication 6186M-IN001L-EN-P - July 2008Additional ResourcesFor additional information on the industrial monitors, refer to Industrial Monitors, publication 6186M-UM001.You can view or download publications at actionURI(http://literature.rockwellautomation.com):http://l...

  • Page 28

    Publication 6186M-IN001L-EN-P - July 2008PN-29059Supersedes Publication 6186M-IN001K-EN-P - July 2007Copyright © 2008 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.Rockwell Automation SupportactionURI(http://support.rockwellautomation.com):RockwellactionURI(http://support.r...